Technical guideFree to readYear not stated

Voltronic Power Galleon II 3P/3P 10-80 kVA online UPS, 5-inch LCD

Original title Voltronic Galleon II 3P/3P 10–80 kVA, 5-inch LCD brochure, printed p.31

Voltronic Power

Voltronic Power's Galleon II is a transformerless 3-phase in, 3-phase out online UPS from 10 to 80 kVA with unity output power factor, 96% efficiency in AC mode, 99% in ECO mode and up to 6 units in parallel.

On this page

Overview

The brochure page presents Voltronic Power's Galleon II series in 10, 15, 20, 30, 40, 60 and 80 kVA models; kVA equals kW (output power factor 1.0). The design is a transformerless online UPS with dual DSP and MCU chips, a 5-inch colour touch LCD that stores 500 event logs, and voice warnings. Silicon carbide diodes are said to keep efficiency above 96% in both AC and battery mode.

Input is 3 x 380/400/415 VAC (3 phase + neutral), with a voltage range of -30% to +20%, frequency 40-70 Hz, power factor of 0.99 or more at full load and input current distortion (THDi) below 3% at full linear load. Output is 3 x 360/380/400/415 VAC with ±1% regulation in battery mode, crest factor 3:1, and THD below 1% on linear and 3% on non-linear load. Transfer time is zero for both AC-to-battery and inverter-to-bypass. If output is set to 360 V, output power is derated to 90%.

Overload capability is stepped: 100-110% for 60 minutes, 111-125% for 10 minutes, 126-150% for 1 minute and above 150% for 400 ms. Efficiency is 96.0% in AC mode, 99.0% in ECO mode and 96.0% in battery mode. Charging current is adjustable; the charger rating is 30% of UPS capacity on the 10/20 kVA models and 20% on 30 kVA and above. The standard battery is 12 V / 9 Ah (10+10 or 16+16 pieces), and long-run models use a charging voltage of ±13.65 V x N (N=16-20).

Other features include an optional dual input, a programmable dry-contact card, a dynamic service password and adjustable power walk-in time, which helps optimise generator sizing. Operation is 0-40 °C, below 95% humidity and 0-1500 m altitude; above 1500 m output is derated 1% per 100 m. Noise is below 60-65 dB at 1 m.

Key points

  1. Models 10, 15, 20, 30, 40, 60 and 80 kVA; kVA = kW (output power factor 1.0); up to 6 units in parallel.
  2. Input 3 x 380/400/415 VAC, -30%/+20%, 40-70 Hz; power factor 0.99 or more; THDi below 3%.
  3. Output regulation ±1%; crest factor 3:1; THD 1% (linear) and 3% (non-linear).
  4. Efficiency: AC mode 96.0%, ECO mode 99.0%, battery mode 96.0%.
  5. Overload: 100-110% for 60 minutes, 111-125% for 10 minutes, 126-150% for 1 minute, above 150% for 400 ms.
  6. Transfer time is zero for AC-to-battery and inverter-to-bypass; power derates to 90% at 360 V output.
  7. Charger: 30% of UPS power on 10/20 kVA and 20% on 30 kVA and above; standard model recharges to 90% in 9 hours.
  8. Environment 0-40 °C, below 95% humidity, full load up to 1500 m; 1% derating per 100 m above.

Using it in design

  • With output power factor 1.0, compare IT load kW directly with UPS kW; account for the 90% derating at the 360 V output setting.
  • Separate efficiency in the energy budget as 96% in AC mode and 99% in ECO mode; judge the reduced protection of ECO mode against load sensitivity.
  • Choose battery autonomy for the standard (12 V/9 Ah) or long-run model; use the charging current and 9-hour recharge time as battery sizing inputs.
  • In parallel installations (up to 6 units, common battery pack) set the power walk-in time to suit generator sizing.
  • At sites above 1500 m apply the 1% per 100 m derating.

Who should read it

Electrical designers selecting 3-phase UPS for small and mid-size data rooms and infrastructure projects.

Document contents

  1. Galleon II 3P/3P 10-80 kVA key features
  2. Selection guide: input, output, bypass
  3. Efficiency, battery and charging
  4. Physical, environment and management

Publication details

Authors
Voltronic Power
Publisher
Voltronic Power
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Voltronic Power Voltronic Galleon II 3P/3P 10–80 kVA, 5-inch LCD brochure, printed p.31. Voltronic Power. https://voltronicpower.com/content/download/Brochure/GalleonII-33-10K-80K%285%20inch%20Touch%20LCD%29%20_DS.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.