Germen N Series 6-10 kVA On-Line UPS, Technical Table (p.2)

Original title Germen N Serisi 6–10 kVA, teknik tablo s.2

Germen UPS

The Germen N Series is a range of 6 kVA / 6000 W and 10 kVA / 10000 W single-phase double-conversion on-line UPS units with unity output power factor, 0 ms transfer time and a 110-300 V AC input window.

On this page

Overview

The document is the brochure for Turkish manufacturer Germen's N Series 6-10 kVA, single-phase-in single-phase-out on-line UPS. The series uses an IGBT rectifier and DSP control in a true double-conversion design, and lists a transformerless build, a 50/60 Hz frequency converter mode, an EPO connection and generator compatibility among its features. Named uses include information centres, server rooms, medical devices, communications and network systems.

The technical table lists four models: NT-6KVA and NTL-6KVA (6000 W), NX-10KVA and NXL-10KVA (10000 W); the L models are long-run versions with external battery cabinets. Input voltage tolerance is 110-300 V AC, input power factor is above 0.99 at full load, output is 208/220/230/240 VAC (±1%) and battery-mode frequency tolerance is ±0.05%. Transfer time is 0 ms, and output THD is 3% or less on linear and 5% or less on non-linear load.

The battery section gives 16 batteries (12, 14 or 20 optional), 216 VDC charge voltage, 160 VDC end-of-discharge voltage and 1 A charge current (adjustable 1-10 A). Operating temperature is 0-40 °C, protection class IP 20 and noise 50 dBA or less. The manufacturer states a 2-year warranty on unit and batteries and a 10-year spare-part supply commitment.

Key points

  1. Models: NT-6KVA, NTL-6KVA (6000 W), NX-10KVA, NXL-10KVA (10000 W); output power factor 1.0.
  2. Input voltage tolerance 110-300 V AC, input power factor above 0.99 at full load, frequency 50/60 Hz ±10 Hz.
  3. Output 208/220/230/240 VAC, ±1%; THD 3% on linear and 5% on non-linear load or less; crest factor 3:1.
  4. Transfer time 0 ms (AC to battery).
  5. AC-mode overload: 30 min at 102-110%, 10 min at 110-130%, 30 s at 130-150%, 200 ms above 150%.
  6. Battery: 16 units (12, 14, 20 optional), charge 216 VDC, end of discharge 160 VDC, charge current 1 A (1-10 A adjustable).
  7. Weights: NT 48.5 kg, NTL 15 kg, NX 58 kg, NXL 18 kg; 0-40 °C, IP 20, 50 dBA or less.
  8. Warranty 2 years (unit and battery); 10-year spare-part supply.

Using it in design

  • When selecting 6 or 10 kVA for a small server room, take kVA and kW as equal since output PF is 1.0.
  • For long autonomy choose the L model (external battery cabinet) and set battery count (12-20) from the runtime.
  • Consider the 110-300 V AC input window for weak-grid or generator-fed scenarios.
  • If altitude exceeds 1000 m (IEC 62040 reference), check derating.

Who should read it

Electrical designers selecting UPS units for small server rooms and network systems, and integrators in the Turkish market.

Publication details

Authors
Germen UPS
Publisher
Germen UPS
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Germen UPS Germen N Serisi 6–10 kVA, teknik tablo s.2. Germen UPS. https://germenups.com/wp-content/uploads/2022/12/N-SERISI-6-10-kVA.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.