Baykee HTT-10kS High-Frequency On-Line Double-Conversion UPS (10 kVA/8 kW)
Original title Baykee HTT-10kS/10kH/15kS/15kH/20kS/20kH technical table
Aerospace Baykee
Baykee HTT-series 10/15/20 kVA high-frequency three-phase in/out on-line UPS: input PF ≥0.99, over 89% AC-mode efficiency and 0 ms transfer from line to battery.
On this page
Overview
The product page presents the Baykee HTT-10kS (10 kVA / 8 kW) and the 15 kVA/12 kW and 20 kVA/16 kW members of the family; the S and H suffixes denote standard and long-run battery options. The page also lists HTT models from 30 to 300 kVA. The unit is a high-frequency on-line double-conversion UPS with three-phase-plus-neutral input and output. Features include cold start, intelligent battery management, self-diagnosis at start-up, RS232 and an optional USB/SNMP card.
Input: low-line loss at 110 Vac (phase-neutral, 50% load) and 176 Vac (100% load), high-line loss at 300 Vac (50% load) and 276 Vac (100% load), frequency 46-54 Hz (50 Hz system), input power factor 0.99 or above at full load. Output: 208/220/230/240 Vac, regulation ±1%, THD below 2% on linear and below 5% on non-linear load, crest factor up to 3:1. Overload in AC mode is 10 min at 100-110% and 1 min at 110-130%; in battery mode 30 s at 100-110%.
Transfer time is 0 ms from line to battery and from inverter to bypass (below 4 ms interruption if phase lock fails) and under 10 ms to ECO. Efficiency is above 89% in AC mode and 86-88% in battery mode. The standard battery is 20 x 12 V/9 Ah (18-20 adjustable), charge voltage 273 Vdc, charge current 1-2 A; the long-run model uses 4 A. For 10 kVA the S unit is 815 x 250 x 826 mm and 109 kg and the H unit 592 x 250 x 826 mm and 38 kg. Operation is 0-40 °C; above 25 °C battery life falls.
Key points
- HTT-10kS/H 10 kVA / 8 kW; HTT-15 15 kVA / 12 kW; HTT-20 20 kVA / 16 kW; the page lists models up to 300 kVA.
- Input PF ≥0.99 (full load); input loss voltage 110-300 Vac (50% load), 176-276 Vac (100% load).
- Output 208/220/230/240 Vac ±1%; THD ≤2% (linear) and ≤5% (non-linear); crest factor 3:1.
- AC-mode overload: 100-110% 10 min, 110-130% 1 min, >130% 1 s.
- Transfer: line to battery 0 ms; inverter to bypass 0 ms; ECO <10 ms.
- Efficiency in AC mode >89%; in battery mode >86-88%.
- Standard battery 20 x 12 V/9 Ah, 273 Vdc, 90% recharge in 9 hours.
- 10 kVA S: 815 x 250 x 826 mm, 109 kg; H: 592 x 250 x 826 mm, 38 kg.
- 0-40 °C; battery life falls above 25 °C.
Using it in design
- Carry input PF ≥0.99 into generator and cable sizing for small rooms.
- The standard 9 Ah battery bank gives short backup; choose the long-run (H) model if an autonomy target exists.
- With efficiency near 89%, add the heat loss (about 0.9 kW at 10 kVA) to the cooling calculation.
- Design the battery room to stay below 25 °C.
Who should read it
Designers selecting three-phase UPS units for small rooms and edge sites.
Document contents
- Features
- Specifications: input, output, transfer, efficiency
- Battery
- Physical and environment
- Other HTT models (30-300 kVA)
Publication details
- Authors
- Aerospace Baykee
- Publisher
- Aerospace Baykee
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Aerospace Baykee Baykee HTT-10kS/10kH/15kS/15kH/20kS/20kH technical table. Aerospace Baykee. https://www.baykee.com/product/high-frequency-online-double-conversion-ups-10kva-8kw-htt-10ks/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.