Chloride CP70Z IEC datasheet rev20-0526, rating matrix p.2
Chloride
Chloride CP70Z industrial UPS datasheet: 5-250 kVA single-phase and up to 500 kVA three-phase output, SCR/IGBT technology, VFI-SS-111 class, 150% for 1 minute overload.
On this page
Overview
Chloride's CP70Z datasheet (rev20-0526) introduces an industrial UPS family designed for oil and gas, refining, power generation, rail and process industries. The system is based on SCR/IGBT technology with digital control, covering 2.5-250 kVA single-phase and 5-500 kVA three-phase output. Dual cooling channels, input and output transformers, board conformal coating and halogen-free cables are standard.
Input is 3 x 400 V (380, 415) +/-10%, 50 Hz (60 Hz) +/-5%, with inrush current of at most 10 x In. A 6- or 12-pulse thyristor rectifier is used; a 12-pulse system can reach THDi below 10% without extra filters. Rated output power is given at 0.8 lagging power factor; dynamic performance is VFI SS 111 per IEC/EN 62040-3. Overload is 150% for 1 minute and 125% for 10 minutes; short-circuit clearing on three-phase output is 315% for 100 ms and 220% for 5 s phase-to-neutral.
The rating matrix is organised by DC intermediate voltage. At 110-120 Vdc: 5, 10, 20, 30, 40, 50 and 60 kVA; at 220-240 Vdc: 10, 20, 30, 40, 50, 60, 80, 100, 120, 160, 200, 250 and 320 kVA; at 400 Vdc: 40, 50, 60, 80, 100, 120, 160, 200, 250, 320, 400 and 500 kVA. Battery options are lead-acid, nickel-cadmium and sodium metal chloride (SMC), with autonomy from a few minutes to several hours on request.
General data: efficiency up to 90% depending on rating, operating temperature 0-40 C, altitude to 1000 m without derating, IP 20, noise 60-75 dB, relative humidity below 95% non-condensing. Options include a 12-pulse rectifier, harmonic filter (THDi about 5%), bypass transformer or stabilizer, DC earth-fault detection, Modbus, Profibus and IEC 61850. The sheet gives no load-point-linked efficiency curve or weight table.
Key points
- Power: single-phase 2.5-250 kVA, three-phase 5-500 kVA (at 0.8 lagging).
- Matrix: 5-60 kVA at 110-120 Vdc; 10-320 kVA at 220-240 Vdc; 40-500 kVA at 400 Vdc.
- Class VFI SS 111 (IEC/EN 62040-3, class 1); transfer time 0 ms when synchronised.
- Overload: 150% for 1 min, 125% for 10 min.
- Short circuit: 3-ph Ph-N 315%/100 ms and 220%/5 s; Ph-Ph 190%/100 ms and 135%/5 s.
- Inrush at most 10 x In; THDi below 10% with 12-pulse.
- Efficiency up to 90% by rating; operation 0-40 C, to 1000 m.
- Battery: lead-acid, NiCd, SMC; battery current limit 0.1 C lead-acid, 0.2 C NiCd and SMC.
Using it in design
- Choose the DC intermediate voltage (110-120, 220-240, 400 Vdc) together with the battery string and power class; the matrix lists discrete steps only.
- Check the 12-pulse THDi target below 10%, or about 5% with the optional filter, against generator compatibility.
- Use the short-circuit capability (315% for 100 ms) as an input to downstream protective-device selectivity.
- Request derating for altitude above 1000 m and temperature above 40 C.
- Do not use an efficiency figure without a stated load point directly in energy calculations.
Who should read it
Electrical engineers writing UPS specifications for industrial and process plants.
Document contents
- Overview and benefits
- Key features
- Technical data: input, output, battery
- General data and standards
- Ratings matrix
- Options
- LYNX HMI
Publication details
- Authors
- Chloride
- Publisher
- Chloride
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Chloride Chloride CP70Z IEC datasheet rev20-0526, rating matrix p.2. Chloride. https://www.chloride.com/files/library/files/Product%20Downloads/Chloride%C2%AE%20CP70Z%20AC%20UPS/Chloride-CP70Z-DS-EN-gl-rev20-0526.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.