Chloride CP70Z IEC datasheet rev20-0526, rating matrix p.2

Chloride

Chloride CP70Z industrial UPS datasheet: 5-250 kVA single-phase and up to 500 kVA three-phase output, SCR/IGBT technology, VFI-SS-111 class, 150% for 1 minute overload.

On this page

Overview

Chloride's CP70Z datasheet (rev20-0526) introduces an industrial UPS family designed for oil and gas, refining, power generation, rail and process industries. The system is based on SCR/IGBT technology with digital control, covering 2.5-250 kVA single-phase and 5-500 kVA three-phase output. Dual cooling channels, input and output transformers, board conformal coating and halogen-free cables are standard.

Input is 3 x 400 V (380, 415) +/-10%, 50 Hz (60 Hz) +/-5%, with inrush current of at most 10 x In. A 6- or 12-pulse thyristor rectifier is used; a 12-pulse system can reach THDi below 10% without extra filters. Rated output power is given at 0.8 lagging power factor; dynamic performance is VFI SS 111 per IEC/EN 62040-3. Overload is 150% for 1 minute and 125% for 10 minutes; short-circuit clearing on three-phase output is 315% for 100 ms and 220% for 5 s phase-to-neutral.

The rating matrix is organised by DC intermediate voltage. At 110-120 Vdc: 5, 10, 20, 30, 40, 50 and 60 kVA; at 220-240 Vdc: 10, 20, 30, 40, 50, 60, 80, 100, 120, 160, 200, 250 and 320 kVA; at 400 Vdc: 40, 50, 60, 80, 100, 120, 160, 200, 250, 320, 400 and 500 kVA. Battery options are lead-acid, nickel-cadmium and sodium metal chloride (SMC), with autonomy from a few minutes to several hours on request.

General data: efficiency up to 90% depending on rating, operating temperature 0-40 C, altitude to 1000 m without derating, IP 20, noise 60-75 dB, relative humidity below 95% non-condensing. Options include a 12-pulse rectifier, harmonic filter (THDi about 5%), bypass transformer or stabilizer, DC earth-fault detection, Modbus, Profibus and IEC 61850. The sheet gives no load-point-linked efficiency curve or weight table.

Key points

  1. Power: single-phase 2.5-250 kVA, three-phase 5-500 kVA (at 0.8 lagging).
  2. Matrix: 5-60 kVA at 110-120 Vdc; 10-320 kVA at 220-240 Vdc; 40-500 kVA at 400 Vdc.
  3. Class VFI SS 111 (IEC/EN 62040-3, class 1); transfer time 0 ms when synchronised.
  4. Overload: 150% for 1 min, 125% for 10 min.
  5. Short circuit: 3-ph Ph-N 315%/100 ms and 220%/5 s; Ph-Ph 190%/100 ms and 135%/5 s.
  6. Inrush at most 10 x In; THDi below 10% with 12-pulse.
  7. Efficiency up to 90% by rating; operation 0-40 C, to 1000 m.
  8. Battery: lead-acid, NiCd, SMC; battery current limit 0.1 C lead-acid, 0.2 C NiCd and SMC.

Using it in design

  • Choose the DC intermediate voltage (110-120, 220-240, 400 Vdc) together with the battery string and power class; the matrix lists discrete steps only.
  • Check the 12-pulse THDi target below 10%, or about 5% with the optional filter, against generator compatibility.
  • Use the short-circuit capability (315% for 100 ms) as an input to downstream protective-device selectivity.
  • Request derating for altitude above 1000 m and temperature above 40 C.
  • Do not use an efficiency figure without a stated load point directly in energy calculations.

Who should read it

Electrical engineers writing UPS specifications for industrial and process plants.

Document contents

  1. Overview and benefits
  2. Key features
  3. Technical data: input, output, battery
  4. General data and standards
  5. Ratings matrix
  6. Options
  7. LYNX HMI

Publication details

Authors
Chloride
Publisher
Chloride
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Chloride Chloride CP70Z IEC datasheet rev20-0526, rating matrix p.2. Chloride. https://www.chloride.com/files/library/files/Product%20Downloads/Chloride%C2%AE%20CP70Z%20AC%20UPS/Chloride-CP70Z-DS-EN-gl-rev20-0526.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.