Controlled Power Company MD Series UPS brochure MD-004-1000, model selection guide p.6
Controlled Power Company (Trystar)
Controlled Power Company (Trystar) MD series UPS with isolation transformer: seven models of 3.1-7.5 kVA, 2170-5250 W, 89-91% efficiency, 7-11 min battery runtime at full load.
On this page
Overview
Controlled Power Company's MD series brochure (MD-004-1000, revised April 2009) presents uninterruptible power systems from 3.1 to 7.5 kVA. Target uses are networking, hosts, telecommunications, CAD/CAM, industrial controls, medical labs and communication closets. The systems keep the load powered for approximately 10 minutes to several hours, depending on the battery reserve purchased.
All MD models include a power-purifying isolation transformer as standard and offer input and output voltage choice between 120 and 240 V. Input power factor correction exceeds 0.95, input harmonics are below 10% THD and the input operating range is +10%/-40%. The patented Fuzzy Ranging control widens the input range down to -40% as a function of load and handles deep brownouts without battery use; Fuzzy Ranging Plus extends the range to 60% of nominal voltage.
Performance: overload 125% for ten minutes, surge capability 150% of rating without static bypass, typical output regulation +/-3%, frequency stability +/-0.2 Hz, crest factor 3.5:1, K factor 30 or better. Safety listings are UL 1778, UL 544 and CSA; total system MTBF is 100,000 hours and mean time to repair is under one hour. Operation is 0-40 C without derating, with elevation to 1500 m.
The selection guide covers seven models: MD3100 (3.1 kVA, 2170 W, 8/19 min, 264 lb), MD3500 (3.5 kVA, 2450 W, 7/17 min), MD4500 (4.5 kVA, 3200 W, 9/21 min), MD5000 (5.0 kVA, 3500 W), MD6000 (6.0 kVA, 4200 W, 11/27 min), MD7000 (7.0 kVA, 5000 W, 8/25 min) and MD7500 (7.5 kVA, 5250 W, 7/21 min). Runtimes are at full and half load, efficiency 89-91%, DC bus 48 V (3.1-5.0 kVA) and 96 V (6.0-7.5 kVA), battery life 5 years.
Key points
- Seven models: 3.1, 3.5, 4.5, 5.0, 6.0, 7.0 and 7.5 kVA; 2170, 2450, 3200, 3500, 4200, 5000 and 5250 W.
- Battery runtime 7-11 min at full load, 17-27 min at half load (by model).
- Efficiency 89% (3.1-5.0 kVA), 90% (6.0 and 7.0 kVA) and 91% (7.5 kVA).
- Input +10%/-40%, power factor above 0.95, THD below 10%.
- Overload 125% for 10 min; surge 150%; regulation +/-3%.
- Unit weight 264-493 lb; cabinets B2 and B3.
- DC bus 48 V (3.1-5.0 kVA) and 96 V (6.0-7.5 kVA); float 2.27 vpc.
- UL 1778, UL 544, CSA; MTBF 100,000 hours; noise 50-51 dB.
Using it in design
- Check the load in watts: for a 0.7 power factor switch-mode load the MD3100 delivers 2170 W.
- Compare the 7-11 minute full-load runtime with generator start time; request extended batteries for longer autonomy.
- Match input and output voltage choice (120, 208, 240 V) to local distribution and load voltage.
- Add weight (264-493 lb) and the 15-inch wide cabinet to floor-loading and layout checks.
- Use input currents (28-68.8 A at 120 V) in feeder protection and cable sizing.
Who should read it
Electrical engineers and industrial plant designers looking for small isolation-transformer UPSs.
Document contents
- MD Series introduction
- Features and benefits
- System description
- Product specifications
- Proven solutions
- Model selection guides
- Battery information
Publication details
- Authors
- Controlled Power Company (Trystar)
- Publisher
- Controlled Power Company (Trystar)
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Controlled Power Company (Trystar) Controlled Power Company MD Series UPS brochure MD-004-1000, model selection guide p.6. Controlled Power Company (Trystar). https://www.trystar.com/wp-content/uploads/MD-Brochure.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.