Sorotec HP9335C II 160-800 kVA high-frequency online UPS

Original title SOROTEC HP9335C II 160–800 kVA web Specification table

Sorotec

Sorotec HP9335C II is a 160-800 kVA transformer-free, full-IGBT double-conversion online UPS: THDi <3%, input PF >=0.99, up to 96.5% online and 99.1% in intelligent ECO mode.

On this page

Overview

The page gives the web specification table of Sorotec's HP9335C II series. The series has eight model columns: 160, 200, 250, 300, 400, 500, 600 and 800 kVA. It is a transformer-free, full-IGBT double-conversion online UPS, presented for protecting computer, telecommunications and industrial automation loads.

Input is 380/400/415 V three-phase four-wire, with a range of 325-478 V and 50/60 Hz (frequency window 40-70 Hz). Input current distortion THDi is below 3% and input power factor is at least 0.99. The battery string has 38 to 48 blocks, with a default of 40, and DC ripple voltage is below 1%. The bypass voltage range is -20% to +15% and can be changed through software.

Output power factor is stated as 0.9 or 1. Steady-state voltage regulation is below 1%, transient regulation below 5%, transient response below 20 ms, and THDv is below 2% on linear and below 5% on non-linear load. Frequency accuracy is +/-0.05%. Efficiency is up to 96.5% in online mode and up to 99.1% in intelligent ECO mode, while the key-features list quotes 99.3% for ECO mode.

General data: relative humidity 0-95% non-condensing, maximum operating altitude 1000 m, noise below 74 dB and below 76 dB at 1 m, and IP20 protection. Two cabinet sizes are listed, 900x1000x1900 mm and 1200x1000x1900 mm. Standards listed are IEC 62040-1, UL1778, IEC 62040-2 and IEC 62040-3. Smart parallel, generator compatibility and battery ground-fault detection are also listed.

Key points

  1. Eight models: 160, 200, 250, 300, 400, 500, 600 and 800 kVA.
  2. Input 380/400/415 V, 325-478 V range, 40-70 Hz; THDi <3%, PF >=0.99.
  3. 38-48 battery blocks per string, default 40; DC ripple <1%.
  4. Output PF 0.9 or 1; regulation <1% (steady), <5% (transient), response <20 ms.
  5. THDv <2% (linear), <5% (non-linear load).
  6. Efficiency: up to 96.5% online, up to 99.1% intelligent ECO.
  7. Humidity 0-95% non-condensing; altitude up to 1000 m; noise <74 / <76 dB; IP20.
  8. Sizes 900x1000x1900 and 1200x1000x1900 mm; IEC 62040-1/-2/-3 and UL1778.

Using it in design

  • Convert the design load to kW at both output PF options (0.9 and 1) and verify the model capacity.
  • Plan the battery string within 38-48 blocks, default 40, and tie the DC bus voltage and battery room area to it.
  • For generator-fed systems, use THDi <3% and the wide input voltage/frequency window (325-478 V, 40-70 Hz) as evidence of generator compatibility.
  • For energy calculations based on ECO mode, get written confirmation of which efficiency figure (99.1% or 99.3%) applies.
  • Reflect IP20 protection, the 1000 m altitude limit and 74-76 dB noise in electrical room layout decisions.

Who should read it

Data-centre electrical designers selecting large UPS units and engineers writing double-conversion UPS specifications.

Document contents

  1. Quick details
  2. Key features
  3. Specification (input, DC, output, bypass)
  4. Dimensions and weight
  5. System efficiency
  6. General data and standards

Publication details

Authors
Sorotec
Publisher
Sorotec
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sorotec SOROTEC HP9335C II 160–800 kVA web Specification table. Sorotec. https://www.sorosolar.com/high-frequency-online-ups-hp9335c-ii-160-800kva-product/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.