Monbat 12UPM4500T Top Terminal AGM VRLA Battery Datasheet (TDS-205)
Original title Monbat 12UPM4500T Top Terminal AGM VRLA: TDS-205, January 2024, pp.1–2
Monbat
Monbat 12UPM4500T is a 12 V, 125 Ah (10 h to 1.80 Vpc) top-terminal AGM VRLA UPS battery with a 10 to 12 year EUROBAT long-life design life; the sheet gives discharge and charge tables.
On this page
Overview
The Monbat 12UPM4500T is a valve-regulated lead-acid (VRLA) AGM battery block made for UPS and reserve power applications. Nominal voltage is 12 V with 6 cells, and the 125 Ah rating applies to a 10-hour discharge to 1.80 V per cell at 25 °C. Internal resistance is 3.7 mOhm and short-circuit current is 3400 A (IEC 60896-21/22). Design life at 20 °C is 10 to 12 years in the EUROBAT long-life class.
Construction uses thick flat pasted plates, very high purity lead, a lead-calcium-tin grid alloy and an AGM separator. The container and lid are ABS with UL94 V0 flammability class. Operating temperature is -20 to +60 °C with 15 to 25 °C recommended. Self-discharge is below 2% per month at 20 °C. Dimensions are 340 x 173 x 278 mm and weight is 46.5 kg; the terminal is on top, brass female M8 with a 7 Nm torque.
The performance section gives constant-current (A), constant-power per cell (W) and constant-power per block (W) discharge tables for 1.60 to 1.85 V per cell end voltages, from 5 minutes to 10 hours, plus temperature correction factors and charge conditions. Float voltage is 2.27 V per cell at 25 °C. The document is a two-page product sheet and does not cover a sizing method.
Key points
- Nominal 12 V, 6 cells, 125 Ah (10 h, 1.80 Vpc, 25 °C); internal resistance 3.7 mOhm; short-circuit current 3400 A.
- Design life at 20 °C: EUROBAT long life, 10 to 12 years.
- Float voltage 2.27 V per cell at 25 °C; temperature correction -3 mV/cell/°C.
- Equalization 2.32 V per cell, boost 2.40 V per cell; charge current limit 0.1 to 0.25 C10 A.
- Discharge tables from 5 minutes to 10 hours for 1.60 to 1.85 Vpc end voltages.
- Temperature factor: for 5 to 59 minute discharges, 0.80 at 0 °C and 1.13 at 40 °C.
- 340 x 173 x 278 mm, 46.5 kg; M8 terminal, 7 Nm torque.
- Self-discharge below 2% per month; storage up to 6 months without recharge.
Using it in design
- Read autonomy from the constant-power (W per cell) table, matching the UPS end-of-discharge voltage (for example 1.75 or 1.80 Vpc) to the table row.
- Target 15 to 25 °C in the battery room; at 0 °C, short-discharge capacity drops by a factor of 0.80.
- Set charger float voltage to 2.27 V per cell with temperature compensation.
- At 46.5 kg per block, calculate rack and floor loading from the number of strings.
- Add the 7 Nm terminal torque and supplied connectors to the installation checklist.
Who should read it
Electrical engineers sizing UPS battery systems and designing battery rooms.
Document contents
- Product characteristics
- Technical specifications and physical characteristics
- Design features
- Constant-current discharge performance
- Constant-power discharge performance
- Temperature correction factor
- Charge conditions
Publication details
- Authors
- Monbat
- Publisher
- Monbat
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Monbat Monbat 12UPM4500T Top Terminal AGM VRLA: TDS-205, January 2024, pp.1–2. Monbat. https://monbat.com/wp-content/uploads/2024/07/Data-sheet-12UPM4500Tv3.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.