Engetron DWTT20-A5 20kVA-220V official product specifications
Engetron
The Engetron DWTT20-A5 is a 20 kVA/20 kW double-conversion modular three-phase UPS: 95% double-conversion and 98% ECO-mode efficiency, 4U rack or tower, 41 kg, input power factor 0.99.
On this page
Overview
Engetron's official product page describes the DWTT20-A5 in its Double Way Trifásico Modular (A5) line: 20 kVA/20 kW, double-conversion topology, pure sine output, and automatic and manual static bypass. The unit mounts in a 19 inch rack (4U) or in tower position and has a rotatable LCD. With an output power factor of 1.0, kVA equals kW on the 10 and 20 kW rack/tower modules.
The electrical data give a three-phase 220/127 V input (3F-N-T), input voltage variation of +/-15%, input frequency of 50/60 Hz (+/-10%) and input power factor of 0.99; the rectifier uses IGBTs. The output is three-phase 220/127 V with static regulation of +/-1% and harmonic distortion below 2% on linear and below 3% on non-linear load. Three-level technology raises efficiency to 95% in double conversion and up to 98% in ECO mode.
System features include active redundant paralleling (N+1) or Dual Bus, power growth by adding modules, battery bank sharing between modules, automatic battery self-test and deep-discharge protection. Lead-acid (VRLA), alkaline (Ni-Cd) and lithium-ion batteries are supported. For monitoring the page lists remote access over HTTPS, telnet and SNMP, Ethernet connectivity (Wi-Fi and mobile network optional) and the Engetron IoT application.
Physical size is 440 x 178 x 863 mm (W x H x D) in rack form and 178 x 500 x 863 mm as a tower, with a weight of 41.0 kg. Options include individual battery management (MSB IoT), an intelligent switching panel (QMI), a 42U rack, a PDU and 24x7 service plans. The page covers a single model; battery runtime and other configurations cannot be derived from it.
Key points
- Rating is 20 kVA/20 kW; output power factor 1 (kVA = kW); double-conversion pure sine output.
- Efficiency is up to 95% in double conversion and up to 98% in ECO mode.
- Input is three-phase 220/127 V, -15%/+15%; frequency 50/60 Hz, +/-10%; input power factor 0.99; IGBT rectifier.
- Output is three-phase 220/127 V; static regulation +/-1%; THD below 2% linear and below 3% non-linear load.
- Rack 440 x 178 x 863 mm (4U) or tower 178 x 500 x 863 mm; weight 41.0 kg.
- Active paralleling (N+1) or Dual Bus; power grows by adding modules; the battery bank can be shared between modules.
- Battery compatibility is VRLA, Ni-Cd and lithium-ion; automatic battery test and deep-discharge protection.
- Remote access over HTTPS, telnet and SNMP; Ethernet standard, Wi-Fi and mobile network optional.
Using it in design
- Use the output power factor of 1.0 in capacity calculations; a 20 kW load fills a 20 kVA module completely, so N+1 needs a second module.
- Check that the 220/127 V scheme matches the facility distribution voltage; 380/400 V sites need a transformer or a different model.
- In rack layout allow for 4U height and 863 mm depth; reserve 500 mm of height for tower position.
- Use the 0.99 input power factor and the harmonic data in generator sizing.
- Decide battery chemistry (VRLA, Ni-Cd, lithium-ion) and runtime separately for the project load.
Who should read it
Electrical designers and IT infrastructure teams selecting modular UPS for rack-scale or small data rooms.
Document contents
- Product description
- Technical characteristics
- Options
- High power density, high efficiency, IoT, connectivity, high availability
- Weight and dimensions
Publication details
- Authors
- Engetron
- Publisher
- Engetron
- Year
- Year not stated
- Document language
- Portuguese
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Engetron Engetron DWTT20-A5 20kVA-220V official product specifications. Engetron. https://www.engetron.com.br/produto/ups-nobreak-trifasico-modular-20kva-220v/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.