Uniline MAXIPRO (MXP) 3-80 kVA UPS brochure
Original title Uniline MAXIPRO (MXP) 3–80 kVA brochure, p.2 technical specifications (image checked)
Uniline Energy Systems
Uniline MAXIPRO MXP offers industrial three-phase in, three-phase out online UPS in 11 models from 3 to 80 kVA, with inverter efficiency above 93%, output THD below 3% and 0.8 lagging power factor.
On this page
Overview
The Uniline Energy Systems (India) brochure presents the MAXIPRO MXP series: IGBT-based online UPS with 3-phase input and 3-phase output. The manufacturer cites under-voltage and sudden dips as the main power problems and uses them to justify the wide input window and double-conversion design. The document is a marketing brochure; it states no test standard or measurement method.
The technical table covers 11 models: 3, 5, 10, 15, 20, 25, 30, 40, 50, 60 and 80 kVA (model numbers 3303 to 3380). Input is 415 V, -20%/+15%, 4-wire three phase; frequency 50 Hz ±10%, and the unit can run on generators. Output is 415 V AC with ±1% regulation, 50 Hz ±0.1% (crystal controlled), a sine wave and harmonic distortion below 3%. Efficiency is above 93% and power factor 0.8 lagging (0.9 on request).
Overload capability is 110% for 10 minutes and 200% for 5 cycles, with crest factor above 3:1 and transient recovery within 3 cycles. A built-in output isolation transformer provides common-mode noise rejection. Operating ambient is 0-50 °C, storage -10 to 60 °C, humidity 95% RH and altitude up to 2000 m; noise is below 50 dB up to 10 kVA and below 60 dB above.
Options include a static bypass switch, remote on/off panel, remote indicator panel, SNMP/RS 232, hot-standby and parallel redundant operation. Efficiency is a single figure; with no load point given, no curve can be derived.
Key points
- 11 models: 3, 5, 10, 15, 20, 25, 30, 40, 50, 60 and 80 kVA; 3-phase in, 3-phase out.
- Input 415 V -20%/+15%, 50 Hz ±10%; generator compatible.
- Output 415 V, regulation ±1%, frequency 50 Hz ±0.1%, THD below 3%.
- Efficiency above 93%; output power factor 0.8 lagging (0.9 optional).
- Overload 110% for 10 minutes and 200% for 5 cycles; crest factor above 3:1; transient recovery 3 cycles.
- Ambient 0-50 °C, 95% RH, 2000 m altitude; noise below 50 dB (up to 10 kVA) and below 60 dB (above).
- Options: static bypass, parallel redundant, hot-standby, SNMP/RS 232.
Using it in design
- For small and medium three-phase critical loads, convert the 3-80 kVA range to kW at 0.8 power factor; kW capacity differs with the 0.9 option.
- Efficiency is a single figure with no load point; request the efficiency curve from the manufacturer for energy-cost calculations.
- Static bypass and parallel redundancy are options; state in the specification that they are ordered when the architecture is N+1.
- The built-in output isolation transformer means the neutral and earthing scheme, and the bypass path, must be verified separately.
Who should read it
Electrical designers and project engineers selecting mid-range three-phase UPS units.
Document contents
- MAXIPRO UPS series salient features
- Technical specifications (3-80 kVA)
- Input, output, protection and ambient conditions
- Options and product range
Publication details
- Authors
- Uniline Energy Systems
- Publisher
- Uniline Energy Systems
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Uniline Energy Systems Uniline MAXIPRO (MXP) 3–80 kVA brochure, p.2 technical specifications (image checked). Uniline Energy Systems. https://unilineindia.com/wp-content/uploads/2022/05/MAXIPRO-MXP_1_compressed.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.