KIJO JH Series: High Rate Battery Specifications (UPS/EPS)

Original title KIJO JH Series: High Rate Battery specifications

KIJO

KIJO's JH series page lists 20 12 V high-rate AGM battery models for UPS and EPS, from 5.5 to 210 Ah, with a 10-year design life and self-discharge of at most 3% per month.

On this page

Overview

The page introduces the JH series high-rate battery under the KIJO brand of Jiangxi JingJiu Power Science & Technology. The series consists of 12 V AGM battery models developed for UPS and EPS systems where high currents are required. The range runs from JH12-24W to JH12-800W, with 20 models listed in total.

The specification table gives each model's nominal voltage (12 V), capacity, length, width, height, total height, weight and terminal type. Capacity is stated at the C20 rate for small models and the C10 rate for large ones: JH12-24W 5.5 Ah (C20), JH12-210W 55 Ah (C10), JH12-800W 210 Ah (C10). Weight runs from 1.68 kg to 68 kg and size from 90×70×101 mm to 522×240×219 mm. Terminal types are F1/F2, M5, M6 and M8.

According to the features section, design life is 10 years at 25 °C, self-discharge is below 3% per month and sealed reaction efficiency is above 99%. Operating temperature is -20 to 60 °C. Plates are pasted flat type with a patented high-rate formula, the separator is an improved AGM, the case is high-strength ABS (UL94-HB, with UL94-V0 optional) and terminals use double sealing (mechanical and epoxy). The safety valve includes a flame filter. Short internal connectors between cells lower internal resistance. The main applications are UPS/EPS; electric tools, toys, medical devices and wheelchairs are also named. The document is at monobloc level, not cell level, and gives no cabinet energy or load-time relationship.

Key points

  1. JH series: 20 models, 12 V, from JH12-24W to JH12-800W.
  2. Capacity from 5.5 Ah (C20, JH12-24W) to 210 Ah (C10, JH12-710W and JH12-800W).
  3. Design life 10 years at 25 °C; self-discharge at most 3% per month; sealed reaction efficiency at least 99%.
  4. Operating temperature -20 to 60 °C.
  5. Weight 1.68-68 kg; length 90-522 mm.
  6. Terminal types: F1/F2, M5, M6, M8.
  7. High-strength ABS case (UL94-HB), UL94-V0 optional; safety valve with flame filter.
  8. Improved AGM separator; pasted flat plate with high-rate formula.
  9. Applications: UPS/EPS, electric tools, toys, medical, wheelchairs.

Using it in design

  • Compare models by separating the C10 and C20 capacity bases; the table gives small models at C20 and large models at C10.
  • Plan battery-room temperature against the 25 °C design-life reference.
  • Use each model's length, width and total height for rack or cabinet layout.
  • Confirm connection cable and terminal torque with the manufacturer for the terminal type (M5, M6, M8).
  • If fire regulations require it, write the UL94-V0 case option into the specification.

Who should read it

Electrical designers selecting monobloc VRLA batteries for data-centre and EPS systems, and engineers preparing battery-room layouts.

Document contents

  1. JH series high-rate battery specifications (model table)
  2. Characteristics
  3. Applications
  4. Related solutions and technologies

Publication details

Authors
KIJO
Publisher
KIJO
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

KIJO KIJO JH Series: High Rate Battery specifications. KIJO. https://www.kijo-battery.com/products/jh-series-jh-high-rate-battery.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.