Falcon FN2 4.5-10 kVA datasheet, p.2 rackmount table (image checked)
Original title Falcon FN2 4.5–10 kVA datasheet, p.2 rackmount table (image checked)
Falcon Electric
Falcon Electric's FN2 rackmount: 4.5, 6, 8 and 10 kVA at unity output power factor, 240 Vdc battery, 0 ms transfer, 90-91% normal and 94-95% ECO efficiency, N+1 paralleling to 40 kVA.
On this page
Overview
Falcon Electric's FN2 datasheet presents a DSP-controlled true on-line UPS family with unity power factor. The rackmount table on page 2 covers four models: FN2-4.5KRM-2TXI, FN2-6KRM-2TXI, FN2-8KRM-2TXI and FN2-10KRM-2TXI. Output power is 4500, 6000, 8000 and 10000 W (power factor 1). The family supports 3+1 parallel redundancy and up to four units in parallel, that is scaling to 40 kVA; a PDU with or without a maintenance bypass switch is offered as an option.
On the electrical input, nominal voltage is 208 or 240 Vac, frequency range 45-70 Hz, input power factor 0.99 at full linear load and input harmonic distortion 5% or less. The input voltage range depends on load: 176-280 V at 100% load, 160-176 V below 75% load and 110-160 V below 50% load. Input current is 30, 36, 52 and 62 A by model. Efficiency is 90% (normal) and 94% (ECO) for 4.5 and 6 kVA, and 91% and 95% for 8 and 10 kVA.
On the output, voltage is 120/208, 110/220, 115/230 or 120/240 Vac (isolated output), regulation +/-3%, harmonic distortion 3% or less and crest factor 3:1. Overload capability is 480 seconds at 110%, 30 seconds at 125% and immediate at 150%. The battery system is 240 Vdc, user-replaceable, five hot-swappable packs of 12 Vdc/9 Ah maintenance-free VRLA. Full-load/half-load runtime is 9.5/26 min for 4.5 kVA, 5.5/17 min for 6 kVA, 4/11.5 min for 8 kVA and 2/8.5 min for 10 kVA.
Physical data: the UPS inverter is 2U (88 x 440 x 680 mm) and the transformer and battery bank are 3U (132 x 440 x 665 mm); system weight is 114.5 kg for 4.5 and 6 kVA and 142.5 kg for 8 and 10 kVA. Operating temperature is 0 to 40 C, humidity 20-95% non-condensing, altitude 1000 m and noise under 60 dBA; heat dissipation is 2559, 3412, 4095 and 4777 BTU/hr. Approvals are UL1778, cUL, FCC Class A and CE. The table covers only the rackmount columns; tower model codes are separate.
Key points
- Four models: 4.5, 6, 8 and 10 kVA; output 4500, 6000, 8000, 10000 W; output power factor 1.
- Efficiency: 4.5 and 6 kVA are 90% normal and 94% ECO; 8 and 10 kVA are 91% normal and 95% ECO; input current is 30, 36, 52, 62 A.
- Input is 208 or 240 Vac, 45-70 Hz; input power factor 0.99 and THDi 5% or less; input range is 176-280 V at 100% load.
- Output regulation is +/-3%, THD 3% or less, crest factor 3:1; overload 110%/480 s, 125%/30 s, 150% immediate.
- Battery is 240 Vdc; five hot-swappable packs; 12 Vdc/9 Ah VRLA; charge current 1.7 A; recharge to 90% in 6 hours.
- Runtime (full/half load): 4.5 kVA 9.5/26 min; 6 kVA 5.5/17 min; 8 kVA 4/11.5 min; 10 kVA 2/8.5 min.
- Transfer time is 0 ms (line fail, bypass); parallel capacity 4 units (up to 40 kVA), 3+1 redundancy.
- System weight is 114.5 kg (4.5 and 6 kVA) and 142.5 kg (8 and 10 kVA); heat dissipation 2559-4777 BTU/hr; noise under 60 dBA.
Using it in design
- Size capacity from output power (power factor 1); the 10 kVA model carries 10 kW.
- Read runtime from the table for full and half load; at 10 kVA full load it is only 2 min, so longer runtime needs the extended battery banks.
- Use the input current (30-62 A) and the load-dependent lower input limits in supply design.
- Put the 3+1 parallel structure and the 4-unit limit (40 kVA) into the capacity plan for N+1.
- Add the heat dissipation (2559-4777 BTU/hr) and the 40 C operating limit to the cooling load calculation; weigh ECO-mode efficiency against its protection level.
Who should read it
Electrical designers and IT infrastructure managers seeking N+1 UPS for small and mid-size rack loads.
Document contents
- Overview and key advantages
- Rackmount model table: electrical input and output, battery, transfer time, connections, environment, controls, mechanical, approvals
Publication details
- Authors
- Falcon Electric
- Publisher
- Falcon Electric
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Falcon Electric Falcon FN2 4.5–10 kVA datasheet, p.2 rackmount table (image checked). Falcon Electric. https://falconups.com/wp-content/uploads/16-FN2-4.5-10kVA-Online-UPS-Rackmount-Tower.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.