Aplab CEROS True Online UPS Systems (3-15 kVA)
Original title Aplab CEROS True Online UPS Systems, pp.1–2
Aplab
Aplab CEROS true on-line UPS specifications: single-phase 3, 5 and 7.5 kVA and three-phase-input 7.5, 10 and 15 kVA models with built-in isolation transformer, IGBT and DSP control.
On this page
Overview
The document is a two-page specification table for Aplab's CEROS true on-line UPS range. The first table covers RC1103, RC1105 and RC1107 (3, 5 and 7.5 kVA; 2400, 4000 and 6000 W) with single-phase input and output. The second covers RC3107, RC3110 and RC3115 (7.5, 10 and 15 kVA; 6, 8 and 12 kW) with three-phase input and single-phase output. All models are IGBT based, DSP controlled and sinusoidal.
The single-phase series has 230 Vac input, 190-265 V (150-280 V when load is below 50%), input power factor 0.8, efficiency above 80% and a built-in isolation transformer. The three-phase series has 415 Vac input (335-475 V), input power factor above 0.92, inverter efficiency above 85%, output power factor 0.8 lagging to unity and overload of 110% for 30 minutes, 125% for 10 minutes and 150% for 1 minute. In both, output is 230 Vac ±1%, THD below 3% on linear load and crest factor 3:1.
Other data: static switch transfer under 4 ms (single phase) or 5 ms in sync and 20 ms out of sync, 0-40 °C operation, humidity to 95%, forced-air cooling, noise below 50-60 dB, charging current 2-10 A and optional RS232. The three-phase models weigh about 105, 110 and 150 kg and are rated for altitudes below 1500 m. Monitoring software references date to the Windows XP era.
Key points
- Single-phase: 3 kVA/2400 W, 5 kVA/4000 W, 7.5 kVA/6000 W; DC bus 96-192 V.
- Three-phase input: 7.5 kVA/6 kW, 10 kVA/8 kW, 15 kVA/12 kW; DC bus 192/240/360 V.
- Single-phase input 190-265 Vac, PF 0.8, efficiency >80%; three-phase input 335-475 Vac, PF >0.92, efficiency >85%.
- Output 230 Vac ±1%, 50 Hz ±0.1% (free running) or ±4% (sync), THD <3%, crest factor 3:1.
- Overload (single phase): 110% 10 min, 125% 1 min, 150% 5 s; (three phase): 110% 30 min, 125% 10 min, 150% 1 min.
- Static switch transfer under 4 ms (single phase, sync); three-phase optional 5 ms sync, 20 ms non-sync.
- 0-40 °C, humidity to 95%, IP20, forced-air cooling, noise <50 dB (single phase) and <60 dB (three phase).
- Charging current 2-10 A; three-phase models weigh 105, 110 and 150 kg.
Using it in design
- For small critical rooms, enter the 0.8 input PF and 80% efficiency into energy and generator calculations; these are lower than newer transformer-less units.
- Compare output in kW, not kVA (for example 2400 W for 3 kVA), against the load list.
- Match the static switch transfer time to the ride-through of the sensitive load.
- With three-phase input, account for the 335-475 V input window and the isolation transformer weight in layout.
Who should read it
Designers selecting mid-range UPS units for small rooms and office critical loads.
Document contents
- CEROS with in-built isolation transformer (1-phase, 3-7.5 kVA)
- CEROS (3-phase input, 7.5-15 kVA)
- Technical specifications
Publication details
- Authors
- Aplab
- Publisher
- Aplab
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Aplab Aplab CEROS True Online UPS Systems, pp.1–2. Aplab. https://www.aplab.in/wp-content/uploads/2022/03/CEROS-True-Online-UPS-Systems.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.