Yiğit Akü AGM batteries (YD series) technical table
Original title Yiğit Akü AGM Aküler (YD Serisi): p.1
Yiğit Akü
The Yiğit Akü YD series is a 12 V AGM battery family for UPS, EPS and emergency power systems; the table covers 12 models from YD12-4.5 to YD12-200, 4.5 to 200 Ah (C10), with dimensions and weights.
On this page
Overview
Yiğit Akü's YD series AGM batteries target general-purpose use plus uninterruptible power supply (UPS), electrical power system (EPS), emergency backup, alarm and security systems, communication power, DC power supply and automatic control systems. The manufacturer highlights a special valve and sealing technology, a PbCaSn alloy for plate grids (less gassing and self-discharge) and a high-quality AGM separator that prevents micro short-circuits.
For each model the technical table gives length, width, two height values (H1 and H2; H2 is the total height including terminals), C20 and C10 capacity, terminal type and weight (±3%). Small blocks are named by C20 rating and large blocks by C10: YD12-4.5 (C20 4.50 Ah, C10 4.19 Ah, 90 x 70 mm, H 101-107 mm, 1.39 kg), YD12-9 (C20 9.00 Ah, C10 8.51 Ah, 151 x 65 mm, 2.52 kg) and YD12-26 (C20 26 Ah, C10 24.60 Ah, 7.80 kg).
Medium and large models are named on C10: YD12-40 (C10 40 Ah, 197 x 165 mm, H 170 mm, 12.00 kg), YD12-65 (C10 65 Ah, 348 x 167 mm, 18.50 kg), YD12-100 (C10 100 Ah, 330 x 173 mm, H 212-220 mm, 30.60 kg), YD12-150 (C10 150 Ah, 483 x 170 mm) and YD12-200 (C10 200 Ah, C20 208 Ah, 522 x 240 mm, H 218-224 mm). The C20 and C10 values of the same block differ, so a design must use one basis.
Key points
- YD series 12 V AGM; for UPS, EPS, emergency power, alarm/security, communication and DC power.
- PbCaSn alloy plate grid; high-quality AGM separator; special valve and sealing structure.
- YD12-4.5: C20 4.50 Ah / C10 4.19 Ah; 90 x 70 mm; H 101-107 mm; 1.39 kg.
- YD12-9: C20 9.00 Ah / C10 8.51 Ah; 151 x 65 mm; 2.52 kg.
- YD12-40: C10 40 Ah (C20 42 Ah); 197 x 165 mm; 12.00 kg.
- YD12-100: C10 100 Ah (C20 105 Ah); 330 x 173 mm; H 212-220 mm; 30.60 kg; terminal T11.
- YD12-200: C10 200 Ah (C20 208 Ah); 522 x 240 mm; H 218-224 mm; terminal T11.
- Weight tolerance ±3%; H2 is height including terminals.
Using it in design
- In UPS battery string sizing, keep the C10 or C20 basis of each model consistent; small and large models are named on different bases.
- For the battery rack use length, width and H2 (including terminals); weight tolerance is ±3%.
- When building series strings of 12 V monoblocks, reflect the terminal type (T1, T2, T6, T11, T12 and so on) in the choice of connectors.
- Do not derive autonomy from this table; request load-time tables from the manufacturer.
Who should read it
Electrical engineers designing UPS battery systems and battery purchasing teams.
Document contents
- General features
- Applications
- 12 V AGM battery dimension and capacity table (YD12-4.5 to YD12-200)
Publication details
- Authors
- Yiğit Akü
- Publisher
- Yiğit Akü
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Yiğit Akü Yiğit Akü AGM Aküler (YD Serisi): p.1. Yiğit Akü. https://yigitaku.com/BackOffice/UploadImage/ProductSubCategory/AGM-Ak%C3%BCler-YD-Serisi-tr.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.