AMETEK Solidstate Controls DPP/3DPP Digital ProcessPower Industrial UPS
Original title AMETEK DPP/3DPP brochure, 3DPP specification tables (PDF p.6)
AMETEK Solidstate Controls
AMETEK Solidstate Controls brochure for the DPP (single phase 5-100 kVA) and 3DPP (three phase 10-225 kVA) industrial PWM UPS: IGBT, fibre-optic control, 92-94% AC-DC and 87-89% DC-AC efficiency, 125/250 Vdc bus.
On this page
Overview
The brochure presents the AMETEK Solidstate Controls DPP (Digital ProcessPower) UPS family, designed for process control and industrial applications. The system is true on-line double conversion, PWM based, with high-power IGBT semiconductors and digital control; fibre-optic cables carry control and communications, which improves isolation and signal speed. DPP covers single phase 5-100 kVA and 3DPP three phase 10-225 kVA. An LCD panel with touch screen shows battery test, float/equalize status, static switch position and alarms.
The technical tables list models at 0.8 and 1.0 load power factor for 120 and 240 Vdc buses. For example at 0.8 power factor and 120 Vdc (60 cells) the DPP005-3 (5 kVA/4 kW) weighs 765 lb and the DPP050-3 (50 kVA/40 kW) 2150 lb; at 240 Vdc (120 cells) the DPP100-3 (100 kVA/80 kW) weighs 4900 lb. AC-DC efficiency is 92-94% and DC-AC efficiency 87% (120 Vdc) and 89% (240 Vdc); heat loss runs from 3403 to 53 313 BTU/h. Input is 208 or 480 Vac, 60/50 Hz, ±10%; AC output is 120, 220 or 240 V.
General data: charger/rectifier output regulation ±1%, ripple <2%; the system recharges to 95% within 8 hours after a 30-minute 125% continuous battery discharge. The static switch uses inversely paired SCR sets, is make-before-break and fails automatically to bypass. Overload capability is 125% continuous, 150% for 10 min, 200% for 1 min and 1000% for 1 cycle. Cabinets are sizes GTD1X to GTD5X (for example GTD1X 79 x 32 x 36 in). The slimmer DPP cabinet is 24 x 27.5 x 79 in and designed for offshore platforms. Optional Modbus RTU, Modbus TCP and web-page communication are available.
Key points
- DPP single phase 5-100 kVA; 3DPP three phase 10-225 kVA; true on-line double conversion, PWM, IGBT.
- AC-DC efficiency 92-94%; DC-AC efficiency 87% (120 Vdc) and 89% (240 Vdc).
- DC bus 110, 120, 220, 240 Vdc; 60 cells (120 Vdc) or 120 cells (240 Vdc) lead acid.
- Input 208/480 Vac (three phase), 60/50 Hz, ±10%; output 120/220/240 Vac.
- DPP005-3: 5 kVA/4 kW, 765 lb; DPP050-3: 50 kVA/40 kW, 2150 lb; DPP100-3: 100 kVA/80 kW, 4900 lb.
- Overload: 125% continuous, 150% 10 min, 200% 1 min, 1000% 1 cycle.
- Static switch make-before-break, automatic bypass on failure; sync capture range 0.5-1.5%.
- Slimmer DPP: 24 x 27.5 x 79 in, top cable entry only; 6- or 12-pulse rectifier.
- Options: Modbus RTU, Modbus TCP, Ethernet web page; parallel redundant configuration.
Using it in design
- For industrial and process-control sites, select the DC bus voltage (125 or 250 Vdc class) together with the battery cell count.
- Set the power factor (0.8 or 1.0) from the load list; the kW rating changes with it.
- Use the table weights (765-4900 lb) for floor loading and heat loss (BTU/h) for the cooling calculation.
- Consider the 12-pulse charger option to cut reflected harmonics to the 10% level.
- In space-limited locations plan the slimmer cabinet and top-only cable entry.
Who should read it
Electrical engineers selecting UPS systems for process-control, industrial and energy facilities.
Document contents
- Digital ProcessPower UPS overview
- LCD panel and indicators
- Slimmer DPP
- DPP specifications (0.8 and 1.0 power factor)
- Cabinet dimensions and model numbering
- General specifications and optional features
- Performance specifications
Publication details
- Authors
- AMETEK Solidstate Controls
- Publisher
- AMETEK Solidstate Controls
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
AMETEK Solidstate Controls AMETEK DPP/3DPP brochure, 3DPP specification tables (PDF p.6). AMETEK Solidstate Controls. https://www.solidstatecontrolsinc.com/-/media/ameteksolidstatecontrols/documentation/brochures/dpp-3dpp-web.pdf?la=en&revision=311dbe06-333a-4297-a2c4-df4496fc29f8
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.