ELSIPOWER Static Transfer Switch product catalog
ELSIPOWER
ELSIPOWER's EL STS series: single-phase 16-1000 A and three-phase 16-2000 A static transfer switches with about 5 ms (quarter-cycle) transfer between synchronized sources and over 99% efficiency.
On this page
Overview
The ELSIPOWER catalogue presents the EL STS static transfer switch series, which moves a load automatically and without interruption between two independent sources, for example two UPS units or a UPS and the mains. There are two models: STS-1, single-phase 16-1000 A, and STS-3, three-phase 16-2000 A. Rack, wall-mount and tower cabinets are offered, and data centres, hospitals, industrial plants and finance and transport infrastructure are listed as applications.
According to the technical table, transfer time is a quarter cycle with synchronized sources (about 5 ms at 50 Hz) and half a cycle with non-synchronized sources. Efficiency is over 99%, the voltage range is +/-20% (transfer outside the range is adjustable), frequency is 50/60 Hz with a 45-65 Hz range, and crest factor is 3:1. Discrete voltage options run from 110 to 240 VAC for STS-1 and from 190 to 660 VAC for STS-3.
On the physical side the catalogue lists protection class IP20 (optionally IP21-IP55), natural or fan-assisted cooling, bottom cable entry (optionally top, rear or side), and a maintenance bypass with an MCB, MCCB or CAM switch for each source. The power module is hot-swappable (in two systems) with front access. Operating temperature is -10 to 50 C and relative humidity 0-95% non-condensing.
The catalogue refers to EN 62310-1, -2 and -3. Standard communication is Modbus RTU over RS232, with RS485, Modbus TCP/IP, SNMP and IEC 61850 as options. It contains no discrete order codes or cabinet dimensions; current ranges are given as continuous ranges, so cabinet sizes and weights for a specific model must be obtained from the manufacturer as model-specific drawings.
Key points
- STS-1 is single-phase 16-1000 A (1 or 2 poles); STS-3 is three-phase 16-2000 A (3 or 4 poles).
- Transfer time is 1/4 cycle with synchronized sources (about 5 ms at 50 Hz) and 1/2 cycle with non-synchronized sources.
- Efficiency is over 99%; voltage range +/-20%; frequency 50/60 Hz, 45-65 Hz; crest factor 3:1.
- Voltage options: 110/115/120 and 220/230/240 VAC (single phase); 190/200/210, 380/400/415, 440/460 and 660 VAC (three phase).
- Protection class IP20 (option IP21-IP55); operating temperature -10 to 50 C, storage -25 to 70 C; humidity 0-95% non-condensing.
- The maintenance bypass is an MCB, MCCB or CAM switch for each source.
- Communication: Modbus RTU (RS232) as standard; RS485, Modbus TCP/IP, SNMP and IEC 61850 as options.
- Standards: EN 62310-1 (general and safety), EN 62310-2 (EMC), EN 62310-3 (performance and test).
Using it in design
- In dual-UPS or single-corded load architectures, verify source synchronization at the STS; the 5 ms transfer applies only to synchronized sources, otherwise allow a half cycle (about 10 ms at 50 Hz).
- Select load current against the 16-1000 A (single phase) or 16-2000 A (three phase) ranges and confirm the cabinet type (rack, wall, tower) for that current with the manufacturer.
- Decide neutral switching (1/2 or 3/4 poles) according to the earthing scheme.
- Include the maintenance bypass and the MCB/MCCB protection on the source inputs in the selectivity study.
- Specify Modbus TCP/IP or SNMP together with the BMS/DCIM integration requirement.
Who should read it
Electrical engineers designing dual-feed load architectures and teams writing STS specifications.
Document contents
- General features
- Basic features
- Options
- Applications
- Technical specifications
Publication details
- Authors
- ELSIPOWER
- Publisher
- ELSIPOWER
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ELSIPOWER ELSIPOWER Static Transfer Switch product catalog. ELSIPOWER. https://www.elsi.com.tr/catalog-pdf?slug=sts-3-phase&lang=en
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.