Statron S3000 industrial PFC / UPS system, 5-200 kVA
Original title Statron S3000 industrial UPS, March 2021, technical specifications p.4
Statron
Statron S3000 is a 5-200 kVA industrial UPS: PFC rectifier (PF 0.99, THDi <5%), up to 95% efficiency, 30-year design life, 300% short-circuit current and a battery discharge test that feeds back to the mains.
On this page
Overview
The 2021 brochure presents Statron's S3000 industrial UPS for oil and gas, power generation, transmission and distribution and infrastructure. The range covers 5 to 200 kVA (power factor 0.8 inductive), comes as S3100 and S3300 configurations and can be customized. Design life is stated as 30 years.
At the input an IGBT-based PFC rectifier works from 3x400 V +/-15%, with input power factor above 0.99 (above 0.97 at 25% load) and input harmonics THDi below 5%, so the upstream generator does not need oversizing. The DC voltage can be 110, 125, 220 or 400 V. AC-AC efficiency is 90-95% depending on model and DC voltage.
At the output, static voltage tolerance is +/-1% and dynamic tolerance is below 5% without battery, with a regulation time below 10 ms. Inverter overload is 150% for 1 min, 125% for 10 min and 105% continuous, and short-circuit current is 300% for up to 3 s. The bypass tolerates 150% for 10 min and 1000% for 100 ms. Load power factor is unrestricted and crest factor is up to 3.
A distinctive feature is the constant-current battery discharge test: battery energy is returned to the mains sinusoidally, so no load bank is needed. Battery management also covers three programmable charge voltages, temperature-dependent charging, a Smart Battery Monitor and partial discharge tests. Communication uses Modbus TCP/IP or RS232/RS485, PROFIBUS, IEC 61850 and an embedded web server.
Key points
- Power range 5-200 kVA (PF 0.8 inductive); design life 30 years.
- PFC rectifier: input PF >0.99, THDi <5%; input 3x400 V +/-15%.
- Efficiency 90-95% (AC-AC), depending on model and DC voltage.
- Output: static +/-1%, dynamic <5% (without battery), regulation <10 ms.
- Inverter overload: 1 min 150%, 10 min 125%; short circuit 300% for 3 s.
- Bypass overload: 10 min 150%, 100 ms 1000%.
- Protection IP21 up to IP54; operating temperature -10 to +40 °C (55 °C optional); no derating up to 1000 m.
- Constant-current discharge test feeds back to the mains without a load bank.
- Performance class VFI-SS-111; noise 63-70 dB(A).
Using it in design
- In generator sizing, document that the PFC rectifier's low input harmonics (THDi <5%, PF >0.99) avoid extra oversizing.
- Choose the DC bus from 110, 125, 220 or 400 V and calculate battery block count and efficiency (90-95%) accordingly.
- For output protection selectivity, compare the 300% short-circuit current and its 3 s duration with breaker curves.
- Add the mains-feedback battery test to the acceptance test procedure; it reduces the load bank area and heat rejection needed.
- Request derating data from the manufacturer for sites above 1000 m or 40 °C.
- Check that IEC 61850 or PROFIBUS fits the SCADA system.
Who should read it
Electrical engineers specifying industrial UPS for power plants, substations, oil and gas facilities and infrastructure projects.
Document contents
- Key features and operational benefits
- Reliability and durability through exceptional design
- PFC rectifier
- Integrated battery discharge test facility
- Communication platform
- Battery use and management
- S3000 technical specification
- Dimensions (IP21 basic configuration)
Publication details
- Authors
- Statron
- Publisher
- Statron
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Statron Statron S3000 industrial UPS, March 2021, technical specifications p.4. Statron. https://statron.com/wp-content/uploads/2022/07/statron-s3000-EN_mrz2021.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.