BPE MPP Series 10-20 kVA Three-Phase Rack Mount Online UPS
Original title BPE MPP Series 10–20 kVA 3:3 catalogue, p.2 technical specifications
Best Power Equipments (BPE)
BPE MPP series 10, 15 and 20 kVA (kW = kVA) 3U rack three-phase in/out online UPS: VFI-SS-111, 96% double-conversion and 99% or higher ECO efficiency, up to 4 units in parallel.
On this page
Overview
The catalogue presents the BPE MPP models MPP3310L30, MPP3315L30 and MPP3320L30: three-phase input and output, 10/15/20 kVA with kW equal to kVA, meaning output power factor 1. The unit is true online double conversion (VFI-SS-111), DSP controlled, with pure sine output; it can be installed as rack or tower. Features include 3-stage charging, frequency conversion mode, ECO mode, EPO, parallel expansion up to 4 units, 30-50 battery configurations, fan speed regulation by load, automatic static bypass, cold and soft start and generator compatibility.
Technical data: input 380/400/415 Vac (3P+N+PE), 228-480 Vac, 40-70 Hz, PF ≥0.99. Output regulation ±1%, crest factor 3:1, harmonic distortion ≤1%, transfer time zero. Overload is <110% for 60 min, 110-125% for 10 min, 125-150% for 1 min and >150% for 200 ms. Efficiency is 96% in double conversion and 99% or higher in ECO mode. The battery is VRLA or lithium compatible, ±180 to ±300 Vdc, 30-50 pieces, maximum charge current 20 A.
Physical data: 443 x 580 x 133 mm (3U), net weight 29 kg for 10-15 kVA and 33 kg for 20 kVA. Operation is 0-50 °C, humidity 0-95% non-condensing, altitude 1500 m, noise below 55-58 dBA at 1 m. Standards are IEC/EN 62040-1, -2, -3 and CE. Communication is RS232, RS485, EPO and a parallel port; SNMP, dry contact and IoT are optional. The catalogue also lists battery pack models.
Key points
- MPP3310L30, MPP3315L30, MPP3320L30: 10, 15, 20 kVA (kW = kVA); 3U; up to 4 units in parallel.
- VFI-SS-111; pure sine; zero transfer time.
- Input 380/400/415 Vac, 228-480 Vac, 40-70 Hz, PF ≥0.99.
- Output regulation ±1%, THD ≤1%, crest factor 3:1.
- Efficiency: 96% double conversion, ≥99% ECO.
- Overload: 60 min <110%, 10 min 110-125%, 1 min 125-150%, 200 ms >150%.
- Battery ±180 to ±300 Vdc, 30-50 pieces, VRLA or lithium; charge current up to 20 A.
- 443 x 580 x 133 mm; 29-33 kg; 0-50 °C; altitude 1500 m.
Using it in design
- In rack-based small data rooms, carry the 3U height and 29-33 kg weight into the rack load calculation.
- Limit paralleling to 4 units and plan redundancy (N+1) accordingly.
- When using ECO efficiency in energy models, account for the changed protection class in that mode.
- With lithium batteries, keep to the 30-50 piece range and the 20 A charge limit.
- Record input PF ≥0.99 and the wide input window in generator compatibility notes.
Who should read it
Electrical designers selecting rack-mount three-phase UPS units for small data rooms and edge sites.
Document contents
- Features and rear panel
- Technical specifications MPP 10-20 kVA
- Technical specifications of battery packs
Publication details
- Authors
- Best Power Equipments (BPE)
- Publisher
- Best Power Equipments (BPE)
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Best Power Equipments (BPE) BPE MPP Series 10–20 kVA 3:3 catalogue, p.2 technical specifications. Best Power Equipments (BPE). https://cdn.prod.website-files.com/69c60f84565f2d4b25a3c71f/69f8335f84bb32fd0fe4c29c_18032026045855MPP_Series_10~20kVA_33_catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.