Power-One PPT IGBT Rectifier Series UPS, 11-200 kVA

Original title Power One UPS PPT IGBT Rectifier Series official Rating Available list

Power-One Micro Systems

Power-One PPT is a 3-level IGBT three-phase UPS from 11 to 200 kVA with a built-in isolation transformer, unity output power factor (kVA = kW), 96% online efficiency, 99% in ECO mode and input power factor above 0.99.

On this page

Overview

The page presents the PPT series for medical, industrial and telecom applications. A three-level IGBT design delivers high efficiency from a smaller, lighter unit: up to 96% in online mode and 99% in ECO mode. Ratings are 11, 15, 20, 30, 40, 60, 80, 100, 120, 160 and 200 kVA with three-phase input and output. Control is fully DSP-based, the isolation transformer is built in, and with unity output power factor kVA equals kW.

Input is 400/415 V AC (3Ph+N), 305-485 V AC phase to phase, 40-70 Hz. Output is 380/400/415 V AC with ±1% regulation, THD of 1% on linear and 3% on non-linear load, crest factor 3:1, transient response ±5% (10-90% load step) and recovery within 1 cycle. Overload is 110% for 60 min, 125% for 10 min and 150% for 60 s.

Battery and charger: VRLA SMF, tubular, NiCd or lithium-ion; 12 V x32 (29-32 adjustable), 384 V DC (348-384 V adjustable), default charge current 10 A and maximum 40 A. Static bypass window is 280-470 V AC with zero transfer time; maintenance bypass and ECO mode are available. Standards are EN 62040-1, -2 and -3; quality systems ISO 9001, 14001, 45001 and 50001. Communication is RS232, RS485 Modbus, SNMP, dry contacts and parallel; protection is IP21.

Key points

  1. Ratings: 11, 15, 20, 30, 40, 60, 80, 100, 120, 160, 200 kVA; output power factor 1 (kVA = kW).
  2. Efficiency: up to 96% online and 99% in ECO mode; input power factor above 0.99.
  3. Input 400/415 V AC, 305-485 V AC range, 40-70 Hz; output 380/400/415 V, ±1%.
  4. THD 1% on linear and 3% on non-linear load; crest factor 3:1; transient response ±5%.
  5. Overload: 110% for 60 min, 125% for 10 min, 150% for 60 s; bypass 125% for 10 min.
  6. Battery 12 V x32 (29-32 adjustable), 384 V DC; charge current default 10 A, maximum 40 A; VRLA, tubular, NiCd or lithium-ion.
  7. Static bypass 280-470 V AC with zero transfer; maintenance bypass and ECO mode available.
  8. EN 62040-1/-2/-3, IP21, RS485 Modbus and SNMP.

Using it in design

  • With unity output power factor, use kVA directly as kW load, but check the loss and weight effect of the built-in transformer in the layout plan.
  • If ECO mode (99%) is considered for energy saving, document the load protection level during bypass operation.
  • Match battery type (VRLA, tubular, NiCd, lithium-ion) to the 384 V DC bus and 40 A maximum charge current.
  • Compare the input voltage window (305-485 V AC) with mains quality and the generator operating band.
  • Because of IP21 protection, place the unit in a controlled UPS room.

Who should read it

Electrical designers selecting mid- to high-power transformer-based online UPS.

Document contents

  1. PPT IGBT Rectifier Series
  2. Rating Available
  3. Key Features
  4. Technical Specification (input, output, battery, bypass, standards, communications, environment)

Publication details

Authors
Power-One Micro Systems
Publisher
Power-One Micro Systems
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Power-One Micro Systems Power One UPS PPT IGBT Rectifier Series official Rating Available list. Power-One Micro Systems. https://www.poweroneups.com/product/ppt-series

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.