XGW 384 V 100 Ah high-voltage LFP battery system (UPS and energy storage)
Original title XGW 384V100Ah lithium iron phosphate battery system, VER 202105, pp.1–2
XGW Digital Technology
The XGW 384 V / 100 Ah system is a 38.4 kWh high-voltage battery rack of 120S1P-connected 3.2 V 100 Ah LFP cells, 324-438 V, 46.1 kW maximum output, over 2500 cycles and about 350 kg.
On this page
Overview
XGW Digital Technology (Shenzhen) offers a complete lithium iron phosphate (LFP) battery system solution for high-voltage energy storage with a wide voltage range of 96-1000 V. The datasheet (version 202105) says the system can be used in UPS, home storage and commercial and industrial energy storage. This document gives the specification of the 384 V / 100 Ah rack.
The system is built from 3.2 V / 100 Ah cells. The module is 15S1P and the system 120S1P; nominal voltage is 384 V, nominal capacity 100 Ah and nominal energy 38.4 kWh. The operating voltage range is 324-438 V, with a cut-off voltage of 324 V and maximum charge voltage of 384 V. Maximum discharge current is 120 A, maximum charge current 100 A and maximum output power 46.1 kW.
Cycle life is more than 2500 at 25 °C, 0.5C/1C and 80% DOD. Charging temperature is 0-55 °C, discharge temperature -20 to 55 °C and relative humidity below 95%. Communication is CAN/RS485/RS232 (a LAN port is also in the feature list); the dry contact is customised on request. Mechanically the battery box is 530 x 442 x 133 mm, the control box 430 x 442 x 133 mm, the 42U rack 600 x 800 x 2000 mm, protection class IP20 and system weight about 350 kg. Certifications are CE and UN38.3. Features include standardised module design, dual charge and discharge control and no-gap power supply.
Key points
- Nominal 384 V, 100 Ah, 38.4 kWh; cell 3.2 V 100 Ah, module 15S1P, system 120S1P.
- Voltage range 324-438 V; cut-off voltage 324 V; maximum charge voltage 384 V.
- Maximum discharge current 120 A, charge current 100 A, output power 46.1 kW.
- Cycles: more than 2500 (25 °C, 0.5C/1C, 80% DOD).
- Temperature: charge 0-55 °C, discharge -20 to 55 °C; humidity below 95%.
- Mechanical: 42U rack 600 x 800 x 2000 mm, about 350 kg, IP20.
- Communication CAN/RS485/RS232; certifications CE and UN38.3.
Using it in design
- Determine the usable energy of the 384 V / 100 Ah rack with DOD in mind; 38.4 kWh is nominal energy and the cycle figure is for 80% DOD.
- Match the UPS DC bus voltage with the rack voltage range (324-438 V, cut-off 324 V).
- Compare the 120 A maximum discharge current and 46.1 kW with the UPS load profile; higher power needs racks in parallel or more cabinets.
- Use the roughly 350 kg weight and the 600 x 800 x 2000 mm footprint as inputs to floor loading and layout drawings.
Who should read it
Electrical designers selecting lithium UPS batteries or energy storage systems.
Document contents
- Features
- System specification
- Mechanical dimensions
- Performance curve
Publication details
- Authors
- XGW Digital Technology
- Publisher
- XGW Digital Technology
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
XGW Digital Technology XGW 384V100Ah lithium iron phosphate battery system, VER 202105, pp.1–2. XGW Digital Technology. https://www.xgwtech.com/assets/downloads/ups-384v-100ah.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.