Fullriver HGL100-12B: General Purpose AGM Battery Datasheet
Original title Fullriver HGL100-12B: General Purpose AGM Battery datasheet
Fullriver
The Fullriver HGL100-12B is a 12 V / 100 Ah (20 h) valve-regulated lead-acid AGM battery with a stated 6-8 year trickle life at 25 °C, a weight of 30.5 kg and an internal resistance of about 3.5 mΩ.
On this page
Overview
The document is the datasheet of the Fullriver HGL100-12B. The unit is presented as a 12 V (6-cell) valve-regulated lead-acid battery for standby applications such as UPS, telecom, switchboard and medical systems. Rated capacity at 25 °C is 100 Ah at the 20-hour rate (to 1.75 V per cell), 93 Ah at 10 h, 85 Ah at 5 h (to 1.70 V) and 60 Ah at 1 h (to 1.60 V).
Mechanical data: 331 x 175 mm footprint, 218 mm overall height, about 30.5 kg, M8 female terminal with 7-9 N.m torque. Internal resistance is about 3.5 mΩ, short-circuit current 2270 A and maximum short-duration discharge current 1000 A (5 s). The container is ABS (UL 94-HB) as standard with an optional flame-retardant ABS (UL 94-V0). The battery can operate in any position without leakage.
On charging, trickle control voltage is 13.5-13.8 V at 25 °C and cycle use is 14.40-14.9 V (initial current 30 A or less); temperature compensation is -4 mV/cell/°C for cycle use and -3 mV/cell/°C for float. The constant-current discharge table (1.75 V/cell) runs from 144.5 A at 15 minutes to 5.0 A at 20 hours. Values are averages after three charge/discharge cycles and are not minimum values.
Key points
- Nominal 12 V; capacity 100 Ah (20 h), 93 Ah (10 h), 85 Ah (5 h), 60 Ah (1 h) at 25 °C.
- Trickle life expectancy 6-8 years at 25 °C; capacity loss per month below 3% at 20 °C.
- Size 331 x 175 x 218 mm (overall height); weight about 30.5 kg; M8 terminal, torque 7-9 N.m.
- Internal resistance about 3.5 mΩ; short-circuit current 2270 A; maximum 1000 A for 5 s.
- Float voltage 13.5-13.8 V per block, cycle voltage 14.40-14.9 V per block (25 °C).
- Capacity depends on temperature: 102% at 40 °C, 85% at 0 °C, 65% at -15 °C (20-hour rate).
- Constant-current discharge: 57.4 A for 1 h, 24.5 A for 3 h, 9.3 A for 10 h (1.75 V/cell).
Using it in design
- For autonomy, use the table current for the actual duration rather than the rated Ah, and apply a low-temperature factor.
- Set the charger float voltage within 13.5-13.8 V per block with -3 mV/cell/°C compensation.
- The 2270 A short-circuit current is an input for DC protective device breaking capacity and selectivity studies.
- Include the 30.5 kg block weight in rack loading and the battery-room weight plan.
Who should read it
Electrical engineers designing UPS battery banks and maintenance teams.
Document contents
- Specifications and rated capacity
- Mechanical specifications
- Charge characteristics
- Constant current discharge ratings
- Discharge curves and temperature effects
Publication details
- Authors
- Fullriver
- Publisher
- Fullriver
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Fullriver Fullriver HGL100-12B: General Purpose AGM Battery datasheet. Fullriver. https://fullriver.com/upload/article/20240617/666fdf70775d3.pdf