Start Akü stationary OPzS battery series technical tables
Original title Start Akü: Stasyoner Akü, OPZS technical tables
Start Akü
Start Akü's domestically produced OPzS stationary lead-acid batteries: 2 V cells from 100 to 3000 Ah, 6 V and 12 V monoblocs from 50 to 200 Ah; tubular positive plates and a low-maintenance design.
On this page
Overview
The page presents the OPzS series of Start Akü Tic. ve San. Ltd. Şti., active in the stationary battery sector since 1980. The batteries are produced in Turkey and are lead-acid. The manufacturer cites long life from the lead alloy used, a low-maintenance design that needs no distilled water top-up for a long time, delivery with connectors, and dispatch either wet or dry-charged to customer order.
Construction details: the positive plates are tubular, with polyester tubes slid over the grid spines and filled with active material. Negative plates are made by pasting high-purity lead grids with active material. Separators are thin and microporous. Cell containers are transparent SAN plastic, resistant to acid and high temperature, and 2, 6 or 12 V OPzS containers are used by capacity. Vent plugs let gases escape while preventing electrolyte leakage.
The technical tables come in two groups. The 2 V cells are listed at 100, 150, 200, 250, 300, 350, 420, 490, 600, 800, 1000, 1200, 1500, 2000, 2500 and 3000 Ah, from 4 OPzS 100 to 24 OPzS 3000; the 4 OPzS 100 cell is 103x206x380 mm and 8 kg dry, and the 24 OPzS 3000 cell is 576x212x797 mm and 160 kg dry (230 kg with acid). The 6 V monoblocs are 100, 150 and 200 Ah, and the 12 V monoblocs are 50, 100 and 150 Ah.
Areas of use are telephone exchanges, electrical protection and switchgear installations, power stations, radio-link systems, solar and wind energy, ship batteries, signalling and security systems, UPS, alarm systems and emergency lighting. The tables give length, width, height and dry and acid-filled weight for each model; the capacity discharge rate and test conditions are in the per-model PDFs.
Key points
- Stationary battery maker since 1980; OPzS series is domestically produced lead-acid.
- 2 V cells: sixteen models from 100 Ah (4 OPzS 100) to 3000 Ah (24 OPzS 3000).
- 6 V monoblocs: 100, 150, 200 Ah; 12 V monoblocs: 50, 100, 150 Ah.
- 4 OPzS 100: 103x206x380 mm, 8 kg dry, 13 kg with acid.
- 24 OPzS 3000: 576x212x797 mm, 160 kg dry, 230 kg with acid.
- Tubular positive plate, high-purity lead negative plate, transparent SAN plastic container.
- Low maintenance; dispatched wet or dry-charged; delivered with connectors.
- Uses: power stations, switchgear, UPS, telecom, signalling, emergency lighting.
Using it in design
- Calculate rack and floor loading from the acid-filled weight; for example the 2000 Ah cell is 155 kg and the 3000 Ah cell 230 kg with acid.
- Compare cell dimensions (length, width, height) with the battery room layout and rack spacing; height varies from 380 to 821 mm.
- Confirm from the per-model PDF which discharge rate (C10, C20 and so on) the capacity values refer to.
- Flooded cells release gas, so calculate battery room ventilation to the applicable standard and plan commissioning for dry-charged deliveries.
Who should read it
Electrical engineers and procurement teams selecting stationary batteries for power stations, switchgear, telecom and UPS applications.
Document contents
- Company and general characteristics
- Structural characteristics (plates, separators, cells, vent plugs)
- Areas of use
- OPzS series 2 V cells table
- OPzS series 6 V and 12 V monobloc table
Publication details
- Authors
- Start Akü
- Publisher
- Start Akü
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Start Akü Start Akü: Stasyoner Akü, OPZS technical tables. Start Akü. https://www.startaku.com.tr/stasyoner.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.