Sunlight VRLA battery catalogue (SPA, AccuForce, SPB, SPG, SPHR, STB FA, SVT)
Original title Sunlight VRLA Catalogue: SPHR, p.8
Sunlight Group
Sunlight Group's VRLA catalogue: SPA, AccuForce, SPB, SPG (gel), SPHR (high rate), STB FA, SVT (2 V, 100-3600 Ah) and S series; SPB/SPG up to 12 years and SVT up to 15 years design life.
On this page
Overview
The catalogue presents Sunlight Group's valve-regulated lead-acid (VRLA) battery family over twelve pages: SPA, AccuForce, SPB, SPG, SPHR, STB FA, SVT, AccuForce S and SPG S. For each series it gives applications (UPS, telecommunications, emergency power, automation and measuring, transport signalling, security systems) and a model table. The tables list nominal voltage, nominal capacity, length, width, height, weight and terminal type.
The SPA is a general-purpose AGM series: 6, 8 and 12 V, 1.3-28 Ah (C20, 1.75 V per cell, 25 °C), from 0.28 kg to 8.6 kg. AccuForce is 12 V 33-200 Ah (C10, 1.80 V per cell, 25 °C), and the SPB is an 'advanced' series in the same capacity range with design life up to 12 years. The SPG is a gel-electrolyte series with a wide temperature range: 12 V 26-250 Ah, with an SPG S variant. All series offer maintenance-free, leak and spill-proof containers and optional UL94 V-0 flame retardant material.
The SPHR is a high-rate AGM series for UPS with short discharge times: in 12 V models from 33W to 1000W, power for a 10-minute discharge (1.67 V per cell, 25 °C) runs from 33.6 W to 1013 W (SPHR 12-1000W: 238 Ah, 64.5 kg). The STB FA is a front-access AGM series that fits common 19/21/23 inch telecom cabinets in 48 V strings and uses a flame retardant ABS case.
The SVT is a very long-life series of 2 V cells: 100, 150, 200, 250, 300, 320, 400, 500, 600, 800, 1000, 1200, 1500, 2000, 3000 and 3600 Ah, with design life up to 15 years. The SVT 2-100 weighs 5.3 kg and the SVT 2-3600 215 kg; capacity is at C10, 1.80 V per cell, 25 °C. The SVT is recommended for standby and cyclic use, including power generation, emergency lighting and security systems.
Key points
- Series: SPA, AccuForce, SPB, SPG (gel), SPHR (high rate), STB FA, SVT, AccuForce S, SPG S.
- SPA: 6/8/12 V, 1.3-28 Ah (C20); 0.28-8.6 kg.
- AccuForce and SPB: 12 V, 33-200 Ah (C10); SPB design life up to 12 years.
- SPG (gel): 12 V, 26-250 Ah; wide temperature range; standby and cyclic use.
- SPHR: 12 V, 10 min power 33.6 W/cell (12-33W) to 1013 W/cell (12-1000W).
- STB FA: front-access AGM, 19/21/23 inch telecom cabinets, 48 V strings; UL94 V-0 ABS case.
- SVT: 2 V, 100-3600 Ah; design life up to 15 years; weight 5.3-215 kg.
- All maintenance-free, leak and spill-proof containers; optional UL94 V-0 flame retardant.
Using it in design
- In UPS battery selection use the SPHR 10-minute W per cell value (1.67 V per cell, 25 °C); do not base autonomy directly on C10 capacity.
- For long-autonomy or long design-life systems, compare 2 V SVT cells (up to 15 years) with 12 V monoblocs (SPB up to 12 years) on cost and life.
- For wide-temperature or cyclic duty consider the SPG gel series, and compare the size and weight of AGM and gel at the same capacity.
- Take rack loading from the table weights (for example 215 kg for the SVT 2-3600) and dimensions.
- Capacity is quoted at C20 (SPA) and C10 (other series), so convert to the same discharge rate before comparing series.
Who should read it
Electrical designers selecting VRLA batteries for UPS and telecom power systems, engineers planning battery rooms and procurement teams.
Document contents
- SPA
- AccuForce
- SPB
- SPG
- SPHR
- STB FA
- SVT
- AccuForce S
- SPG S
Publication details
- Authors
- Sunlight Group
- Publisher
- Sunlight Group
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Sunlight Group Sunlight VRLA Catalogue: SPHR, p.8. Sunlight Group. https://www.sunlight-group.com/files/153300/1763040391-sunlight_vrla_batteries_brochure.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.