Leonics Ultimate-K UKT Series Single-Phase True On-Line Double Conversion UPS Brochure
Original title LEONICS Ultimate-K UKT specification brochure LEN.BRO.UPS.229 Rev.10.10/2026, p.2
LEONICS
The brochure (Rev. 10.10/2026) for Leonics' UKT series of single-phase true online double-conversion UPS from 1 kVA to 10 kVA, giving product features and a technical table for small networks, servers and IT equipment.
On this page
Overview
The series has five models: UKT-1K, 2K, 3K, 6K and 10K. Capacities are 1 kVA / 1 kW, 2 kVA / 2 kW, 3 kVA / 2.7 kW, 6 kVA / 5.4 kW (6 kW option) and 10 kVA / 9 kW (10 kW option). The main features are high input power factor (0.99 or above), fully digital microprocessor control, wide input voltage range, start-up without battery, cold start, advanced battery management, lightning and surge protection, short-circuit and overload protection, and an emergency power off (EPO) function.
Electrical data: nominal input 220 Vac single phase, input range 110 to 300 Vac (depending on load), and at full load 176 to 300 Vac for 1K to 3K and 143 to 300 Vac for 6K and 10K; input frequency 40 to 70 Hz. Output is 220 Vac ±1%, 50 Hz ±0.1%, pure sine; THDv is up to 3% linear and 5% non-linear on 1K to 3K, and 1% and 3% on 6K and 10K; crest factor 3:1. Efficiency is 89%, 90%, 91%, 95% and 95.5%. Transfer time between AC and battery mode is zero.
Battery and physical data: sealed lead-acid (VRLA) batteries, 12 V 9 Ah x 3 in the 1K, x 6 in the 2K and 3K, x 20 in the 6K and 10K; backup time 15 to 30 minutes (depending on load); 90% charge in 6 to 10 hours. A manual maintenance bypass switch is only on the 6K and 10K, which also offer (as an option) N+X parallel redundancy up to 4 units and RS-485 and parallel ports. Weight is 12.5 kg to 71.0 kg, noise below 45 to 50 dBA at 1 m, operation 0 to 40 °C. Standards are IEC/EN 62040-1, 62040-2 and 62040-3.
Key points
- Five models: 1, 2, 3, 6 and 10 kVA; power 1, 2, 2.7, 5.4 (6 kW option) and 9 kW (10 kW option).
- Input power factor 0.99 or above; input range 110 to 300 Vac (load dependent), at full load 176 to 300 Vac (1K to 3K) or 143 to 300 Vac (6K and 10K).
- Output 220 Vac ±1%, 50 Hz ±0.1%, pure sine, crest factor 3:1.
- Efficiency 89, 90, 91, 95 and 95.5%; zero transfer time between AC and battery mode.
- VRLA batteries: 12 V 9 Ah x 3, x 6 and x 20; backup time 15 to 30 min.
- Manual maintenance bypass and (optional) N+X parallel up to 4 units only on 6K and 10K.
- Weight 12.5 kg to 71.0 kg; noise below 45 to 50 dBA at 1 m.
- IEC/EN 62040-1, -2, -3; operation 0 to 40 °C, derating above 1000 m.
Using it in design
- For small server rooms in the 1 to 10 kVA range, compare the kW limit (2.7, 5.4, 9 kW) rather than kVA with the load list.
- If maintenance bypass is needed, choose the 6K or 10K; the option for N+X parallel up to 4 units must be written into the specification separately.
- Compare the backup time (15 to 30 min) with the data-centre shutdown time; for longer time, design the extended-battery option.
- Match the two input ranges (176 to 300 Vac and 143 to 300 Vac at full load) to the mains quality.
- Evaluate the efficiency spread (89% to 95.5%) on annual energy cost.
Who should read it
Designers and procurement teams selecting single-phase UPS for small networks, server rooms and IT equipment.
Document contents
- Key features
- Product images and model range (UKT-1K, 2K, 3K, 6K, 10K)
- Specifications (capacity, input, output, efficiency, transfer time, battery, indicators, connection, communication, standards, environment, dimensions and weight)
Publication details
- Authors
- LEONICS
- Publisher
- LEONICS
- Year
- 2026
- Document number
- LEN.BRO.UPS.229 Rev.10.10/2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document