Controlled Power Company MD Series UPS brochure MD-004-1000, model selection guide p.6

Controlled Power Company (Trystar)

Controlled Power Company (Trystar) MD series UPS with isolation transformer: seven models of 3.1-7.5 kVA, 2170-5250 W, 89-91% efficiency, 7-11 min battery runtime at full load.

On this page

Overview

Controlled Power Company's MD series brochure (MD-004-1000, revised April 2009) presents uninterruptible power systems from 3.1 to 7.5 kVA. Target uses are networking, hosts, telecommunications, CAD/CAM, industrial controls, medical labs and communication closets. The systems keep the load powered for approximately 10 minutes to several hours, depending on the battery reserve purchased.

All MD models include a power-purifying isolation transformer as standard and offer input and output voltage choice between 120 and 240 V. Input power factor correction exceeds 0.95, input harmonics are below 10% THD and the input operating range is +10%/-40%. The patented Fuzzy Ranging control widens the input range down to -40% as a function of load and handles deep brownouts without battery use; Fuzzy Ranging Plus extends the range to 60% of nominal voltage.

Performance: overload 125% for ten minutes, surge capability 150% of rating without static bypass, typical output regulation +/-3%, frequency stability +/-0.2 Hz, crest factor 3.5:1, K factor 30 or better. Safety listings are UL 1778, UL 544 and CSA; total system MTBF is 100,000 hours and mean time to repair is under one hour. Operation is 0-40 C without derating, with elevation to 1500 m.

The selection guide covers seven models: MD3100 (3.1 kVA, 2170 W, 8/19 min, 264 lb), MD3500 (3.5 kVA, 2450 W, 7/17 min), MD4500 (4.5 kVA, 3200 W, 9/21 min), MD5000 (5.0 kVA, 3500 W), MD6000 (6.0 kVA, 4200 W, 11/27 min), MD7000 (7.0 kVA, 5000 W, 8/25 min) and MD7500 (7.5 kVA, 5250 W, 7/21 min). Runtimes are at full and half load, efficiency 89-91%, DC bus 48 V (3.1-5.0 kVA) and 96 V (6.0-7.5 kVA), battery life 5 years.

Key points

  1. Seven models: 3.1, 3.5, 4.5, 5.0, 6.0, 7.0 and 7.5 kVA; 2170, 2450, 3200, 3500, 4200, 5000 and 5250 W.
  2. Battery runtime 7-11 min at full load, 17-27 min at half load (by model).
  3. Efficiency 89% (3.1-5.0 kVA), 90% (6.0 and 7.0 kVA) and 91% (7.5 kVA).
  4. Input +10%/-40%, power factor above 0.95, THD below 10%.
  5. Overload 125% for 10 min; surge 150%; regulation +/-3%.
  6. Unit weight 264-493 lb; cabinets B2 and B3.
  7. DC bus 48 V (3.1-5.0 kVA) and 96 V (6.0-7.5 kVA); float 2.27 vpc.
  8. UL 1778, UL 544, CSA; MTBF 100,000 hours; noise 50-51 dB.

Using it in design

  • Check the load in watts: for a 0.7 power factor switch-mode load the MD3100 delivers 2170 W.
  • Compare the 7-11 minute full-load runtime with generator start time; request extended batteries for longer autonomy.
  • Match input and output voltage choice (120, 208, 240 V) to local distribution and load voltage.
  • Add weight (264-493 lb) and the 15-inch wide cabinet to floor-loading and layout checks.
  • Use input currents (28-68.8 A at 120 V) in feeder protection and cable sizing.

Who should read it

Electrical engineers and industrial plant designers looking for small isolation-transformer UPSs.

Document contents

  1. MD Series introduction
  2. Features and benefits
  3. System description
  4. Product specifications
  5. Proven solutions
  6. Model selection guides
  7. Battery information

Publication details

Authors
Controlled Power Company (Trystar)
Publisher
Controlled Power Company (Trystar)
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Controlled Power Company (Trystar) Controlled Power Company MD Series UPS brochure MD-004-1000, model selection guide p.6. Controlled Power Company (Trystar). https://www.trystar.com/wp-content/uploads/MD-Brochure.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.