CONSNANT CNG330 160-250kVA official model specification table

Original title CONSNANT CNG330 160–250kVA official model specification table

CONSNANT

CONSNANT CNG330 low-frequency three-phase online UPS: 160, 200 and 250 kVA (128-200 kW), 6/12-pulse rectifier, output isolation transformer, up to 8 units in parallel.

On this page

Overview

CONSNANT's product page presents the CNG330 series of 160-250 kVA low-frequency online UPS with three-phase output. Capacities are 160 kVA/128 kW, 200 kVA/160 kW and 250 kVA/200 kW. Nominal voltage is 380/400/415 VAC, input range +/-20% and frequency 50/60 Hz. The page lists target uses as IDC, hospitals, traffic control, banks, industrial processes and medium-scale network management.

The technology is online double conversion (VFI) with IGBT and an isolation transformer at the inverter output. The input supports 6- or 12-pulse rectification, with input current distortion below 4% using a filter. Power factor is 0.8/0.9, output voltage 220 V +/-1% phase-to-neutral, stability under 100% unbalanced load within 2%, THD below 3% linear and 5% non-linear, transfer time 0 ms. Overload is 125% for 10 minutes and 150% for 1 minute, then transfer to bypass.

Efficiency can exceed 98% in a selectable economy mode for stable mains. Battery voltage is 384 VDC with a standard 32 blocks (30-34) or 40 blocks (38-42). The text describes up to 6 units in parallel or N+1 redundancy with closed-loop communication, while the technical table gives 8 parallel machines. A generator interface, backfeed protection, a 128-message event log, RS232/RS485 and optional SNMP are included.

Physical data: size 1200 x 850 x 1900 mm (W x D x H), net weight 805, 902 and 1360 kg, gross weight 863, 958 and 1403 kg, operating temperature 0-40 C, noise below 65 dB at 1 m. The page also explains low versus high frequency UPS: the low-frequency design has an SCR rectifier and a power-frequency isolation transformer; high-frequency designs are smaller and lighter, low-frequency designs heavier and costlier.

Key points

  1. Three models: 160 kVA/128 kW, 200 kVA/160 kW and 250 kVA/200 kW.
  2. Nominal voltage 380/400/415 VAC, input range +/-20%, 50/60 Hz.
  3. Double-conversion VFI, IGBT, isolation transformer at inverter output.
  4. 6/12-pulse rectification; input current distortion below 4% with filter.
  5. Overload: 125% for 10 min, 150% for 1 min, then bypass.
  6. Efficiency above 98% in economy mode; transfer time 0 ms.
  7. Battery 384 VDC; standard 32 or 40 blocks.
  8. Net weight 805, 902, 1360 kg; size 1200 x 850 x 1900 mm; up to 8 units in parallel.

Using it in design

  • Compare the critical load in kW with the 0.8 or 0.9 power factor; for 250 kVA the limit is 200 kW.
  • Carry the weight (up to 1.4 t) and the 1200 x 850 mm footprint into UPS-room floor loading.
  • Assess 6- and 12-pulse options for input harmonics together with generator and transformer sizing.
  • If economy mode is used, compare the protection level in that mode with load sensitivity.
  • State the redundancy target (N+1) and the closed-loop communication path in the specification for parallel systems.

Who should read it

Electrical engineers and data-centre designers selecting medium and large UPSs.

Document contents

  1. Model and application fields
  2. Features
  3. Other characteristics
  4. Low versus high frequency UPS
  5. Technical parameters
  6. Service and warranty

Publication details

Authors
CONSNANT
Publisher
CONSNANT
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CONSNANT CONSNANT CNG330 160–250kVA official model specification table. CONSNANT. https://www.consnant.com/160-250kva-low-frequency-online-ups-three-phase-output

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.