Technical guideFree to read2024

Thomson TS 870 Automatic Transfer Switch Brochure (MCB-CL062r12, 10/2024)

Original title Thomson TS 870 Automatic Transfer Switch brochure

Thomson Power Systems

A Thomson Power Systems product brochure giving transition types, configurations, withstand ratings, enclosure dimensions and shipping weights for the TS 870 automatic transfer switch family from 100 to 1200 A.

On this page

Overview

The brochure presents the TS 870 series as an ATS with fully enclosed silver-alloy contacts for 100-1200 A continuous current, 2, 3 or 4 poles, 120-600 VAC and 50/60 Hz. The power switching units are fully isolated on the utility and generator sides, the motor-operated mechanism provides mechanical interlocking, and optional integral overcurrent trip elements can save cost in upstream devices. All models are 3-cycle withstand tested to UL 1008 and CSA C22.2 No. 178 and withstand 6 times overload for 10 cycles. Seismic certification covers IBC 2012 section 13 (Occupancy Category IV) and ASCE7-05 region 3.

Standard transfer is open transition (break-before-make) on all models with an adjustable neutral position delay; the TSC 7320 controller with a 2.3 in backlit LCD shows status and settings without opening the door. 1000-1200 A models offer fast open transition with phase monitoring. The closed transition option (1000-1200 A) verifies synchronism before transferring without interruption; paralleling is limited to 100 ms, and if exceeded the other source is opened within 500 ms for isolation. On utility failure the closed-transition unit reverts automatically to open transition, and closed transition is inhibited when only one source is available. 400-800 A closed-transition units use the TSC 900 controller.

The bypass-isolation configuration gives maintenance staff a mechanism to isolate and bypass the ATS manually in a make-before-break procedure; utility and generator can never be paralleled. The service entrance (SE) ATS is for the US market only, includes isolation and overcurrent protection on the utility side, removes the need for a separate upstream breaker, and has a NEMA 1 enclosure with a padlockable service disconnect.

Tables give per-model withstand currents (for example 65 kA at 240 V, 25 kA at 480 V and 18 kA at 600 V for 100-150 A; 150 / 100 / 65 kA for 1000-1200 A) together with enclosure dimensions, terminal ranges and shipping weights. The 200 A row is limited to 240 V maximum; the 600 V limit of the other current rows must not be carried over to it. Weights in the document are shipping weights and apply to the ATS unit only; versions with a bypass switch are in a separate table.

Key points

  1. 100-1200 A, 2/3/4 poles, 120-600 VAC, 50/60 Hz; fully enclosed silver-alloy contacts, 100% continuous current.
  2. 3-cycle withstand tested to UL 1008 and CSA C22.2 No. 178; 6 times overload for 10 cycles.
  3. Standard transition is open (break-before-make) with adjustable neutral position delay; TSC 7320 controller has a 2.3 in LCD.
  4. Closed transition for 1000-1200 A: synchronism check, paralleling at most 100 ms, other source opened within 500 ms if exceeded; 400-800 A closed transition uses TSC 900.
  5. Withstand current examples (240 V / 480 V / 600 V): 100-150 A 65 / 25 / 18 kA; 400-800 A 65 / 50 / 35 kA; 1000-1200 A 150 / 100 / 65 kA.
  6. The 200 A row is given for 240 V only (65 kA); the 600 V limit must not be carried over to it.
  7. Seismic certification IBC 2012 section 13, Occupancy Category IV and ASCE7-05 region 3 (minimum SS=200%).
  8. Enclosure and weight examples (ATS unit, shipping): 100-200 A 3-pole 65 kg; 400 A 3-pole 103 kg; 800 A 3-pole 140 kg; 1000/1200 A 249 kg.
  9. Warranty 2 years; bypass-isolation and service entrance (US only) versions are available.

Using it in design

  • For a data centre, evaluate the 1000-1200 A closed-transition version together with the bypass-isolation configuration for maintenance without load interruption.
  • Read the WCR from the model and voltage row and compare with the fault-current study; remember the 200 A row is given for 240 V only.
  • In closed transition, check the 100 ms paralleling limit and the 500 ms back-up isolation time in generator and utility protection coordination.
  • Use the enclosure dimensions (for example 1000-1200 A: 70 x 34.3 x 14 in) and shipping weight in the floor plan; see the separate table for bypass versions.
  • In seismic zones, compare the IBC 2012 and ASCE7-05 certification in the document with the project requirement.

Who should read it

Electrical engineers selecting ATS equipment for data centres and commercial or industrial facilities.

Document contents

  1. TS 870 features
  2. General description
  3. Closed transition ATS (momentary)
  4. Bypass isolation ATS
  5. Service entrance ATS
  6. Withstand current ratings (3 cycle models)
  7. Enclosure dimensions and cable terminals
  8. Enclosure dimensions and terminations for ATS with bypass switch

Publication details

Authors
Thomson Power Systems
Publisher
Thomson Power Systems
Year
2024
Document number
MCB-CL062r12-TPS-EN-US-102024
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Thomson Power Systems (2024). Thomson TS 870 Automatic Transfer Switch brochure. Thomson Power Systems. MCB-CL062r12-TPS-EN-US-102024. https://edge.sitecorecloud.io/regalrexnorc4eb-hubandspoke33d4-prodfa01-faf2/media/Project/Regal-Rexnord/IPS/ThomsonPowerSystems/Literature/Product-Brochures/MCB-CL062r12-TPS-EN-US-102024.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.