Powertronix General Catalogue: Three-Phase IGBT, SCR and Multilevel UPS Series
Original title Powertronix general catalogue, IGBT Series technical table p.11
Powertronix
Powertronix general catalogue of Italian-built online UPS: the IGBT series covers 10-200 kVA at 0.9 power factor with 95.5% efficiency, up to 8 units in parallel (1.6 MVA) and IEC 62040-3 VFI-SS-111.
On this page
Overview
The catalogue introduces the product range of Powertronix, on the market since 1986. Three-phase UPS families are the SCR series 50-300 kVA, the IGBT series 10-200 kVA, the Multilevel series 10-500 kVA, the Modular series 20-850 kVA and the Rack Independent series 10-200 kVA. Single-phase UPS in tower and rack-tower form span 1-10 kVA. It also lists Enerclever (BID/UPS 50-300 kVA and custom Energy Stations), AVR voltage stabilisers and DC systems (CMP). All three-phase UPS are online double conversion classified IEC EN 62040-3 VFI-SS-111 and are built at Grezzago under ISO 9001 procedures.
The IGBT series comprises Mizar (10-15 kVA), Alcor (20-40 kVA), Auriga (60-100 kVA) and Auriga HP (120-200 kVA). Output power factor is 0.9; a single unit reaches 200 kVA and a parallel system of 8 units 1.6 MVA. The input draws low-distortion sine current through a PFC IGBT stage (input power factor 0.99, THDi up to 3%), and there is no output transformer. Standard features are RS232, Modbus RTU RS485, an intelligent slot (SNMP, HTTP, Modbus), dry contacts, external manual bypass and EPO, with 3-to-3, 3-to-1, 1-to-1 and 1-to-3 phase flexibility.
The technical table gives static voltage stability ±1%, dynamic ±5%, crest factor 3:1, output voltage distortion up to 1% on linear load, frequency stability 0.01%, efficiency 95.5%, and overload of 125% for 10 minutes and 150% for 60 seconds. Batteries are VRLA AGM or GEL with maximum charging current of 25% of nominal power and a DIN 41733 temperature-compensated profile. Protection is IP20; weight is 70 kg (10 kVA) to 590 kg (200 kVA); operating temperature +20 to +40 °C, relative humidity 95% non-condensing, altitude 1000 m (1% derating per 100 m up to 2000 m). Standards are IEC EN 62040-1, -2 and -3 VFI-SS-111 and the LV and EMC directives.
Key points
- Three-phase families: SCR 50-300 kVA, IGBT 10-200 kVA, Multilevel 10-500 kVA, Modular 20-850 kVA, Rack Independent 10-200 kVA; single phase 1-10 kVA.
- IGBT series: Mizar 10-15, Alcor 20-40, Auriga 60-100, Auriga HP 120-200 kVA; output power factor 0.9.
- Parallel: up to 8 units, maximum 1.6 MVA.
- Input power factor 0.99; THDi up to 3%; soft start 0-100% in 30 s.
- Output voltage static ±1%, dynamic ±5%; crest factor 3:1; efficiency 95.5%; overload 125% for 10 min, 150% for 60 s.
- Battery VRLA AGM or GEL; charging current up to 25% of nominal power; DIN 41733 temperature-compensated charging.
- IP20; weight 70-590 kg; ambient +20 to +40 °C; altitude 1000 m with 1% derating per 100 m (to 2000 m).
- Active power 9-180 kW (10-200 kVA); IEC EN 62040-1/-2/-3 VFI-SS-111.
Using it in design
- With a 0.9 power factor, a 200 kVA unit carries 180 kW; compare against the kW load list.
- For growth, record the up-to-8-unit parallel option (1.6 MVA) and N+1 redundancy in the capacity plan.
- With THDi up to 3% and input power factor 0.99, recalculate generator sizing using these values.
- Apply the 1% per 100 m derating at sites above 1000 m.
- As the design is transformerless, specify an external isolation transformer separately where isolation is needed.
Who should read it
Electrical designers and procurement engineers selecting mid- to high-power UPS.
Document contents
- Not UPS only
- Product overview
- Three-phase UPS: SCR, IGBT, Multilevel, Modular series
- IGBT Series: Mizar, Alcor, Auriga, Auriga HP
- Single-phase UPS
- Enerclever
- Voltage stabilizer and DC systems
Publication details
- Authors
- Powertronix
- Publisher
- Powertronix
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Powertronix Powertronix general catalogue, IGBT Series technical table p.11. Powertronix. https://powertronix.it/upload/files/Catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.