Ultracell UHR High Rate series: full specifications
Ultracell
Ultracell UHR is a VRLA series built for high-current, short-duration UPS discharge; the 12 V group has 25 models from 2.2 to 250 Ah, with design life of 5 years for small units and 12 years for large ones.
On this page
Overview
Ultracell's UHR series is a family of valve-regulated lead-acid (VRLA) batteries designed for UPS and critical backup applications that need rapid, high-current discharge. The product page emphasises sealed maintenance-free construction, superior lead plates for conductivity and stability, and high power delivery in compact case sizes. The series includes 2 V, 6 V and 12 V groups.
The specification table on the page lists 25 models for the 12 V group, from UHR2.2-12 to UHR250-12. For each model it gives 20-hour capacity, 10-hour capacity, W15 power (at 1.67 V per cell), length, width, height, total height, weight, terminal type and design life. UHR2.2-12 is 2.2 Ah (20 hour), 70 x 47.5 x 97 mm, 0.78 kg and 5 years; UHR9-12 is 9 Ah, 34.6 W15 and 5 years.
The large models have a 12-year design life: UHR100-12 is C10 100 Ah, W15 400, 330 x 173 x 216 mm, 31.2 kg, terminal F11; UHR250-12 is C10 250 Ah, W15 750, 522 x 268 x 226 mm, 79.5 kg, terminal F11. C20 and C10 capacities are separate columns; small models quote C20 and large ones C10. The basis of the W15 column is not stated explicitly in the document, so it should not be used as watts per cell.
Key points
- UHR series: VRLA for high-current short discharge; 2 V, 6 V and 12 V groups; the 12 V group has 25 models (UHR2.2-12 to UHR250-12).
- Design life is 5 years for small models and 12 years for UHR100-12 and UHR250-12.
- UHR100-12: C10 100 Ah, W15 400, 330 x 173 x 216 mm, 31.2 kg, terminal F11.
- UHR250-12: C10 250 Ah, W15 750, 522 x 268 x 226 mm, 79.5 kg, terminal F11.
- UHR9-12: 9 Ah (20 hour), W15 34.6, 151 x 65 x 93.5 mm, 2.52 kg, terminal F2/F1.
- The table has separate columns for C20, C10, W15 (1.67 V/cell) and total height.
- Sealed maintenance-free design for UPS, emergency power and industrial backup.
Using it in design
- When selecting UPS batteries, compare the W15 value (15 minutes, 1.67 V per cell) with your load and time tables; Ah alone is not enough.
- Do not mix C20 and C10 capacities; small and large models are published on different bases.
- For battery room layout use length, width, total height (with terminal) and weight (79.5 kg for UHR250-12).
- Tie the design life (5 and 12 years) to the maintenance and replacement plan, and verify the temperature effect with the manufacturer.
Who should read it
Engineers designing UPS battery systems and battery purchasing teams.
Document contents
- UHR series overview
- Key features
- 12 V specification table
Publication details
- Authors
- Ultracell
- Publisher
- Ultracell
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Ultracell Ultracell UHR High Rate series: full specifications. Ultracell. https://ultracell.co.uk/uhr-high-rate-series
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.