Baykee HTT-10kS High-Frequency On-Line Double-Conversion UPS (10 kVA/8 kW)

Original title Baykee HTT-10kS/10kH/15kS/15kH/20kS/20kH technical table

Aerospace Baykee

Baykee HTT-series 10/15/20 kVA high-frequency three-phase in/out on-line UPS: input PF ≥0.99, over 89% AC-mode efficiency and 0 ms transfer from line to battery.

On this page

Overview

The product page presents the Baykee HTT-10kS (10 kVA / 8 kW) and the 15 kVA/12 kW and 20 kVA/16 kW members of the family; the S and H suffixes denote standard and long-run battery options. The page also lists HTT models from 30 to 300 kVA. The unit is a high-frequency on-line double-conversion UPS with three-phase-plus-neutral input and output. Features include cold start, intelligent battery management, self-diagnosis at start-up, RS232 and an optional USB/SNMP card.

Input: low-line loss at 110 Vac (phase-neutral, 50% load) and 176 Vac (100% load), high-line loss at 300 Vac (50% load) and 276 Vac (100% load), frequency 46-54 Hz (50 Hz system), input power factor 0.99 or above at full load. Output: 208/220/230/240 Vac, regulation ±1%, THD below 2% on linear and below 5% on non-linear load, crest factor up to 3:1. Overload in AC mode is 10 min at 100-110% and 1 min at 110-130%; in battery mode 30 s at 100-110%.

Transfer time is 0 ms from line to battery and from inverter to bypass (below 4 ms interruption if phase lock fails) and under 10 ms to ECO. Efficiency is above 89% in AC mode and 86-88% in battery mode. The standard battery is 20 x 12 V/9 Ah (18-20 adjustable), charge voltage 273 Vdc, charge current 1-2 A; the long-run model uses 4 A. For 10 kVA the S unit is 815 x 250 x 826 mm and 109 kg and the H unit 592 x 250 x 826 mm and 38 kg. Operation is 0-40 °C; above 25 °C battery life falls.

Key points

  1. HTT-10kS/H 10 kVA / 8 kW; HTT-15 15 kVA / 12 kW; HTT-20 20 kVA / 16 kW; the page lists models up to 300 kVA.
  2. Input PF ≥0.99 (full load); input loss voltage 110-300 Vac (50% load), 176-276 Vac (100% load).
  3. Output 208/220/230/240 Vac ±1%; THD ≤2% (linear) and ≤5% (non-linear); crest factor 3:1.
  4. AC-mode overload: 100-110% 10 min, 110-130% 1 min, >130% 1 s.
  5. Transfer: line to battery 0 ms; inverter to bypass 0 ms; ECO <10 ms.
  6. Efficiency in AC mode >89%; in battery mode >86-88%.
  7. Standard battery 20 x 12 V/9 Ah, 273 Vdc, 90% recharge in 9 hours.
  8. 10 kVA S: 815 x 250 x 826 mm, 109 kg; H: 592 x 250 x 826 mm, 38 kg.
  9. 0-40 °C; battery life falls above 25 °C.

Using it in design

  • Carry input PF ≥0.99 into generator and cable sizing for small rooms.
  • The standard 9 Ah battery bank gives short backup; choose the long-run (H) model if an autonomy target exists.
  • With efficiency near 89%, add the heat loss (about 0.9 kW at 10 kVA) to the cooling calculation.
  • Design the battery room to stay below 25 °C.

Who should read it

Designers selecting three-phase UPS units for small rooms and edge sites.

Document contents

  1. Features
  2. Specifications: input, output, transfer, efficiency
  3. Battery
  4. Physical and environment
  5. Other HTT models (30-300 kVA)

Publication details

Authors
Aerospace Baykee
Publisher
Aerospace Baykee
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Aerospace Baykee Baykee HTT-10kS/10kH/15kS/15kH/20kS/20kH technical table. Aerospace Baykee. https://www.baykee.com/product/high-frequency-online-double-conversion-ups-10kva-8kw-htt-10ks/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.