Technical guideFree to readYear not stated

SanRex UPS catalogue, printed p.4 single/three-phase specification tables

SanRex (Sansha Electric)

The SanRex (Sansha Electric) UPS catalogue gives data for the BACKUPS 1000 series (5-100 kVA, 200/210 V, input power factor 0.98+), a parallel-redundant series (20-4000 kVA) and the SRG series (50-400 kVA, 97%+ efficiency, transfer under 2 ms).

On this page

Overview

The Japanese UPS catalogue of Sansha Electric (SanRex) presents three product families. The BACKUPS 1000 series is a standard mid-size continuous-inverter UPS for 5-100 kVA; listed features are auto-return, wide crest factor and high overload capacity, a full-colour touch panel, lithium-ion battery compatibility and a high power factor converter that reduces input capacity. The parallel-redundant series spans 20-4000 kVA (500 kVA x 8 in parallel).

The SRG series is a continuous direct-feed type (with voltage sag compensation): 50-400 kVA and 5-50 kVA for DC 100 V loads. The catalogue stresses high efficiency (97% or more, 96% below 100 kVA) and losses cut to about a quarter of the company's continuous-inverter type. A semiconductor fast switch gives transfer of under 2 ms without interruption, and lead-acid batteries cover long outages.

The single- and three-phase tables on page 4 cover BACKUPS 1000 output ratings of 5, 10, 20, 30, 50, 75 kVA (single-phase) and 10, 20, 30, 50, 75, 100 kVA (three-phase). Output voltage is 200/210 V, input range 180-231 V, frequency 50/60 Hz ±10%, input power factor 0.98 or more and total input current harmonic distortion below 5% (each order below 3%). The circuit is IGBT full bridge with a 16 kHz carrier. Output voltage accuracy is ±1%, transient deviation ±2% and overload capacity 125% for 10 min and 150% for 1 min.

The tables also cover the battery (MSE-type valve-regulated lead-acid, 180 cells; long-life, lithium-ion or small sealed types possible), charge current (5-20 A), bypass input and the dimensions of the inverter, input/output and battery cabinets. A UPS capacity selection form is included.

Key points

  1. BACKUPS 1000: 5-100 kVA; single-phase 5, 10, 20, 30, 50, 75 kVA; three-phase 10, 20, 30, 50, 75, 100 kVA.
  2. Input: 200/210 V, 180-231 V, 50/60 Hz ±10%, power factor ≥ 0.98, THDi total below 5% (each order below 3%).
  3. Output: 200/210 V, ±1% accuracy, transient ±2%, settling 50 ms, THDv below 2% on linear load and 5% on 100% rectifier load.
  4. Overload: 125% for 10 min, 150% for 1 min; bypass 1000% for 1 cycle.
  5. IGBT full bridge, 16 kHz carrier; DC bus 300-401 V (180 cells).
  6. Battery MSE-type VRLA lead-acid; charge current 5-20 A; lithium-ion option.
  7. Parallel-redundant series 20-4000 kVA (500 kVA x 8).
  8. SRG: 50-400 kVA, efficiency ≥ 97% (≥ 96% below 100 kVA), transfer under 2 ms; losses about a quarter of the continuous-inverter type.

Using it in design

  • Use the 200/210 V, 180-231 V input system only where mains voltage is compatible; check whether 400 V systems need a transformer or another product.
  • Use the input power factor of 0.98 and THDi of 5% as inputs to generator and input protection sizing.
  • In battery room planning, use the 180 cells, charge current and battery cabinet width and depth (for example 1800 mm width for 100 kVA).
  • If efficiency is a priority, compare the loss difference (about 4 times) between continuous direct feed (SRG) and continuous inverter types and whether transfer under 2 ms suits the load sensitivity.
  • Carry the load, rectifier load and starting inrush data of the UPS capacity selection form into the specification.

Who should read it

Electrical designers and specification engineers selecting UPS for Japanese-standard 200/210 V systems or imported equipment.

Document contents

  1. Product line-up
  2. BACKUPS 1000 series
  3. Parallel-redundant series
  4. SRG series
  5. Single- and three-phase specification tables
  6. Cabinet dimensions
  7. UPS capacity selection form

Publication details

Authors
SanRex (Sansha Electric)
Publisher
SanRex (Sansha Electric)
Year
Year not stated
Document language
Japanese
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

SanRex (Sansha Electric) SanRex UPS catalogue, printed p.4 single/three-phase specification tables. SanRex (Sansha Electric). https://www.sansha.co.jp/products/pdf/UPS-J.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.