Polarium Battery 23-inch 2U / 210 Ah SLB48-200-228-1

Original title Polarium SLB48-200-228-1 Technical Specification 770-00242 Rev 1.0, p.1

Polarium

Polarium SLB48-200-228-1 is a 48 V, 210 Ah (9912 Wh), 23-inch 2U nickel-based lithium-ion battery with a 20-year calendar life, 6 kW peak power for 60 s, 100 A cutoff current and a weight of about 53 kg.

On this page

Overview

The datasheet presents Polarium's 13S series, generation 5.5, 23-inch 2U lithium-ion battery module, intended for backup power at hybrid, off-grid and grid-connected sites. Nominal voltage is 48 V, rated capacity 210 Ah at 0.2C and 25 °C, rated energy 9912 Wh. Calendar life at 80% SOC is 20 years.

Electrical limits: peak discharge power 6 kW for 60 seconds, safe discharge cutoff current 100 A, end-of-discharge voltage (LVBD) 39 V (cut off when one cell reaches 3.0 V, 13 cells in series), charge current limit 100 A. Charge voltage is 54.6 V for 100% SOC and 52 V for 80% SOC. At charge currents of 100 A or more the battery temporarily reduces the current to 6-12 A. Temperatures: charging 0 to +55 °C, discharging -20 to +60 °C, storage -20 to +60 °C; humidity per ETSI 300 019-1-3 class 3.2 (0-95%).

Physical data: 544x725x87 mm, about 53 kg, IP20, 100 A BMS-controlled dual-pole breaker. Communication is RS485 and two RJ45 ports with Modbus, and Studio monitoring software for PC is included. Safety standards are IEC 62619, IEC 62368 and UN 38.3. The document also gives constant-current (1-24 h) and constant-power discharge tables; at a 46.5 V end voltage, 10 hours corresponds to 12.6 A or 574 W. A patented anti-theft device disables the module if removed from site.

Key points

  1. 48 V, 210 Ah (0.2C, 25 °C), 9912 Wh; nickel-based lithium-ion; 13 cells in series.
  2. Peak discharge power 6 kW (60 s); safe discharge cutoff current 100 A; charge current limit 100 A.
  3. End-of-discharge voltage 39 V; charge voltage 54.6 V (100% SOC) and 52 V (80% SOC).
  4. Calendar life 20 years (at 80% SOC).
  5. Temperatures: charge 0 to +55 °C, discharge -20 to +60 °C, storage -20 to +60 °C; ETSI 300 019-1-3 class 3.2.
  6. Size 544x725x87 mm (23-inch 2U), about 53 kg, IP20.
  7. Communication RS485, 2 x RJ45, Modbus; standards IEC 62619, IEC 62368, UN 38.3.
  8. Example autonomy: 12.6 A or 574 W for 10 hours to a 46.5 V end voltage.

Using it in design

  • In telecom and edge cabinets, compare the 725 mm depth and 53 kg of the 23-inch 2U module with the shelf load capacity.
  • With a 39 V end-of-discharge voltage, choose the DC/DC or UPS input low-voltage threshold to match.
  • Use the constant-power table to size module count for the target autonomy; at 1 hour the table gives a value only at the 46.5 V end voltage.
  • Verify the charger and room temperature against the 100 A charge limit and the 0-55 °C charge range.
  • Connect the Modbus and RS485 output to the monitoring system.

Who should read it

Engineers designing telecom and edge backup power and suppliers evaluating lithium-ion battery options.

Document contents

  1. Technical Specification
  2. Constant Current discharge table
  3. Constant Power discharge table

Publication details

Authors
Polarium
Publisher
Polarium
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Polarium Polarium SLB48-200-228-1 Technical Specification 770-00242 Rev 1.0, p.1. Polarium. https://polarium.com/wp-content/uploads/dlm_uploads/2022/09/POLARIUM-SLB48-200-228-1-TDS.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.