Technical guideFree to read2026

MERCIA-E Automatic Transfer Switches Technical Data Sheet

Original title Mercia-E Automatic Transfer Switches technical data sheet

Craig & Derricott

The technical data sheet for the Craig & Derricott MERCIA-E ATS range from 32 A to 160 A, with no-break bypass and an IP65 enclosure (ENG-DS-015, Issue 1, 02.11.2026).

On this page

Overview

The range incorporates a TP&N (three-phase plus neutral) ATS with an integrated controller. The controller continuously monitors voltage and frequency of two AC sources, which may be utility, generator or a combination, and on source failure transfers the load automatically to the healthy supply. The single-line, no-break (SL, NB) bypass arrangement lets the ATS be isolated from service without interrupting the load; the outgoing load stays energised during maintenance.

Each unit is housed in an IP65-rated mild steel enclosure finished in Light Grey (RAL 7035) with removable gland plates. Standard equipment includes volt-free contacts, Modbus RS485 communication, LED status indication on the door, and generator start/stop and mimic terminals; volt-free terminals are provided for BMS remote monitoring. The passcode-protected controller has programmable functions including under/over voltage, under/over frequency and power loss. All switches are padlockable in the OFF position.

Electrical ratings: rated voltage 400 V, rated current 32 to 160 A, impulse withstand voltage 8 kV, insulation voltage 690 V, Form 3 separation, ambient temperature -25 to +55 °C, maximum cable capacity 50 mm2. Short-time withstand current (1 s) is 800 A below 63 A and 3 kA for 80 to 160 A; conditional short-circuit current is 10 kA below 45 A (50 A gG fuse-link) and 50 kA for 63 to 160 A (80 A gG fuse-link). Standards listed are BS EN 60947-1, -3, -5-1 and -6-1, BS EN 61439-1 and -2, BS 8519:2020, BG 70/2021 and BS EN 60529; RoHS and REACH compliant. Weight values are shown as to be confirmed in the data sheet.

Key points

  1. 32 to 160 A; rated voltage 400 V; TP&N ATS with integrated controller.
  2. Single-line no-break (SL, NB) bypass: the ATS is isolated from S1, S2 and load while the load stays energised.
  3. IP65 mild steel enclosure; sizes 600 x 600 x 300 mm (H x W x D) for 32 to 100 A and 800 x 600 x 300 mm for 125 to 160 A.
  4. Standard: volt-free contacts, Modbus RS485, LED door indication, generator start/stop and mimic terminals.
  5. Impulse withstand voltage 8 kV; insulation voltage 690 V; Form 3; ambient -25 to +55 °C.
  6. Conditional short-circuit current: 10 kA below 45 A (50 A gG), 50 kA for 63 to 160 A (80 A gG).
  7. AC33b power: 14 kW at 32 A, 35 kW at 63 A, 55 kW at 100 A, 89 kW at 160 A.
  8. Standards: BS EN 60947-6-1 (transfer switching equipment), BS EN 61439-1 and -2, BS 8519:2020, BG 70/2021.

Using it in design

  • Where the load must not be interrupted during maintenance, choose this no-break bypass arrangement and write the procedure for isolating the ATS from S1, S2 and load into the operating instructions.
  • Compare the expected short-circuit current at the supply point with the conditional values (10 kA below 45 A, 50 kA for 63 to 160 A) and the upstream fuse class.
  • Check AC33b power (for example 55 kW at 100 A) against the load type; assess motor-loaded feeds separately.
  • Programme the under/over voltage and frequency thresholds to match the generator acceptance window and define passcode management.
  • Add the volt-free contact and Modbus RS485 points to the monitoring list; because enclosure weight is not given, ask the manufacturer for wall-loading advice.

Who should read it

Electrical engineers designing generator-backed small and mid-sized critical distribution and teams writing ATS specifications.

Document contents

  1. Overview and key features
  2. Dimensions
  3. Installation guidance
  4. Technical specification and standards
  5. Ordering information

Publication details

Authors
Craig & Derricott
Publisher
Craig & Derricott
Year
2026
Document number
ENG-DS-015 Issue 1
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Craig & Derricott (2026). Mercia-E Automatic Transfer Switches technical data sheet. Craig & Derricott. ENG-DS-015 Issue 1. https://craigandderricott.co.uk/wp-content/uploads/2026/10/ENG-DS-015_ATS_Mercia_Datasheet-V1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.