Technical guideFree to readYear not stated

Thycon static transfer switches STSt and STSi (100-3000 A)

Original title THYCON Static Transfer Switches brochure

THYCON

The Thycon brochure compares the thyristor STSt (200-2800 A, fault transfer under 5 ms, 99% efficiency) and the IGCT STSi (300-2000 A, under 1 ms, 98.6%) static transfer switches.

On this page

Overview

Thycon is an Australian power-electronics manufacturer active since 1968. The brochure presents two classes of static transfer switch (STS) from 100 to 3000 A: the STSt, using bi-directional thyristors, and the STSi, using integrated gate commutated thyristors (IGCT). An STS feeds a load needing a single AC supply by selecting one of several sources; if one supply fails it transfers the load automatically to an alternative source, and manual selection is also possible.

Both classes interrupt the supply statically the moment a source failure is detected, isolate the load and reconnect it to the alternative source. Break-before-make transfer keeps the two sources truly independent so the failure of one does not affect the other. Thycon's Point of Wave transfer technology transfers to the same point of the alternative source's waveform, reducing inrush for transformers, drives and motors. The STSt can transfer with up to ±15 degrees of phase shift between sources and the STSi up to ±180 degrees.

The technology comparison table gives: STSt 200-2800 A, 99% efficiency, fault capacity up to 100 kA, fault transfer under 5 ms, MTBF 250,000 hours; STSi 300-2000 A, 98.6% efficiency, fault capacity up to 30 kA, fault transfer under 1 ms, MTBF 200,000 hours. Both have MTTR of 1 hour, fault detection of 0.5 ms, a short-circuit failure mode and 120 s withstand at 150% overload. The 1000% overload withstand is 1000 ms for STSt and 500 ms for STSi.

The brochure also covers control and monitoring (a smart LCD monitor storing the last 200 events, Modbus, SNMP or web interfaces), optional soft-start, container modules and maintenance plans. The design is fuseless with no moving parts; Thycon states it supplies 10-20 times rated current under load fault conditions.

Key points

  1. STSt (thyristor): 200-2800 A, 99% efficiency, up to 100 kA fault capacity, fault transfer under 5 ms, MTBF 250,000 hours.
  2. STSi (IGCT): 300-2000 A, 98.6% efficiency, up to 30 kA fault capacity, fault transfer under 1 ms, MTBF 200,000 hours.
  3. Overload: 150% for 120 seconds (both); 1000% for 1000 ms (STSt) and 500 ms (STSi).
  4. Phase shift between sources: STSt ±15 degrees (user defined), STSi ±180 degrees.
  5. Fault detection time 0.5 ms; break-before-make transfer; manual transfer 0-1 second.
  6. Device safety margin typically 1000% (STSt) and 500% (STSi); allowable crest factor above 5.
  7. Fault current capability 10-20 times rated current; fuseless design with no moving parts.
  8. The monitor stores the last 200 events in non-volatile memory; Modbus, SNMP and web interfaces are options.

Using it in design

  • In dual-feed data halls, when using an STS to remove single points of failure, compare the transfer time (5 ms and 1 ms) against the interruption tolerance of the load input and UPS output.
  • Check the phase shift between sources: STSt is limited to ±15 degrees and STSi tolerates ±180 degrees; where sources are not synchronised, specify the STSi or Point of Wave transfer.
  • Use the fault capacity at the STS output (100 kA and 30 kA) as an input to short-circuit and selectivity studies.
  • For transformer loads, specify the optional soft-start and Point of Wave transfer.
  • State in the architecture requirement that both sources must be independent with high MTBF and low MTTR.

Who should read it

Electrical engineers designing dual-feed data-centre power architectures and project teams writing STS specifications.

Document contents

  1. Principle of operation
  2. STS features and benefits
  3. Applications
  4. STSt and STSi technology
  5. Installation and testing
  6. Reliability and maintenance
  7. Control and monitoring
  8. Options
  9. Thycon STS advantages
  10. Technology comparison

Publication details

Authors
THYCON
Publisher
THYCON
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

THYCON THYCON Static Transfer Switches brochure. THYCON. https://www.thycon.com.au/wp-content/uploads/2024/02/THYCON_STS_brochure-1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.