CONSNANT CNG330 low-frequency three-phase online UPS: 160, 200 and 250 kVA (128-200 kW), 6/12-pulse rectifier, output isolation transformer, up to 8 units in parallel.
On this page
Overview
CONSNANT's product page presents the CNG330 series of 160-250 kVA low-frequency online UPS with three-phase output. Capacities are 160 kVA/128 kW, 200 kVA/160 kW and 250 kVA/200 kW. Nominal voltage is 380/400/415 VAC, input range +/-20% and frequency 50/60 Hz. The page lists target uses as IDC, hospitals, traffic control, banks, industrial processes and medium-scale network management.
The technology is online double conversion (VFI) with IGBT and an isolation transformer at the inverter output. The input supports 6- or 12-pulse rectification, with input current distortion below 4% using a filter. Power factor is 0.8/0.9, output voltage 220 V +/-1% phase-to-neutral, stability under 100% unbalanced load within 2%, THD below 3% linear and 5% non-linear, transfer time 0 ms. Overload is 125% for 10 minutes and 150% for 1 minute, then transfer to bypass.
Efficiency can exceed 98% in a selectable economy mode for stable mains. Battery voltage is 384 VDC with a standard 32 blocks (30-34) or 40 blocks (38-42). The text describes up to 6 units in parallel or N+1 redundancy with closed-loop communication, while the technical table gives 8 parallel machines. A generator interface, backfeed protection, a 128-message event log, RS232/RS485 and optional SNMP are included.
Physical data: size 1200 x 850 x 1900 mm (W x D x H), net weight 805, 902 and 1360 kg, gross weight 863, 958 and 1403 kg, operating temperature 0-40 C, noise below 65 dB at 1 m. The page also explains low versus high frequency UPS: the low-frequency design has an SCR rectifier and a power-frequency isolation transformer; high-frequency designs are smaller and lighter, low-frequency designs heavier and costlier.
Key points
- Three models: 160 kVA/128 kW, 200 kVA/160 kW and 250 kVA/200 kW.
- Nominal voltage 380/400/415 VAC, input range +/-20%, 50/60 Hz.
- Double-conversion VFI, IGBT, isolation transformer at inverter output.
- 6/12-pulse rectification; input current distortion below 4% with filter.
- Overload: 125% for 10 min, 150% for 1 min, then bypass.
- Efficiency above 98% in economy mode; transfer time 0 ms.
- Battery 384 VDC; standard 32 or 40 blocks.
- Net weight 805, 902, 1360 kg; size 1200 x 850 x 1900 mm; up to 8 units in parallel.
Using it in design
- Compare the critical load in kW with the 0.8 or 0.9 power factor; for 250 kVA the limit is 200 kW.
- Carry the weight (up to 1.4 t) and the 1200 x 850 mm footprint into UPS-room floor loading.
- Assess 6- and 12-pulse options for input harmonics together with generator and transformer sizing.
- If economy mode is used, compare the protection level in that mode with load sensitivity.
- State the redundancy target (N+1) and the closed-loop communication path in the specification for parallel systems.
Who should read it
Electrical engineers and data-centre designers selecting medium and large UPSs.
Document contents
- Model and application fields
- Features
- Other characteristics
- Low versus high frequency UPS
- Technical parameters
- Service and warranty
Publication details
- Authors
- CONSNANT
- Publisher
- CONSNANT
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
CONSNANT CONSNANT CNG330 160–250kVA official model specification table. CONSNANT. https://www.consnant.com/160-250kva-low-frequency-online-ups-three-phase-output
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.