IREM Power Quality Catalogue: Minipower and Steropower UPG UPS Tables
Original title IREM Power Quality catalogue, STEROPOWER UPG tables pp.80–81
IREM
Pages 78-81 of IREM's Power Quality catalogue tabulate the 1-200 kVA online double-conversion Minipower and Steropower UPG UPS models, all classified VFI-SS-111.
On this page
Overview
The document consists of the UPS table pages from the Power Quality catalogue of the Italian manufacturer IREM. These pages cover the single-phase Minipower USE-UPX (1-10 kVA), the three/single-phase Minipower UPH (8-20 kVA) and the three-phase Steropower UPG (10-200 kVA) series. All are online double-conversion and carry the IEC 62040-3 classification VFI-SS-111.
The Steropower UPG table lists models of 10, 15, 20, 30, 40 and 60 kVA (kVA equal to kW) with a 380-400-415 Vac three-phase plus neutral input; the input voltage range is 320-480 Vac and frequency is 40-72 Hz. Output static regulation is ±1.5% to ±1%, dynamic regulation ±3% and crest factor 3:1. Inverter overload is 10 minutes at 110% and 1 minute at 125%; the bypass is automatic and manual with 0 ms intervention time.
On models with an internal sealed lead-acid battery, full-load backup time is 20 minutes on the UPG10, 10 on the UPG15-40 and 8 on the UPG60; typical recharge time is 6 hours. On the 80-200 kVA models the battery is external, so no backup time is tabulated. Cabinet sizes run from 280×840×700 mm (131-155 kg) to 380×850×1025 mm (288-322 kg); noise is below 40 dB, and below 50 dB on the UPG60. Protection degree is IP20.
The Minipower tables cover smaller ratings: USE1.0-UPX10 are 230 Vac single-phase, with power factor 0.9 (USE) or 1 (UPX) and weight 13-82 kg. The UPH8-UPH20 have a 380-400-415 Vac three-phase input and a 220-230-240 Vac single-phase output, weighing 72-155 kg. The catalogue states that the tables may change without notice. A battery box for extended backup and a box for an output isolation transformer are offered as options.
Key points
- Three series: Minipower USE-UPX (1-10 kVA), UPH (8-20 kVA) and Steropower UPG (10-200 kVA); all online double conversion, class VFI-SS-111.
- UPG10-60: 380-400-415 Vac 3-phase + neutral, input 320-480 Vac, frequency 40-72 Hz.
- UPG output: static ±1.5% / ±1%, dynamic ±3%, crest factor 3:1.
- Inverter overload: 10 min at 110%, 1 min at 125%; bypass overload 60 min at 125%, 10 min at 150%.
- Bypass automatic and manual; intervention time 0 ms.
- Full-load backup on internal batteries: UPG10 20 min, UPG15-40 10 min, UPG60 8 min; recharge about 6 hours.
- On UPG80-200 the battery is external (no backup time tabulated).
- UPG net weight 131-322 kg; noise below 40 dB (below 50 dB on UPG60); IP20.
- CE compliance with Directives 2014/35/EU and 2014/30/EU.
Using it in design
- Up to UPG60 the internal battery gives short backup; plan a battery box and external battery for longer runtime.
- From 80 kVA upward the battery is external, so battery room, DC cabling and protection need separate design.
- Evaluate the output isolation transformer box option where a separate neutral or earthing reference is needed.
- Carry cabinet weight (131-322 kg) into floor-loading and transport-route checks.
- With noise of 40-50 dB, check whether the UPS can be placed in office-like areas.
Who should read it
Electrical designers selecting mid-range three-phase UPS, and engineers comparing products from the Italian manufacturer.
Document contents
- Single-phase UPS: Minipower USE-UPX
- Three/single-phase UPS: Minipower UPH
- Three-phase UPS: Steropower UPG 10-60
- Three-phase UPS: Steropower UPG 80-200
Publication details
- Authors
- IREM
- Publisher
- IREM
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
IREM IREM Power Quality catalogue, STEROPOWER UPG tables pp.80–81. IREM. https://www.irem.it/Brochure/IREM-catalogue-POWER-EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.