Fullriver HGL100-12B: General Purpose AGM Battery Datasheet

Original title Fullriver HGL100-12B: General Purpose AGM Battery datasheet

Fullriver

The Fullriver HGL100-12B is a 12 V / 100 Ah (20 h) valve-regulated lead-acid AGM battery with a stated 6-8 year trickle life at 25 °C, a weight of 30.5 kg and an internal resistance of about 3.5 mΩ.

On this page

Overview

The document is the datasheet of the Fullriver HGL100-12B. The unit is presented as a 12 V (6-cell) valve-regulated lead-acid battery for standby applications such as UPS, telecom, switchboard and medical systems. Rated capacity at 25 °C is 100 Ah at the 20-hour rate (to 1.75 V per cell), 93 Ah at 10 h, 85 Ah at 5 h (to 1.70 V) and 60 Ah at 1 h (to 1.60 V).

Mechanical data: 331 x 175 mm footprint, 218 mm overall height, about 30.5 kg, M8 female terminal with 7-9 N.m torque. Internal resistance is about 3.5 mΩ, short-circuit current 2270 A and maximum short-duration discharge current 1000 A (5 s). The container is ABS (UL 94-HB) as standard with an optional flame-retardant ABS (UL 94-V0). The battery can operate in any position without leakage.

On charging, trickle control voltage is 13.5-13.8 V at 25 °C and cycle use is 14.40-14.9 V (initial current 30 A or less); temperature compensation is -4 mV/cell/°C for cycle use and -3 mV/cell/°C for float. The constant-current discharge table (1.75 V/cell) runs from 144.5 A at 15 minutes to 5.0 A at 20 hours. Values are averages after three charge/discharge cycles and are not minimum values.

Key points

  1. Nominal 12 V; capacity 100 Ah (20 h), 93 Ah (10 h), 85 Ah (5 h), 60 Ah (1 h) at 25 °C.
  2. Trickle life expectancy 6-8 years at 25 °C; capacity loss per month below 3% at 20 °C.
  3. Size 331 x 175 x 218 mm (overall height); weight about 30.5 kg; M8 terminal, torque 7-9 N.m.
  4. Internal resistance about 3.5 mΩ; short-circuit current 2270 A; maximum 1000 A for 5 s.
  5. Float voltage 13.5-13.8 V per block, cycle voltage 14.40-14.9 V per block (25 °C).
  6. Capacity depends on temperature: 102% at 40 °C, 85% at 0 °C, 65% at -15 °C (20-hour rate).
  7. Constant-current discharge: 57.4 A for 1 h, 24.5 A for 3 h, 9.3 A for 10 h (1.75 V/cell).

Using it in design

  • For autonomy, use the table current for the actual duration rather than the rated Ah, and apply a low-temperature factor.
  • Set the charger float voltage within 13.5-13.8 V per block with -3 mV/cell/°C compensation.
  • The 2270 A short-circuit current is an input for DC protective device breaking capacity and selectivity studies.
  • Include the 30.5 kg block weight in rack loading and the battery-room weight plan.

Who should read it

Electrical engineers designing UPS battery banks and maintenance teams.

Document contents

  1. Specifications and rated capacity
  2. Mechanical specifications
  3. Charge characteristics
  4. Constant current discharge ratings
  5. Discharge curves and temperature effects

Publication details

Authors
Fullriver
Publisher
Fullriver
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Fullriver Fullriver HGL100-12B: General Purpose AGM Battery datasheet. Fullriver. https://fullriver.com/upload/article/20240617/666fdf70775d3.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.