Moura VRLA MVA Series Technical Manual V5, 18 December 2024, section 5 (p.8)
Original title Moura VRLA Série MVA Technical Manual V5, 18 December 2024, section 5 (p.8)
Moura
The Moura MVA series is a range of 12 V, 5 to 250 Ah (C10 at 1.75 Vpc) AGM VRLA stationary batteries; float life exceeds 10 years above 26 Ah and float voltage is 2.27 Vpc.
On this page
Overview
The manual (in Portuguese) presents the Moura Estacionária VRLA MVA series with AGM technology and reference standards such as NBR 14204/14205, IEC 60896-21/22 and IEEE 485. Rated capacity is 5 to 250 Ah (C10 to 1.75 V per cell at 25 °C), operating temperature is -15 to 45 °C (25±5 °C recommended) and float life is more than 5 years for models up to 26 Ah and more than 10 years above 26 Ah. The container and lid are high-purity PP (E series) or ABS, with optional UL 94 V0 flame retardant. The safety valve operates at 4.0 to 4.4 psi.
Section 5 gives, for 19 models from 12MVA-5 to 12MVA-250, nominal capacity at C20, C10, C5, C3 and C1 discharge rates, dimensions, weight (±3%), terminal type and terminal position. For example 12MVA-100 is 100 Ah at C10, 55 Ah at C1, 330 x 174 x 226 mm and 29.0 kg; 12MVA-250 is 250 Ah at C10, 534 x 271 x 233 mm and 71.0 kg. The manual also treats gas recombination, constant-current and constant-power discharge tables, K-factor curves, charging methods, internal resistance, thermal runaway, ripple current, life and sizing.
The charging section gives float voltage at 25 °C as 2.25 Vpc minimum, 2.27 Vpc ideal and 2.30 Vpc maximum, with a temperature coefficient of -3 mV/°C/cell; not following this range can mean loss of warranty and early failure, and temperatures above 25 °C shorten life. End of life is capacity falling to 80% of rated. The UPS sizing example takes 15 kVA, power factor 0.80, inverter efficiency 85% and 15 minutes of discharge to a total power of 14.118 kW and 235.3 W per cell.
Key points
- 19 models, 12MVA-5 to 12MVA-250; nominal capacity 5 to 250 Ah C10 (1.75 Vpc, 25 °C).
- Float life: >5 years up to 26 Ah; >10 years above 26 Ah; end of life at 80% capacity.
- Float voltage at 25 °C: 2.25 (minimum), 2.27 (ideal), 2.30 Vpc (maximum); coefficient -3 mV/°C/cell.
- Operating temperature -15 to 45 °C; recommended 25±5 °C.
- 12MVA-100: 100 Ah C10; 55 Ah C1; 330 x 174 x 226 mm; 29.0 kg.
- 12MVA-250: 250 Ah C10; 534 x 271 x 233 mm; 71.0 kg.
- Internal resistance and short-circuit current table; for example 12MVA-26: 14 mOhm, 650 A.
- Sizing example: 15 kVA, pf 0.80, inverter 85%, 15 min, 60 cells: 235.3 W per cell.
Using it in design
- In UPS sizing, use kW = kVA x pf and inverter efficiency; the example method is total power = kVA x pf / efficiency, watts per cell = total power / cell count, then select from the constant-power table at the end voltage.
- Set rectifier float voltage at 2.27 Vpc with -3 mV/°C/cell temperature compensation; stay within 2.25 to 2.30 Vpc.
- Keep the battery room at 25±5 °C; temperature shortens life.
- Use short-circuit current (for example 12MVA-26: 650 A) as an input to protection and busbar fault calculations.
- Use dimensions, ±3% weight and terminal type in rack and connection design.
Who should read it
Electrical engineers sizing and installing stationary VRLA battery systems for UPS and telecom.
Document contents
- Presentation
- Reference standards
- Product characteristics
- Construction characteristics
- Nominal capacities and dimensional characteristics
- Chemical reactions and gas recombination
- Electrical characteristics
- Discharge characteristics
- Charge characteristics
- Internal resistance and short-circuit current
- Thermal runaway
- Ripple voltage and current
- Battery life characteristics
- Battery sizing
- Packaging, receiving and storage
- Battery installation
Publication details
- Authors
- Moura
- Publisher
- Moura
- Year
- Year not stated
- Document language
- Portuguese
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Moura Moura VRLA Série MVA Technical Manual V5, 18 December 2024, section 5 (p.8). Moura. https://www.moura.com.br/assets/pdf/produtos/estacionarias/vrla/MANUAL_TECNICO_MOURA_VRLA_MVA_V5_18_DEZEMBRO_2024_ANATEL.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.