Lacerda Proteus RT 5/6/8/10 kVA Online Double-Conversion Nobreak Technical Description
Original title Lacerda Proteus RT 5/6/8/10kVA technical description, pp.2–3
Lacerda Sistemas de Energia
Lacerda Sistemas de Energia's Proteus RT technical description gives a 5-10 kVA/kW online double-conversion UPS with efficiency above 94%, 220 V single or two-phase and a 20-block 240 VDC battery.
On this page
Overview
The document is the Portuguese technical description of the Proteus RT nobreak (UPS) from the Brazilian manufacturer Lacerda Sistemas de Energia. The model is an online double-conversion, sine-wave UPS rated 5, 6, 8 and 10 kVA, where kVA equals kW because output power factor is 1. The chassis can be used as 19-inch 2U rack or as tower (convertible, supplied with rack-mount rails).
The rectifier has a nominal 220 Vac input, single or two phase, and is a high-frequency IGBT type. Mains variation is -36%/+27%, input power factor is above 0.99, THDi is below 5% and input frequency is 40-70 Hz. The inverter is a high-frequency IGBT with PWM pure-sine output: static regulation ±1%, dynamic regulation 4% (0-100-0 load step), THDv below 2% on linear load, crest factor 3:1 and efficiency above 95%. AC/AC efficiency in double conversion is above 94%.
The battery is sealed hot-swappable VRLA in a 19-inch rack: 20 blocks, nominal 240 VDC, float 272 VDC, minimum bank voltage 204 VDC. Recharge time is 4 hours to 90%; autonomy is set by the project, and extension is made with a quick-connect connector. Cold start, periodic and user-programmable self-test, and automatic restart after the batteries are exhausted or mains returns are also provided.
Environmental and physical data: operation 0-40 °C, relative humidity 0-95% non-condensing, altitude below 1,000 m for full performance, forced ventilation, noise given as below 55 and below 58 dBA in the table. Heat dissipation is 391, 469, 625 and 780 W (1330-2660 BTU/h). The UPS is 88×438×610 mm and the battery bank 132×438×715 mm; at least 30 cm of clearance on all sides is required for installation. Protection degree is IP 20, communication RS 232/USB, with EPO emergency shutdown and generator compatibility (GMG mode).
Key points
- Model Proteus RT: 5, 6, 8, 10 kVA (= kW); output power factor 1; online double conversion.
- Input 220 Vac single or two phase; mains -36%/+27%; input PF >0.99; THDi <5%; frequency 40-70 Hz.
- Inverter: static ±1%, dynamic 4%, THDv <2% (linear load), crest factor 3:1, efficiency >95%; AC/AC efficiency >94%.
- Battery: 20 VRLA blocks, 240 VDC nominal, float 272 VDC, minimum 204 VDC; hot-swappable 19-inch rack.
- Recharge to 90% in 4 hours; autonomy per project; quick-connect connector for extension.
- Heat dissipation 391-780 W (1330-2660 BTU/h); noise <55 and <58 dBA (two values).
- UPS 88×438×610 mm (2U rack or tower), battery bank 132×438×715 mm; tower needs at least 30 cm clearance on all sides.
- Automatic and manual bypass; cold start; automatic restart; EPO; RS 232/USB; IP 20; GMG mode compatibility.
Using it in design
- Add the heat dissipation (391-780 W) to the rack or room cooling load.
- Use the noise limit in deciding whether the UPS can be installed in an office-like area.
- The battery bank is 20 blocks at 240 VDC, so write this voltage and the quick-connect connector into the specification when planning external extension.
- On generator-fed systems, confirm GMG mode compatibility and the wide input window (-36%/+27%).
- For tower installation put 30 cm clearance on all sides into the plan; for rack installation, the 2U height and the separate battery bank height.
Who should read it
Electrical designers selecting small and mid-size UPS, and engineers comparing products in the Brazilian market.
Document contents
- Technical specifications (model, capacity, technology, efficiency, environment, chassis, bypass)
- Rectifier
- Inverter
- Battery
Publication details
- Authors
- Lacerda Sistemas de Energia
- Publisher
- Lacerda Sistemas de Energia
- Year
- Year not stated
- Document language
- Portuguese
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lacerda Sistemas de Energia Lacerda Proteus RT 5/6/8/10kVA technical description, pp.2–3. Lacerda Sistemas de Energia. https://lacerdasistemas.com.br/wp-content/uploads/2023/12/PROTEUS-RT-5-a-10-kVA-E_S-220-V.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.