PowerShield Centurion RT LiFePO4 1-3 kVA Online UPS Brochure
Original title PowerShield Centurion RT LiFePO4 brochure, printed p.31
PowerShield
PowerShield Centurion RT LiFePO4 is a 1000, 2000 and 3000 VA true online double-conversion rack/tower UPS with lithium iron phosphate batteries: 0.9 output power factor and 96-97% efficiency in advanced ECO mode.
On this page
Overview
The brochure presents PowerShield's PSLCERT1000, 2000 and 3000 models (1000 VA / 900 W, 2000 VA / 1800 W, 3000 VA / 2700 W). The unit is true online double conversion with pure sine output, installable in a 19-inch rack or as a free-standing tower, with programmable outlets, USB and HID communication and NetGuard software. The lithium iron phosphate (LiFePO4) battery is credited with two to three times the battery life of lead-acid, up to one third less weight, 3 times faster recharge, tolerance up to 40 °C and a non-flammable chemistry; warranty is 5 years.
Input: line loss at 160/140/120/110 V AC by load, high-line transfer 300 V AC, frequency 40-70 Hz and 0.99 power factor correction. Output is 240 V AC (200/208/220/230/240 selectable), ±1% regulation in battery mode and crest ratio up to 3:1; mains-to-battery transfer is zero and inverter-to-bypass typically 4 ms. Efficiency in advanced ECO mode is 96%, 97% and 97%; in battery mode 87%, 88% and 89%. Typical recharge is 2 hours.
Backup time is the same for all three models: 44 min at 25% load, 22 min at 50%, 14 min at 75% and 11 min at 100%. Dimensions (D x W x H) are 380x438x88, 480x438x88 and 600x438x88 mm; weights 10.2, 14.6 and 19.7 kg. Operation is 0-40 °C, 20-90% humidity, noise below 50 dBA. Protection covers overload, discharge, thermal, short circuit and overcharge; surge protection is 1872 J / 39,000 A. Options are SNMP, Modbus, AS400, environmental monitoring, rail kit and maintenance bypass switches. Compliance is EN 62040-1-1, EN 62040-2 and RoHS.
Key points
- Models PSLCERT1000 / 2000 / 3000: 1000 VA / 900 W, 2000 VA / 1800 W, 3000 VA / 2700 W; output power factor 0.9.
- Battery: LiFePO4; typical recharge 2 hours; life two to three times lead-acid; no degradation up to 40 °C.
- Efficiency: 96%, 97%, 97% in advanced ECO mode; 87%, 88%, 89% in battery mode.
- Backup time: 44 min at 25% load, 22 min at 50%, 14 min at 75%, 11 min at 100%.
- Transfer: zero mains to battery; inverter to bypass typically 4 ms.
- Input: 40-70 Hz, input power factor 0.99, high-line transfer 300 V AC.
- Size 380x438x88 to 600x438x88 mm; weight 10.2, 14.6, 19.7 kg; noise below 50 dBA.
- Surge protection 1872 J / 39,000 A; 5-year warranty; USB/RS232, HID, optional SNMP/Modbus/AS400.
Using it in design
- Verify the rack fit: 2U-class height (88 mm) and depth up to 600 mm in a 19-inch rack.
- Compare the 11 min backup at 100% load with the autonomy requirement at this scale.
- Reflect the 40 °C battery temperature tolerance in the battery life cost model for edge and warm cabinets.
- Specify the SNMP/Modbus/AS400 card or NetGuard software if monitoring is needed.
- If advanced ECO mode is used, compare the 4 ms bypass transfer with the load tolerance.
Who should read it
Designers selecting lithium-battery UPS for edge sites and small IT rooms.
Document contents
- Features
- Specifications (input, output, efficiency, battery, protection, communications, physical, environment, compliance)
Publication details
- Authors
- PowerShield
- Publisher
- PowerShield
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
PowerShield PowerShield Centurion RT LiFePO4 brochure, printed p.31. PowerShield. https://powershield.com.au/download/centurion-rt-lifepo4-brochure/?wpdmdl=12847
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.