Technical guideFree to readYear not stated

Moura VRLA MVA Series Technical Manual V5, 18 December 2024, section 5 (p.8)

Original title Moura VRLA Série MVA Technical Manual V5, 18 December 2024, section 5 (p.8)

Moura

The Moura MVA series is a range of 12 V, 5 to 250 Ah (C10 at 1.75 Vpc) AGM VRLA stationary batteries; float life exceeds 10 years above 26 Ah and float voltage is 2.27 Vpc.

On this page

Overview

The manual (in Portuguese) presents the Moura Estacionária VRLA MVA series with AGM technology and reference standards such as NBR 14204/14205, IEC 60896-21/22 and IEEE 485. Rated capacity is 5 to 250 Ah (C10 to 1.75 V per cell at 25 °C), operating temperature is -15 to 45 °C (25±5 °C recommended) and float life is more than 5 years for models up to 26 Ah and more than 10 years above 26 Ah. The container and lid are high-purity PP (E series) or ABS, with optional UL 94 V0 flame retardant. The safety valve operates at 4.0 to 4.4 psi.

Section 5 gives, for 19 models from 12MVA-5 to 12MVA-250, nominal capacity at C20, C10, C5, C3 and C1 discharge rates, dimensions, weight (±3%), terminal type and terminal position. For example 12MVA-100 is 100 Ah at C10, 55 Ah at C1, 330 x 174 x 226 mm and 29.0 kg; 12MVA-250 is 250 Ah at C10, 534 x 271 x 233 mm and 71.0 kg. The manual also treats gas recombination, constant-current and constant-power discharge tables, K-factor curves, charging methods, internal resistance, thermal runaway, ripple current, life and sizing.

The charging section gives float voltage at 25 °C as 2.25 Vpc minimum, 2.27 Vpc ideal and 2.30 Vpc maximum, with a temperature coefficient of -3 mV/°C/cell; not following this range can mean loss of warranty and early failure, and temperatures above 25 °C shorten life. End of life is capacity falling to 80% of rated. The UPS sizing example takes 15 kVA, power factor 0.80, inverter efficiency 85% and 15 minutes of discharge to a total power of 14.118 kW and 235.3 W per cell.

Key points

  1. 19 models, 12MVA-5 to 12MVA-250; nominal capacity 5 to 250 Ah C10 (1.75 Vpc, 25 °C).
  2. Float life: >5 years up to 26 Ah; >10 years above 26 Ah; end of life at 80% capacity.
  3. Float voltage at 25 °C: 2.25 (minimum), 2.27 (ideal), 2.30 Vpc (maximum); coefficient -3 mV/°C/cell.
  4. Operating temperature -15 to 45 °C; recommended 25±5 °C.
  5. 12MVA-100: 100 Ah C10; 55 Ah C1; 330 x 174 x 226 mm; 29.0 kg.
  6. 12MVA-250: 250 Ah C10; 534 x 271 x 233 mm; 71.0 kg.
  7. Internal resistance and short-circuit current table; for example 12MVA-26: 14 mOhm, 650 A.
  8. Sizing example: 15 kVA, pf 0.80, inverter 85%, 15 min, 60 cells: 235.3 W per cell.

Using it in design

  • In UPS sizing, use kW = kVA x pf and inverter efficiency; the example method is total power = kVA x pf / efficiency, watts per cell = total power / cell count, then select from the constant-power table at the end voltage.
  • Set rectifier float voltage at 2.27 Vpc with -3 mV/°C/cell temperature compensation; stay within 2.25 to 2.30 Vpc.
  • Keep the battery room at 25±5 °C; temperature shortens life.
  • Use short-circuit current (for example 12MVA-26: 650 A) as an input to protection and busbar fault calculations.
  • Use dimensions, ±3% weight and terminal type in rack and connection design.

Who should read it

Electrical engineers sizing and installing stationary VRLA battery systems for UPS and telecom.

Document contents

  1. Presentation
  2. Reference standards
  3. Product characteristics
  4. Construction characteristics
  5. Nominal capacities and dimensional characteristics
  6. Chemical reactions and gas recombination
  7. Electrical characteristics
  8. Discharge characteristics
  9. Charge characteristics
  10. Internal resistance and short-circuit current
  11. Thermal runaway
  12. Ripple voltage and current
  13. Battery life characteristics
  14. Battery sizing
  15. Packaging, receiving and storage
  16. Battery installation

Publication details

Authors
Moura
Publisher
Moura
Year
Year not stated
Document language
Portuguese
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Moura Moura VRLA Série MVA Technical Manual V5, 18 December 2024, section 5 (p.8). Moura. https://www.moura.com.br/assets/pdf/produtos/estacionarias/vrla/MANUAL_TECNICO_MOURA_VRLA_MVA_V5_18_DEZEMBRO_2024_ANATEL.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.