FSP Champ 6K/10K User Manual, Section 6 Specifications (p.23)
Original title FSP Champ 6K/10K User Manual, section 6 Specifications, printed p.23
FSP Technology
FSP Technology's Champ 6K and 10K are single-phase on-line UPS units rated 6000 VA / 5400 W and 10000 VA / 9000 W, with 0 ms transfer, 92-93% AC-mode efficiency and tower and rack variants.
On this page
Overview
Section 6 of the manual gives the specification tables for the tower and rack models of the FSP Champ PF 0.9 6K/10K on-line UPS. The family splits into standard models (6K, 6KR, 10K, 10KR) and long-run models (6KL, 6KRL, 10KL, 10KRL), where long-run units use external battery packs.
On the input side the unit is single phase with power factor of at least 0.99 at 100% load; low-line loss is 110 VAC at 50% load and 176 VAC at 100% load, and high-line loss is 300 VAC. Output is selectable at 208/220/230/240 VAC with ±1% regulation, THD of 3% on linear and 5% on non-linear load, 0 ms transfer time and crest factor up to 3:1. Efficiency exceeds 92% (AC mode) and 90% (battery) for the 6K, and 93% and 91% for the 10K.
Standard models hold 16 or 20 batteries of 12 V 9 Ah (218.4 or 273 VDC) and recharge to 90% in 9 hours; long-run models use 16-20 batteries with a 4 A default charge current (6 A only with 16 batteries). The tables also list dimensions, weights, environment and management options.
As limits, the footnotes require derating to 60% in CVCF mode and to 90% when output is set to 208 VAC, plus 1% per 100 m above 1000 m. Efficiency values are not tied to a specific load point, so no curve can be built.
Key points
- Ratings: 6K is 6000 VA / 5400 W; 10K is 10000 VA / 9000 W (output PF 0.9).
- Input PF at least 0.99 at 100% load; low-line loss 110 VAC (50% load) / 176 VAC (100% load), high-line loss 300 VAC.
- Output 208/220/230/240 VAC, ±1%; THD 3% or less on linear and 5% or less on non-linear load.
- Transfer time is 0 ms (line to battery and inverter to bypass).
- Efficiency: 6K above 92% AC and 90% battery; 10K above 93% AC and 91% battery.
- AC-mode overload: 30 min at 100-110%, 5 min at 110-130%, 10 s above 130%.
- Standard tower weights: 6K 61 kg (16 batteries), 10K 74-76 kg; long-run tower body 12-16 kg; rack units are 2U or 3U (15 or 18 kg).
- Derate to 60% in CVCF mode and 90% at 208 VAC output; 1% per 100 m above 1000 m.
Using it in design
- If 208 VAC output or CVCF (frequency converter) mode is used, multiply capacity by 0.9 or 0.6 respectively.
- For long-run models, size the external battery pack, charge current (1-6 A) and battery count (16-20) from the required runtime.
- Use standard and long-run dimensions and weights separately in rack and floor-load plans.
- Apply the derating above 1000 m altitude in the load calculation.
Who should read it
Electrical designers and installers selecting small-room and rack UPS units.
Publication details
- Authors
- FSP Technology
- Publisher
- FSP Technology
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
FSP Technology FSP Champ 6K/10K User Manual, section 6 Specifications, printed p.23. FSP Technology. https://www.fsp-group.com/download/user_manual/Champ6k10k_UserManual.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.