Syndome Hercules-RT HE-RT series 1-3 kVA rack/tower UPS catalogue

Original title Syndome HE-RT 1–3kVA technical catalogue, p.2

Syndome

Syndome Hercules-RT HE-RT is a 1, 2 and 3 kVA (output power factor 1.0) true online double-conversion UPS: 80-300 V input, THDi <3%, 97% efficiency in ECO mode.

On this page

Overview

The catalogue presents Syndome's Hercules-RT series of the HE-RT-1K, 2K and 3K models. The series is a true online double-conversion topology with DSP control, IGBT converters and high-frequency PWM. In normal mode voltage and frequency are synchronized to the line, in ECO mode the load is fed via bypass within a programmable range, and in frequency mode both voltage and frequency are controlled. It can start without a battery (AC start) and the batteries are easy to replace.

Capacities are 1 kVA/1 kW, 2 kVA/2 kW and 3 kVA/3 kW (PF 1.0). The input voltage range is 80-300 V (80 V at 0-30% load), frequency 50/60 Hz +/-10%, power factor >=0.99, and generator input is 1.5 times the UPS rating. Output voltage is selectable at 208/220/230/240 V +/-1%, harmonic distortion is below 3% on linear and below 5% on non-linear load (the highlights also state THDv below 1% on linear load), and crest ratio is 3:1.

Overload in line mode is 2 min at 100-110%, 1 min at 110-130% and 3 s above 130%. Efficiency is 89% and 91% in AC mode, above 85% and above 88% in battery mode, and 97% in ECO mode. The battery count is 2, 4 or 6 of 12 V 7/9 Ah by model; backup time is over 15 min (load dependent), recharge to 90% takes 4 hours and charging current is at most 1.5 A. AC to DC transfer time is zero.

Physical and general data: dimensions 438x88x430 mm (1K and 2K) and 438x88x610 mm (3K), weights including batteries 10.5, 17.32 and 27.34 kg, noise below 45 and below 50 dB at 1 m, operating temperature 0-40 °C and humidity 0-95% non-condensing. Interfaces are USB, EPO, RS232 and optional SNMP, relay and RS485 cards. Standards are TIS 1291 Parts 1, 2, 3 (Class C2), ISO 9001 and ISO 14001.

Key points

  1. HE-RT-1K, 2K, 3K: 1, 2, 3 kVA and 1, 2, 3 kW (PF 1.0).
  2. Input voltage 80-300 V (80 V at 0-30% load); frequency 50/60 Hz +/-10%; input PF >=0.99.
  3. Input THDi <3%; output THDv <3% (linear), <5% (non-linear).
  4. Efficiency: AC mode 89%/91%, battery mode >85%/>88%, ECO mode 97%.
  5. Overload: 2 min at 100-110%, 1 min at 110-130%, 3 s above 130%.
  6. Battery: 2/4/6 x 12 V 7/9 Ah; backup >15 min; 90% charge in 4 h; charging current 1.5 A.
  7. Size 438x88x430 mm (1K, 2K) and 438x88x610 mm (3K); weight 10.5-27.34 kg with batteries.
  8. Generator input 1.5 times UPS rating; AC start without battery.

Using it in design

  • With output PF 1.0, compare the load directly in kW; the 3 kVA model gives 3 kW.
  • For generator-fed systems size the generator at 1.5 times the UPS rating and use the wide input window (80-300 V).
  • When taking the 97% ECO efficiency into energy calculations, remember the load is then fed via bypass and assess load sensitivity.
  • In rack layout check the height (88 mm, 2U) and the 3K depth (610 mm); compare weight with batteries against rack load capacity.
  • State the SNMP and relay card options in the specification for monitoring.

Who should read it

Electrical designers and resellers selecting 1-3 kVA rack/tower UPS for edge sites, small server rooms and telecom equipment.

Document contents

  1. System (topology, operation modes)
  2. Performance and user interface
  3. Specification table (HE-RT-1K, 2K, 3K)
  4. Rear panel
  5. International standards

Publication details

Authors
Syndome
Publisher
Syndome
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Syndome Syndome HE-RT 1–3kVA technical catalogue, p.2. Syndome. https://www.syndome.com/wp-content/uploads/2024/10/new-catalog-HE-RT.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.