Hykon TRANQL Online UPS Booklet: 1-6 kVA Tower Series

Original title Hykon Tranql Online UPS Booklet, printed p.2 (PDF p.5)

Hykon

Hykon's TRANQL booklet presents a 1-6 kVA single-phase double-conversion tower UPS series with efficiency up to 95.5% and a 110-300 Vac input window.

On this page

Overview

Hykon was founded in 1991 and is an ISO 9001 certified power-electronics manufacturer. After a company profile, the booklet lists the TRANQL family by power class: 1-6 kVA tower, 10-20 kVA tower, 15-40 kVA tower and rack, plus 60-120, 120-240 and 120-780 kVA modular UPS systems. The document is a product brochure rather than an application guide.

The first section covers the 1-6 kVA tower series. It is single-phase in and single-phase out with online double conversion. The headline features are unity output power factor, a wide 110-300 Vac input window, charging current up to 12 A and efficiency up to 95.5%. Stated applications include IT rooms, server rooms, data centres, communication base stations, medical devices and CCTV.

The specification table places the 1, 2 and 3 kVA models side by side. The input carries 100% load between 176 and 276 Vac; between 110 and 176 Vac the permitted power falls from 100% to 50%, and between 276 and 300 Vac the load is limited to 50%. Output voltage is selectable at 220/230/240 Vac, output THDv is below 2% on linear load and below 5% on non-linear load (per IEC 62040-3), and crest factor is 3.

Overload capability in normal mode is 30 minutes at 102-110%, 10 minutes at 110-125% and 30 seconds at 125-150%. In battery mode these shorten to 1 minute, 10 seconds and 5 seconds. Battery input is 36, 72, 96 or 192 VDC depending on the model, and an external battery cabinet is offered as an option. The booklet closes with the manufacturer's note that products are continuously updated and the document is for reference only.

Key points

  1. The 1-6 kVA tower series uses single-phase in, single-phase out online double conversion.
  2. Efficiency is 94.5%, 95% and 95.5% by model at full load in double-conversion mode.
  3. Input window 110-300 Vac: 100% load at 176-276 Vac, linear derating from 100% to 50% at 110-176 Vac, 50% load at 276-300 Vac.
  4. Output power factor is 1; output voltage 220/230/240 Vac (power factor 0.9 for the 200/208 Vac option).
  5. Output THDv is below 2% (linear load) and below 5% (non-linear load); crest factor 3.
  6. Normal-mode overload: 30 min at 102-110%, 10 min at 110-125%, 30 s at 125-150%.
  7. Maximum charging current is 12 A (adjustable); battery voltage is 36, 72, 96 or 192 VDC by model.
  8. Interfaces: RS232 standard; SNMP card, AS400, USB, RS485, EPO and external battery temperature sensor are options.

Using it in design

  • For a small IT room or edge site, use the unity output power factor when sizing 1-3 kVA units: kVA equals kW and no extra margin for power-factor loss is needed.
  • Where mains voltage can sag, carry the 50-100% power derating between 110 and 176 Vac into the load plan.
  • When choosing a battery cabinet, check the model's battery voltage (36, 72, 96 or 192 VDC) and the permitted charging current.
  • Compare the battery-mode overload times (only 5-60 seconds) with load inrush currents.
  • For 10 kVA and above, move to the 10-20 kVA tower and modular series in the same booklet; the table here covers only the 1-6 kVA class.

Who should read it

Electrical designers selecting UPS for small IT and edge data-centre loads, and engineers comparing products in the Indian market.

Document contents

  1. About Hykon
  2. Contents (TRANQL series)
  3. TRANQL 1-6 kVA tower UPS: power range, operation, application, characteristics
  4. TRANQL 1-6 kVA specification table
  5. TRANQL 10-20 kVA tower UPS summary

Publication details

Authors
Hykon
Publisher
Hykon
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Hykon Hykon Tranql Online UPS Booklet, printed p.2 (PDF p.5). Hykon. https://admin.hykonindia.com/storage/8573/Tranql-Online-UPS-Booklet_compressed.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.