ZIGOR ZGR SCALABLE 60-300 kVA modular online UPS datasheet
Original title Zigor UPS 2024 ZGR SCALABLE datasheet, pp.26–27
Zigor
Zigor ZGR SCALABLE is a 3-phase modular online UPS with unity power factor, scaling in 60, 150 and 300 kVA cabinets with 10-30 kVA modules; efficiency up to 95.5% in inverter mode and up to 4 units in parallel.
On this page
Overview
The ZGR SCALABLE datasheet from Zigor's 2024 UPS catalogue presents a modular online UPS family designed for data centres and critical loads, expandable across three cabinet sizes: ZGR SCALABLE 60k (10-60 kVA / kW), 150k (10-150 kVA / kW) and 300k (10-300 kVA / kW). Power grows with 10, 15, 20, 25 and 30 kVA modules, and capacity can be increased without enlarging the physical cabinet. Module power factor is 1.0 (kVA = kW).
Input is 3 phases + N + PE, voltage range 305-485 Vac (allowing generator use), frequency 40-70 Hz (auto detecting), power factor 0.99 and non-linear THDi below 3% at full load. Output is 380/400/415 Vac ±1%, frequency 50/60 Hz ±0.1% in battery mode, pure sine wave, THD below 2% (linear) and 4% (non-linear) at full load, crest factor 3:1. Transfer time is 0 ms for both battery and bypass. Online overload is below 110% for 10 minutes, below 130% for 1 minute and above 150% on bypass.
Efficiency is up to 95.5% in inverter mode. DC bus voltage is 360-600 Vdc (configurable) with up to 18 A charge current per module; autonomy depends on battery capacity. The design includes 3-level IGBT technology, 3-level smart charging, centralised control, a 7-inch touch LCD, cold start, EPO, 50-60 Hz frequency converter and grid backfeed. Parallel operation is possible as N+x for up to 4 units.
Mechanically, cabinets are 600 x 1200 x 850 mm (60k and 150k, about 142 and 153 kg) and 600 x 2000 x 850 mm (300k, 295 kg); modules are 440 x 86 x 620 mm (2U) and about 21 kg. Noise is below 58, 61 and 68 dB at 1 m. Operation is 0-40 °C and 0-95% humidity. Bypass maintenance switch (MCB) is 125 A, 200-250 A and 500-600 A. Standards: EN 62040-1, -2 and -3; CE.
Key points
- Three cabinets: ZGR SCALABLE 60k (10-60 kVA), 150k (10-150 kVA), 300k (10-300 kVA); power factor 1.0 (kVA = kW).
- Modules of 10, 15, 20, 25 and 30 kVA; module 440 x 86 x 620 mm (2U), about 21 kg.
- Input 305-485 Vac, 40-70 Hz, power factor 0.99, THDi below 3%.
- Output 380/400/415 Vac ±1%; THD below 2% (linear) and 4% (non-linear); transfer 0 ms.
- Efficiency up to 95.5% in inverter mode.
- Online overload: below 110% for 10 minutes, below 130% for 1 minute; bypass above 150%.
- DC bus 360-600 Vdc; 18 A charge per module; up to 4 units in parallel (N+x).
- Cabinet weight about 142 kg (60k), 153 kg (150k), 295 kg (300k); noise below 58/61/68 dB.
Using it in design
- Choose modules in 10-30 kVA steps against N+1 redundancy and growth plans; the cabinet size caps capacity at 60, 150 or 300 kVA.
- Use efficiency in the energy budget as the inverter-mode value (up to 95.5%); since no load point is given, request the curve from the manufacturer.
- The 305-485 Vac input range reduces battery transfers during generator and mains fluctuations; match the 360-600 Vdc DC bus with the battery string.
- Use the bypass maintenance switch ratings (125, 200-250, 500-600 A) as inputs to switchgear and protection coordination.
- Take the noise (58-68 dB) and cabinet weight into account in the electrical room layout.
Who should read it
Electrical designers selecting modular UPS for data centres and critical loads.
Document contents
- ZGR SCALABLE introduction
- Specifications: input, output, efficiency, battery
- Monitoring, connections and functions
- Environmental and mechanical characteristics
- Standards
Publication details
- Authors
- Zigor
- Publisher
- Zigor
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Zigor Zigor UPS 2024 ZGR SCALABLE datasheet, pp.26–27. Zigor. https://zigor.com/wp-content/uploads/2023/02/SHEET-ZGR-SCALABLE-60-%E2%80%93-300-KVA_CAT_ZIGOR_UPS_2024_EN_web_actualizado-13.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.