XGW 384 V 100 Ah high-voltage LFP battery system (UPS and energy storage)

Original title XGW 384V100Ah lithium iron phosphate battery system, VER 202105, pp.1–2

XGW Digital Technology

The XGW 384 V / 100 Ah system is a 38.4 kWh high-voltage battery rack of 120S1P-connected 3.2 V 100 Ah LFP cells, 324-438 V, 46.1 kW maximum output, over 2500 cycles and about 350 kg.

On this page

Overview

XGW Digital Technology (Shenzhen) offers a complete lithium iron phosphate (LFP) battery system solution for high-voltage energy storage with a wide voltage range of 96-1000 V. The datasheet (version 202105) says the system can be used in UPS, home storage and commercial and industrial energy storage. This document gives the specification of the 384 V / 100 Ah rack.

The system is built from 3.2 V / 100 Ah cells. The module is 15S1P and the system 120S1P; nominal voltage is 384 V, nominal capacity 100 Ah and nominal energy 38.4 kWh. The operating voltage range is 324-438 V, with a cut-off voltage of 324 V and maximum charge voltage of 384 V. Maximum discharge current is 120 A, maximum charge current 100 A and maximum output power 46.1 kW.

Cycle life is more than 2500 at 25 °C, 0.5C/1C and 80% DOD. Charging temperature is 0-55 °C, discharge temperature -20 to 55 °C and relative humidity below 95%. Communication is CAN/RS485/RS232 (a LAN port is also in the feature list); the dry contact is customised on request. Mechanically the battery box is 530 x 442 x 133 mm, the control box 430 x 442 x 133 mm, the 42U rack 600 x 800 x 2000 mm, protection class IP20 and system weight about 350 kg. Certifications are CE and UN38.3. Features include standardised module design, dual charge and discharge control and no-gap power supply.

Key points

  1. Nominal 384 V, 100 Ah, 38.4 kWh; cell 3.2 V 100 Ah, module 15S1P, system 120S1P.
  2. Voltage range 324-438 V; cut-off voltage 324 V; maximum charge voltage 384 V.
  3. Maximum discharge current 120 A, charge current 100 A, output power 46.1 kW.
  4. Cycles: more than 2500 (25 °C, 0.5C/1C, 80% DOD).
  5. Temperature: charge 0-55 °C, discharge -20 to 55 °C; humidity below 95%.
  6. Mechanical: 42U rack 600 x 800 x 2000 mm, about 350 kg, IP20.
  7. Communication CAN/RS485/RS232; certifications CE and UN38.3.

Using it in design

  • Determine the usable energy of the 384 V / 100 Ah rack with DOD in mind; 38.4 kWh is nominal energy and the cycle figure is for 80% DOD.
  • Match the UPS DC bus voltage with the rack voltage range (324-438 V, cut-off 324 V).
  • Compare the 120 A maximum discharge current and 46.1 kW with the UPS load profile; higher power needs racks in parallel or more cabinets.
  • Use the roughly 350 kg weight and the 600 x 800 x 2000 mm footprint as inputs to floor loading and layout drawings.

Who should read it

Electrical designers selecting lithium UPS batteries or energy storage systems.

Document contents

  1. Features
  2. System specification
  3. Mechanical dimensions
  4. Performance curve

Publication details

Authors
XGW Digital Technology
Publisher
XGW Digital Technology
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

XGW Digital Technology XGW 384V100Ah lithium iron phosphate battery system, VER 202105, pp.1–2. XGW Digital Technology. https://www.xgwtech.com/assets/downloads/ups-384v-100ah.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.