NeoPower NP3380/L 80 kVA Transformer Based 3P Online UPS Specification
Original title NeoPower NP3380/L 80kVA transformer-based three-phase online UPS specification
NeoPower
NeoPower NP3380/L is an 80 kVA three-phase double-conversion UPS with an output isolation transformer: 0.8 output power factor, 90-93% efficiency, 98% in economic mode and up to 8 units in parallel.
On this page
Overview
The page presents the 80 kVA NP3380/L from NeoPower's NP3300 series. The series covers 10 kVA to 400 kVA per unit and uses double-conversion IGBT with a DSP processor to deliver a pure sine output. An output isolation transformer is standard; an input isolation transformer and a 5th-harmonic filter are optional. Data centres, mainframes, telecom and medical equipment are named as target applications.
Electrical data: input 380 V AC (400/415 V available) 3Ph+N+PE, voltage range ±25%, 45-65 Hz, maximum 130 A, input power factor 0.8 (0.9 optional), soft start from 0 to 100% in 10 seconds. Rated output current is 115 A, THD is below 2% on linear and below 5% on non-linear load, steady-state voltage accuracy ±1%, transient response ±5% in 10 ms. Battery voltage is 192 (384) V DC, sealed maintenance-free lead acid.
Overload capacity is 60/10/1 minutes on the inverter (110/125/150% of rated current) and 18 min/10 min/1 s on bypass (150/175/200%). Size is 800x745x1400 mm, weight without battery 550 kg, protection IP22, noise below 65 dB, operating temperature -10 to 50 °C. Rated power applies below 1000 m, derated 1% per additional 100 m up to 4000 m. MTBF is stated as 30,000 hours.
Key points
- 80 kVA, output power factor 0.8 (0.9/1.0 optional); input 380 V (400/415 V) 3Ph+N+PE, maximum 130 A, rated output current 115 A.
- Efficiency: 90-93% in normal mode, 98% in economic mode; inverter efficiency 94% at full load.
- Output THD: below 2% on linear and below 5% on non-linear load; voltage accuracy ±1%; crest factor 3:1.
- Parallel operation: up to 8 units, with unbalanced-capacity paralleling and shared battery set support.
- Overload: inverter 60/10/1 min at 110/125/150%; bypass 18 min/10 min/1 s at 150/175/200%.
- Output isolation transformer standard; input isolation transformer and 5th-harmonic filter optional.
- Size 800x745x1400 mm, 550 kg without battery, IP22, noise below 65 dB; operation -10 to 50 °C, humidity up to 95%.
- Altitude derating: 1% per 100 m above 1000 m, to a maximum of 4000 m; safety standards EN 50091-1 and EN 50091-2.
Using it in design
- With the 0.8 power factor, an 80 kVA unit carries about 64 kW of real load (72 kW with the 0.9 option).
- Check the 550 kg unit weight without batteries as a separate item in the floor loading and layout plan.
- Re-verify downstream short-circuit current and neutral earthing for the output isolation transformer arrangement.
- Where harmonics matter, specify the 5th-harmonic filter and input transformer options.
- Apply the altitude derating to the capacity calculation for sites above 1000 m.
Who should read it
Electrical designers and procurement engineers evaluating transformer-based online UPS.
Document contents
- General
- Features (reliability, information processing, paralleling)
- Technical Specification
Publication details
- Authors
- NeoPower
- Publisher
- NeoPower
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
NeoPower NeoPower NP3380/L 80kVA transformer-based three-phase online UPS specification. NeoPower. https://www.ineopower.com/productdetails/2.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.