Hitzinger U POWER DDUPS Systems Brochure: Dynamic Diesel Uninterruptible Power Supply

Original title Hitzinger UPS systems brochure

Hitzinger

The Hitzinger U POWER brochure presents battery-less dynamic diesel UPS (DDUPS) systems: single units up to 3000 kVA, systems up to 50 MVA, efficiency up to 97%, 10-year overhaul intervals and Uptime Tier I-IV configurations.

On this page

Overview

The document is Hitzinger's brochure for its dynamic diesel uninterruptible power supply (DDUPS) systems. The system has five main components: the diesel engine, electromagnetic clutch, synchronous alternator, kinetic energy storage module (KIN) and coupling choke. The alternator, KIN module and control unit are the company's own developments. Named fields of application are data centres, telecommunications, airports, government, hospitals and industry.

Four basic systems are offered. NBDK (IT power): single unit up to 3000 kVA, system configuration up to 50 MVA, medium-voltage systems up to 24 kV, tolerances during mains failure of ±1% frequency and ±5% voltage. NBDD (industrial): 100-1000 kVA, flywheel mounted on the alternator shaft, ±5% frequency. NBAP (pump): 50-800 kW, connected directly to a rotating machine. HPCON (clean power): 100-2500 kVA power conditioner. All offer 50/60 Hz input and voltage up to 11 kV.

The working principle: in normal operation the synchronous machine runs in motor mode, filters harmonics and balances asymmetric loads. On mains failure the KIN module supplies the load without interruption, the diesel engine starts at the same time, the electromagnetic clutch closes and the load transfers to the alternator. The configuration section shows Single, Parallel, Isolated parallel, A+B and distributed redundant N+1 (STS) layouts and alignment with Uptime Institute Tier levels. Features include battery-less operation, no input or output harmonic distortion, input power factor above 0.98, efficiency up to 97%, double the service life of a static UPS and no environmental conditioning required.

Key points

  1. Systems: NBDK (IT, single unit up to 3000 kVA, system up to 50 MVA), NBDD (100-1000 kVA), NBAP (50-800 kW), HPCON (100-2500 kVA).
  2. NBDK mains-failure tolerances: frequency ±1%, voltage ±5%; NBDD frequency ±5%.
  3. Medium-voltage systems up to 24 kV, directly generated voltage up to 11 kV.
  4. Efficiency up to 97%; input power factor above 0.98; no input or output harmonic distortion.
  5. Battery-less; the outer rotor of the kinetic energy storage (KIN) module turns at 2750 rpm.
  6. Overhaul interval 10 years; double the service life of a static UPS; no environmental conditioning needed.
  7. Tier I (N), Tier II (N+1), Tier III (N+1, concurrently maintainable), Tier IV (2(N+1), fault tolerant) configurations.
  8. Diesel engines from makers such as MTU, Cummins and Deutz; cooling options: front radiator, remote radiator, table cooler, heat exchanger.

Using it in design

  • Where a rotary UPS is considered instead of a battery room, compare DDUPS efficiency, maintenance interval and footprint against static UPS plus battery life-cycle cost.
  • Choose the configuration from the target Uptime Tier (N, N+1, 2(N+1), A+B or distributed redundant N+1 STS).
  • Evaluate medium-voltage connection (10-11 kV) and the directly generated MV option to reduce transformer needs.
  • Add diesel fuel, exhaust and cooling (radiator type) requirements to building design; obtain KIN ride-through time from the manufacturer for the project.

Who should read it

Electrical designers of large data centres and critical facilities, and managers evaluating rotary UPS options.

Document contents

  1. Fields of Application
  2. Basic Systems
  3. The System (Main Parts, Control & Switchgear Unit, Choke, Work & Energy Flow, System Configurations, Features & Benefits, Options)
  4. Our Solution
  5. Our Commitment

Publication details

Authors
Hitzinger
Publisher
Hitzinger
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Hitzinger Hitzinger UPS systems brochure. Hitzinger. https://hitzinger.at/wp-content/uploads/2021/02/hitzinger-ups-systems.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.