SCU CMS Series Modular UPS brochure, printed pp.9-11
Original title SCU CMS Series Modular UPS brochure, printed pp.9–11
Sicon Chat Union Electric (SCU)
The SCU CMS series builds 50-800 kVA systems from 10, 25 and 50 kVA modules, paralleling to 3200 kVA, with AC-AC efficiency of 95% or more, THDi of 3% or less and input power factor of 0.99 or more.
On this page
Overview
The brochure presents SCU's CMS series as an industrial-grade, non-isolated (transformerless), modular UPS. Each module is a fully functional UPS (converter, inverter, charger and controller). The system scales from 10 kVA to 800 kVA and can parallel up to 3200 kVA. Module ratings are 10, 25 and 50 kVA and system ratings 50, 100, 150, 250, 350, 500 and 800 kVA. Wire in/out modes are 3/3, 3/1, 1/3 and 1/1.
Performance indices: AC-AC efficiency of 95% or more, inverter (DC-AC) efficiency of 98% or more, THDi of 3% or less and input power factor of 0.99 or more. N+X module-level redundancy, multi-level decentralised control and master-slave synchronisation in sequence control remove the system bottleneck. Each module shares input and output current automatically and all modules share the batteries. Battery management includes discharge management, automatic float and equalising charge transfer and temperature compensation.
Frame models: CMS-50/10 (5 slots, 600 x 800 x 1200 mm), CMS-100/10 (10 slots, 600 x 800 x 1600 mm), CMS-150/25 (6 slots, 600 x 800 x 1600 mm), CMS-250/25 (10 slots, 800 x 800 x 2000 mm), CMS-350/50 (7 slots, 800 x 1000 x 2000 mm), CMS-500/50 (10 slots, 1400 x 1000 x 2000 mm) and CMS-800/50 (16 slots, 2000 x 1000 x 2000 mm). Module sizes are 482 x 465 x 89 mm (2U) for 10 kVA, 482 x 464 x 133 mm (3U) for 25 kVA and 482 x 700 x 176 mm (4U) for 50 kVA.
Standard equipment is a manual bypass, SPD (Class C), RS232 and RS485 ports, remote monitoring software and dry contacts; options are an input/output transformer, battery bank and IPDS. The monitoring software can watch up to 600 UPS. The STS module is a parallel of SCR and AC contactor with overload capacity of 1000% for 1 min and transfer time under 1 ms; the modules are dust-proof to IP30.
Key points
- Module ratings 10, 25, 50 kVA; system ratings 50, 100, 150, 250, 350, 500, 800 kVA; parallel up to 3200 kVA.
- AC-AC efficiency ≥ 95%, inverter efficiency ≥ 98%, THDi ≤ 3%, input PF ≥ 0.99.
- Wire in/out modes 3/3, 3/1, 1/3, 1/1; N+X module redundancy.
- CMS-50/10 600 x 800 x 1200 mm (5 slots); CMS-100/10 600 x 800 x 1600 mm (10 slots).
- CMS-250/25 800 x 800 x 2000 mm; CMS-500/50 1400 x 1000 x 2000 mm; CMS-800/50 2000 x 1000 x 2000 mm (16 slots).
- Module size: CM10 482 x 465 x 89 mm (2U), CM25 482 x 464 x 133 mm (3U), CM50 482 x 700 x 176 mm (4U).
- STS module: transfer time < 1 ms, overload 1000% for 1 min; module protection IP30.
- Standard: manual bypass, SPD (Class C), RS232/RS485, dry contacts; options: transformer, battery bank, IPDS.
Using it in design
- In the growth plan, choose the module size (10, 25 or 50 kVA) by target system power; check frame slot count and the spare modules needed for N+X.
- Use frame size and weight for floor loading and layout; add the battery bank and optional transformer to the area separately.
- Use the input power factor of 0.99 and THDi of 3% as inputs to generator and input protection sizing.
- Match the input/output phase mode (3/3, 3/1, 1/3, 1/1) to the mains and load phase structure.
- Use the central STS with decentralised control as a design rationale for reduced single-point-of-failure risk; specify the SNMP/MODBUS options for monitoring.
Who should read it
Electrical designers and capacity planners selecting modular UPS for small, medium and large data centres.
Document contents
- CMS features
- Frame models CMS-50/10 to CMS-800/50
- UPS module (CM10, CM25, CM50)
- Monitor module (CMS-CSU)
- STS module (CMS-STS)
Publication details
- Authors
- Sicon Chat Union Electric (SCU)
- Publisher
- Sicon Chat Union Electric (SCU)
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Sicon Chat Union Electric (SCU) SCU CMS Series Modular UPS brochure, printed pp.9–11. Sicon Chat Union Electric (SCU). https://www.sicon-emi.com/uploadfile/downloads/CMS%20%20Modular%20UPS%2010-3200kVA.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.