Powercom VANGUARD VGD-6000-20K Single-Phase Online UPS Catalogue
Original title POWERCOM VGD-6000–20K catalogue, revision 20240322, p.2
Powercom
Powercom VANGUARD VGD is a 6-20 kVA single-phase online double-conversion tower UPS: 0.7 output power factor, input power factor above 0.97, ECO mode efficiency above 94% and 0 ms transfer.
On this page
Overview
The catalogue states that Powercom's VGD family spans 700 VA to 20 kVA; the specification table covers the VGD-6000, 8000, 10K, 12K, 15K and 20K. All are single-phase tower, high-frequency double-conversion units with true sine output. Ratings are 6000 VA / 4200 W, 8000 VA / 5600 W, 10 kVA / 7000 W, 12 kVA / 8400 W, 15 kVA / 10.5 kW and 20 kVA / 14 kW, so the rated output power factor is 0.7.
Input is 208/220/230/240 V AC with a load-dependent window from 120-276 V AC (below 25% load) to 180-276 V AC (100% load). Input power factor is above 0.97 and cold start is supported. Output is ±2% voltage, 50/60 Hz ±0.25 Hz, 0 ms transfer, crest factor 3:1 and THD 3% on linear load (and 5%). Overload in line mode is 110-125% for 60 s and 125-150% for 10 s; in battery mode above 110% for 10 s. At 208 V output, capacity derates to 90%.
The battery uses 12 V 7 Ah or 9 Ah blocks, 20 on the 6000-10K models and 2x20 on the 12K-20K models, with a typical recharge of 4 hours to 90%. Features include ECO mode, free-run frequency stability, generator mode, battery remaining time display, multi-language LCD, EPO, USB/RS232 with optional SNMP and UPSMON PRO software. An external battery module is optional; sizes run from 257x590x570 mm (86 kg) to 342x760x905 mm (207 kg), with isolation-transformer versions at 123-273.5 kg.
Key points
- Six models: VGD-6000 (4200 W), 8000 (5600 W), 10K (7000 W), 12K (8400 W), 15K (10.5 kW), 20K (14 kW); output power factor 0.7.
- Single-phase, tower, double conversion, pure sine; 0 ms transfer.
- Input power factor above 0.97; input window 120-276 to 180-276 V AC by load.
- ECO mode efficiency above 94%; output voltage ±2%; capacity is 90% at 208 V output.
- Overload: line mode 110-125% for 60 s, 125-150% for 10 s; battery mode above 110% for 10 s.
- Battery: 12 V 7 Ah or 9 Ah, 20 units (2x20 for 12K-20K); recharge to 90% in 4 hours.
- Size and weight: 257x590x570 mm, 86 kg to 342x760x905 mm, 207 kg; transformer versions 123-273.5 kg.
- Communication: LCD, RS232, USB B, optional SNMP; UPSMON PRO; EPO.
Using it in design
- With a 0.7 output power factor, compare real kW capacity (for example 14 kW for 20 kVA) against the kW load list, not kVA.
- Carry the weight of the large single-phase unit (86-273.5 kg) into floor loading and layout.
- Verify that generator mode and the wide input window suit generator-fed installations.
- For the required autonomy, consider the external battery module option and the 4-hour recharge to 90%.
- Include the 90% capacity derating at 208 V output in the load calculation.
Who should read it
Designers and integrators selecting mid-range single-phase online UPS.
Document contents
- Main Feature
- Specification (configuration, input, output, protection, battery, communication, physical)
Publication details
- Authors
- Powercom
- Publisher
- Powercom
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Powercom POWERCOM VGD-6000–20K catalogue, revision 20240322, p.2. Powercom. https://www.upspowercom.com/pcm-img/UPS-VGD/Catalog2.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.