TAB OPzV valve regulated stationary battery range

Original title TAB OPzV official product table

TAB

TAB's OPzV range comprises valve-regulated lead-acid 2 V cells with tubular positive plates: 200-3000 Ah, short-circuit current 1724-17525 A, internal resistance 1.22-0.12 mOhm, weight 18-227 kg.

On this page

Overview

The page presents the OPzV stationary battery range of Slovenia-based TAB. The range combines the benefits of recombination technology (virtually no maintenance because of very low gas emission) with the advantages of conventional vented batteries with positive tubular plates (long life and excellent cycling capability). The manufacturer lists the features as safe, versatile, reliable, minimal gassing and deep-discharge resistant, and calls it an ideal energy source for many standby applications.

The technical table lists 2 V cells from 4 OPzV 200 to 24 OPzV 3000 in fourteen models, with nominal capacity of 200, 250, 300, 350, 420, 490, 600, 800, 1000, 1200, 1500, 2000, 2500 and 3000 Ah. Capacities are given to EN/IEC 60896-21 at 20 °C for 10, 5, 3 and 1 hour discharges (end voltage 1.80, 1.77, 1.75 and 1.67 V per cell respectively). For the 4 OPzV 200 the values are 222, 187, 164 and 120 Ah.

The table also gives internal resistance (Ri) and short-circuit current (Isc): 1.22 mOhm and 1724 A for the 4 OPzV 200, and 0.12 mOhm and 17525 A for the 24 OPzV 3000. Length runs from 103 mm to 576 mm, width from 191 to 482 mm depending on cell type, and height from 354/380 mm to 771/796 mm. Weight is 18 kg for the 4 OPzV 200 and 227 kg for the 24 OPzV 3000, with 2, 4, 6 or 8 poles.

The table footnote states that dimensions and weights are within standard production tolerances, that weight tolerance is +/-5%, that electrical values are approximate and that technical changes may be made without notice. The page also links to TAB's TOPzS and TOPLA DIN product pages.

Key points

  1. 2 V OPzV cells: fourteen models, 200-3000 Ah nominal (4 OPzV 200 to 24 OPzV 3000).
  2. Capacity given per EN/IEC 60896-21 at 20 °C for 10 h (1.80 V), 5 h (1.77 V), 3 h (1.75 V) and 1 h (1.67 V).
  3. 4 OPzV 200: 222/187/164/120 Ah; Ri 1.22 mOhm; Isc 1724 A; 18 kg.
  4. 24 OPzV 3000: Ri 0.12 mOhm; Isc 17525 A; 227 kg.
  5. Length 103-576 mm, height from 354/380 to 771/796 mm.
  6. Recombination technology: very low gassing, virtually maintenance-free; tubular positive plates: long life and cycling capability.
  7. Weight tolerance +/-5%; electrical values are approximate.

Using it in design

  • Read the load/time relationship directly from the 1, 3, 5 and 10 hour discharge columns; do not size a short-duration UPS load from nominal capacity alone.
  • Include the tabulated short-circuit current (Isc, 1724-17525 A) and internal resistance (Ri) in the DC distribution selectivity and protective device breaking capacity calculation.
  • Enter cell weight (18-227 kg) and dimensions in the rack and floor loading calculation; the tallest cell is 796 mm.
  • Even though valve-regulated, calculate battery room ventilation to the applicable standard.
  • Given the +/-5% weight tolerance and approximate electrical values, ask for a manufacturer-approved drawing at design stage.

Who should read it

Electrical engineers and procurement teams selecting stationary batteries for power plants, substations, telecom and data-centre DC systems.

Document contents

  1. TAB OPzV batteries (description and features)
  2. Technical table: capacity at 10, 5, 3 and 1 h, internal resistance, short-circuit current, dimensions, weight
  3. Notes on tolerances

Publication details

Authors
TAB
Publisher
TAB
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

TAB TAB OPzV official product table. TAB. https://www.tab.si/products/opzv/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.