Technical guideFree to readYear not stated

TMEIC TMUPS E200 UPS specification table

Original title TMEIC TMUPS E200 official specification table

TMEIC

TMEIC TMUPS E200 is a large three-phase UPS family in nine models from 50 to 500 kVA (45-450 kW) at 200-220 V, with 0.9 power factor, ±1% voltage accuracy and THD under 2%.

On this page

Overview

The official TMEIC product page presents the E200 as a high-efficiency, space-saving large-capacity UPS that allows varied system configurations with redundancy. The page is published in Japanese and offers a standard specification table, a single-line diagram and a dimension drawing. The table gives nine discrete models, not a continuous capacity range.

Rated output is listed as 50, 75, 100, 150, 200, 250, 300, 400 and 500 kVA, with matching kW of 45, 67.5, 90, 135, 180, 225, 270, 360 and 450 (power factor 0.9 lagging; 1.0 as an option). Input and output voltage is 200, 210 or 220 V (input ±10%), 50 or 60 Hz, three-phase three-wire. Input frequency is accepted within ±5%.

Performance limits are: voltage accuracy ±1% at 0-100% load, voltage unbalance ±1% at 100% unbalanced load, frequency accuracy ±0.01% in free-running operation, and overload of 125% for 10 minutes and 150% for 1 minute. Transient voltage deviation is ±2% on AC input loss or return, ±5% for a 0-100% load step, ±5% when one unit enters or leaves parallel, and ±5% on bypass-to-UPS transfer; voltage settling time is under 50 ms. Voltage THD is under 2% on linear load and under 5% on a full rectifier load.

Ambient conditions are 0-40 °C (recommended 25 °C), 30-90% relative humidity (non-condensing), indoor installation (free of corrosive gas and dust) and Munsell 5Y7/1 paint. The page gives no efficiency, battery or weight values in this table.

Key points

  1. Nine models: 50, 75, 100, 150, 200, 250, 300, 400 and 500 kVA; 45-450 kW equivalent.
  2. Input and output 200/210/220 V, three-phase three-wire, 50 or 60 Hz; input voltage ±10%.
  3. Power factor 0.9 lagging; 1.0 as an option.
  4. Voltage accuracy ±1% (0-100% load); frequency ±0.01% (free running).
  5. Overload: 125% for 10 minutes and 150% for 1 minute.
  6. Transients: ±2% on mains loss; ±5% on load step; ±5% on parallel entry/exit; ±5% on bypass transfer; settling under 50 ms.
  7. Voltage THD: under 2% on linear load and under 5% on rectifier load.
  8. Ambient 0-40 °C (recommended 25 °C), 30-90% RH, indoor.

Using it in design

  • On a 200-220 V system take kW capacity at 0.9 power factor (kVA x 0.9); request confirmation for the 1.0 option.
  • Compare the transient limits (±2% and ±5%) with the voltage tolerance of the critical load.
  • For redundancy in parallel, use the parallel entry/exit deviation and the 50 ms settling time as coordination inputs.
  • Since this page gives no efficiency, battery or weight data, request the general catalogue; keep the 0-40 °C limit in the room layout.

Who should read it

Electrical designers selecting large UPS units, especially engineers working on 200 V class networks.

Document contents

  1. Overview and features
  2. Standard specifications: rated output, AC input, AC output
  3. Overload, transient voltage and waveform distortion
  4. Other: ambient temperature, humidity, location and paint
  5. Outline drawing and general catalogue

Publication details

Authors
TMEIC
Publisher
TMEIC
Year
Year not stated
Document language
Japanese
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

TMEIC TMEIC TMUPS E200 official specification table. TMEIC. https://www.tmeic.co.jp/product/power_electronics/ups/tmups_e200/specification/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.