Aokly 6-GFM-38 VRLA Battery Specification (12 V, 38 Ah)
Original title Aokly 6-GFM-38 VRLA Battery Specification, 2503, pp.1–2
Aokly
Aokly datasheet for the 12 V, 38 Ah (C10) 6-GFM-38 VRLA block: 197 x 166 x 170 mm, 12 kg, about 10 milliohm internal resistance, 10-year design life and discharge tables from 5 minutes to 20 hours.
On this page
Overview
The document is a two-page specification for the Aokly (Guangdong, China) 6-GFM-38 12 V VRLA block. Nominal capacity is 38 Ah at C10 to 1.8 V per cell and 25 °C. The block measures 197 x 166 x 170 mm, weighs 12.0 kg ±3%, has an internal resistance of about 10.0 milliohm and an ABS case (UL94 HB or V-0 optional). Self-discharge is 3% per month or less.
The operating range is -20 to 55 °C on discharge and 0 to 40 °C on charge. Capacity is 105% at 40 °C, 100% at 25 °C and 86% at 0 °C. Charge voltage is 2.25-2.30 V per cell for float (-3 mV/°C), 2.40-2.45 V for equalization (-4 mV/°C) and 2.40-2.45 V for cycle use (-5 mV/°C); maximum charge current is 9.5 A. Constant-current and constant-power tables run from 5 minutes to 20 hours for end voltages of 9.60 to 11.10 V; at 10.50 V the 15-minute current is 64.2 A and the 1-hour current 26.4 A.
The second page lists general features: 10-year design life, low self-discharge, wide temperature range and fully sealed maintenance-free construction. Applications are telecom, UPS and data centre, energy storage, emergency lighting, security and medical equipment. Standards are IEC 60896, IEC 61427, GB/T 19638 and YD/T 1360-2015; the product carries TLC, CE and RoHS marks.
Key points
- 12 V, 38 Ah (C10, 1.8 V/cell, 25 °C); 197 x 166 x 170 mm; 12.0 kg ±3%.
- Internal resistance about 10.0 milliohm; self-discharge 3% per month or less.
- Capacity: 105% at 40 °C, 100% at 25 °C, 86% at 0 °C.
- Float 2.25-2.30 V/cell (-3 mV/°C); cycle and equalization 2.40-2.45 V/cell; maximum charge current 9.5 A.
- Operation: discharge -20 to 55 °C, charge 0 to 40 °C.
- Constant current at 10.50 V end voltage: 5 min 83.2 A, 15 min 64.2 A, 1 h 26.4 A, 10 h 3.86 A.
- Constant power at 10.50 V: 5 min 906 W, 15 min 738 W, 1 h 306 W.
- 10-year design life; IEC 60896 and IEC 61427 compliant.
Using it in design
- Read the constant-power table at the UPS cut-off voltage; for a 12 V block the 10.50 V row matches 1.75 V per cell.
- If the battery room is below 25 °C, derate capacity with the table's temperature ratios.
- Set charger compensation to -3 mV/°C per cell for float.
- Include the 12 kg block weight in rack loading for small UPS and telecom backups.
Who should read it
Designers and buyers selecting batteries for small UPS and DC power systems.
Document contents
- Specifications
- Constant current discharge
- Constant power discharge
- General features, applications and standards
Publication details
- Authors
- Aokly
- Publisher
- Aokly
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document