GTEC MUST900 Rev.2026-03 Modular Three-Phase UPS 30-600 kVA, Technical Table (p.7)
Original title GTEC MUST900 Rev.2026-03, technical table p.7
GTEC
The GTEC MUST900 is a modular UPS built from 30 kVA / 27 kW hot-swappable modules in 180, 300 and 600 kVA cabinets (up to 900 kVA in parallel), with stated efficiency above 95% in normal mode and 99% in ECO mode.
On this page
Overview
The document is GTEC's brochure for the MUST900 modular three-phase UPS (Rev.2026-03). The system is built on 30 kVA / 27 kW hot-swappable power modules and a centralised static bypass. There are three cabinet options: MUST900-180 (up to 6 modules, 180 kVA / 162 kW), MUST900-300 (up to 10 modules, 300 kVA / 270 kW) and MUST900-600 (20 modules in two cabinets with a shared bypass in a third cabinet, 600 kVA / 540 kW). Parallel operation of 3 cabinets reaches 900 kVA, and output power factor is 0.9.
Electrically, the IGBT rectifier keeps input power factor above 0.99 and input current THDi below 3%, and the three-level inverter delivers efficiency above 95%. Input is 380/400/415 VAC, 304-478 VAC at full load, with load decreasing linearly between 228 and 304 VAC. Output voltage THDv is below 1% on linear and below 5% on full non-linear load, transient response is below 5% and recovery is below 30 ms. Battery voltage is ±240 VDC, standard 40 (20+20) 12 V batteries with 32-44 selectable (derating below 40), external, Pb or Ni-Cd.
Smart Parallel Management switches modules on and off according to load. In the document's example, at night load (30 kVA, n+1) with 2 modules working the system efficiency is 94.6%, against 85% with all 10 modules on. Operating temperature is 0-40 °C, altitude up to 1000 m (1% derating per 100 m between 1000 and 2000 m), noise at most 65 dB and protection IP20. The document notes that technical data may change without notice.
Key points
- Module 30 kVA / 27 kW, 460 x 790 x 134 mm (W x D x H), 34 kg.
- Cabinets: 180 kVA (600 x 1100 x 1600 mm, 170 kg), 300 kVA (600 x 1100 x 2000 mm, 280 kg), 600 kVA (2000 x 1100 x 2000 mm, 620 kg); 900 kVA with 3 cabinets in parallel.
- Efficiency: above 95% in normal mode, 99% in ECO mode, 95% on battery.
- Input PF above 0.99, input current THDi below 3%; output PF 0.9; output THDv below 1% on linear load.
- Bypass overload: 110% continuous, 5 min at 110-125%, 1 min at 125-150%, 1 s at 150-400%; inverter: 60 min at 110%, 10 min at 125%, 1 min at 150%.
- Battery ±240 VDC, standard 40 (20+20) 12 V units; derating below 40.
- Example: at 30 kVA night load (n+1), efficiency is 85% with 10 modules on and 94.6% with 2 on under Smart Parallel.
- Operation 0-40 °C, 1000 m (1% per 100 m between 1000 and 2000 m), 65 dB maximum, IP20.
Using it in design
- Choose module count with N+1 logic; cabinet capacity (6, 10 or 20 modules) sets the growth path.
- For variable load profiles include Smart Parallel Management in the efficiency calculation; night efficiency can drop to 85% with all modules on.
- For floor loading add cabinet (170-620 kg) and module (34 kg) weights plus the separate external battery cabinets.
- Apply derating if fewer than 40 batteries are used, and 1% per 100 m above 1000 m.
Who should read it
Data-centre electrical designers selecting modular UPS and engineers planning redundancy architecture.
Document contents
- Overview
- Best electronic design flexibility
- Maintenance management
- Efficient energy saving
- Product range
- Parallel operation up to 900 kVA
- Display and communication
- Technology
- Smart Parallel Management
- Technical table
Publication details
- Authors
- GTEC
- Publisher
- GTEC
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
GTEC GTEC MUST900 Rev.2026-03, technical table p.7. GTEC. https://gtec-power.eu/wp-content/uploads/2026/03/MUST900_ENG_WEB_Rev-2026-03.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.