ICA SIN1100C-SIN3100C User Manual (Uninterruptible Power Systems)

Original title ICA SIN1100C–SIN3100C user manual, printed p.5

ICA

ICA's SIN1100C-SIN3100C manual defines four on-line sine-wave UPS models from 1600 to 5000 VA, with their input, battery, output and installation data.

On this page

Overview

The document is a bilingual English and Indonesian user manual for the SIN1100C, SIN1500C, SIN2100C and SIN3100C models of the Indonesian manufacturer ICA. Its sections cover safety notes, introduction, technical specification, front and rear panel views, UPS installation, start-up, operating procedure, an indicator status table and troubleshooting. The unit is introduced as a true on-line sine-wave UPS using high-voltage PWM technology and a static transfer switch (STS). It is stated to suit non-linear loads such as switching power supplies, with a 3:1 crest ratio. On inverter failure or overload the STS moves the output to the bypass line and re-transfers automatically once conditions are normal. A communication interface for Windows and Linux hosts is provided.

The specification table lists capacities of 1600 VA/1040 W, 2500 VA/1625 W, 3100 VA/2015 W and 5000 VA/3250 W. Input is 185-250 V at 50 Hz ±5%; output is 220 V ±2%, 50 Hz ±1% with THD below 3%. Efficiency at full load is about 85%, transfer time on mains loss is 0 ms and backup time at nominal load is 10 minutes.

The internal battery consists of sealed lead-acid 12 V 7 Ah blocks: 7 blocks for 84 V DC, 10 for 120 V DC and 16 for 192 V DC. Operating temperature is 0-40 °C. Gross weights are given as 64, 80, 104 and 123.5 kg. The manual is a product guide for small office and IT loads; it contains no data-hall-scale design criteria.

Key points

  1. Four models: SIN1100C (1600 VA/1040 W), SIN1500C (2500 VA/1625 W), SIN2100C (3100 VA/2015 W), SIN3100C (5000 VA/3250 W).
  2. Input 185-250 V, 50 Hz ±5%; output 220 V ±2%, 50 Hz ±1%, THD below 3%.
  3. Topology: PWM-controlled on-line sine wave; STS bypass with 2 ms inverter-to-bypass and 0 ms back-transfer.
  4. Efficiency about 85% at full load; load crest ratio 3:1.
  5. Internal battery 12 V 7 Ah: 84 V DC (7 blocks), 120 V DC (10 blocks), 192 V DC (16 blocks).
  6. Backup time at nominal load is 10 minutes.
  7. Operating temperature 0-40 °C; gross weight from 64 to 123.5 kg.
  8. The manual covers safety, installation, start-up, indicator table and troubleshooting steps.

Using it in design

  • Set the roughly 85% efficiency against modern double-conversion units at 94-96% when estimating heat load and energy cost.
  • Compare the short 10-minute backup with the load's safe shutdown time.
  • Check battery voltage (84, 120 or 192 V DC) and block count before adding external batteries.
  • Note the 185-250 V input window on sites where mains voltage fluctuates.
  • Carry the manual's safety notes, and its rule of replacing batteries with the same number and type, into the maintenance procedure.

Who should read it

Technicians installing small UPS units, facility owners protecting IT equipment, and engineers comparing products in the Indonesian market.

Document contents

  1. Safety notes
  2. Introduction
  3. Technical specification
  4. Front panel and rear panel view
  5. UPS installation
  6. UPS start-up
  7. Operation procedure
  8. Table of indicator status
  9. Troubleshooting

Publication details

Authors
ICA
Publisher
ICA
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ICA ICA SIN1100C–SIN3100C user manual, printed p.5. ICA. https://icaups.co.id/wp-content/uploads/2021/02/Buku-Manual-SIN1100C-SIN3100C.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.