BVT 32-63 A Three-Phase 19-inch Static Transfer Switch, 3U, Touch Screen
Original title BVT 32A40A45A50A63A three-phase19in STS3U technical page
Huizhou BVT Technology
BVT's 32, 40, 45, 50 and 63 A three-phase 19-inch 3U static transfer switch: fully digital control, under 4 ms power-off transfer, under 10 ms priority transfer and 190-250 Vac input.
On this page
Overview
The product page presents Huizhou BVT Technology's 32, 40, 45, 50 and 63 A three-phase 19-inch static transfer switch (STS) with touch screen. The device is described as fully digitally controlled, with strong interference immunity and fast operation. Power-off transfer takes under 4 ms and priority switching under 10 ms; the figure was tested on a purely resistive load and may be slightly longer with no load. The front panel has a display and indicator lights for STS status; a version that switches live and neutral together is available.
Technical data: rated voltage Ua=Ub=Uc=220 V, input range 190-250 Vac, 50/60 Hz, power factor 1. Automatic transfer thresholds are 190 ±5 Vac on undervoltage, 250 ±5 Vac on overvoltage and 45 ±0.2 Hz and 65 ±0.2 Hz on frequency. Over-limit protection shutdown is at ≤120 Vac or ≥260 Vac and at ≤45 Hz or ≥65 Hz. Load current up to 110% runs continuously; above that the unit shuts down immediately. Dielectric strength is 2 kVAC for 1 min.
Environment: noise below 60 dB at 1 m, ambient temperature -25 to 50 °C, humidity 0-90% non-condensing, IP20, altitude up to 3000 m, with output reduced by 2% per 100 m between 2000 and 3000 m. Protections are input under- and overvoltage, output overload, over-temperature and short circuit.
Key points
- Ratings 32, 40, 45, 50 and 63 A; 3U, 19-inch rack, touch screen.
- Power-off transfer ≤4 ms; priority transfer ≤10 ms (resistive load).
- Rated 220 V (Ua=Ub=Uc), input 190-250 Vac, 50/60 Hz, PF 1.
- Transfer thresholds: 190 ±5 Vac, 250 ±5 Vac, 45 ±0.2 Hz, 65 ±0.2 Hz.
- Overload: continuous up to 110%, immediate shutdown above.
- Ambient -25 to 50 °C, humidity 0-90%, IP20, noise ≤60 dB.
- Altitude ≤3000 m; output falls 2% per 100 m between 2000 and 3000 m.
- A version switching live and neutral together is available.
Using it in design
- In small rooms, place the STS in a 3U rack position between two UPS units for single-corded loads.
- Compare the load's tolerance time with the 4 ms and 10 ms values.
- Because the unit shuts down immediately above 110%, keep continuous load current below the rating.
- Choose the live/neutral switching version where neutral isolation between sources is needed.
- Apply altitude derating (2% per 100 m) for sites above 2000 m.
Who should read it
Electrical engineers designing A/B power transfer for small critical rooms.
Document contents
- Product description and features
- Technical parameters
- Environment and protection functions
Publication details
- Authors
- Huizhou BVT Technology
- Publisher
- Huizhou BVT Technology
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Huizhou BVT Technology BVT 32A40A45A50A63A three-phase19in STS3U technical page. Huizhou BVT Technology. https://www.bvtpower.com/fr/three-phase-sts-amp-sts-cabinet/bvt_32a_40a_45a_50a_63a_three_phase_19_inch_static_transfer_switch_3u_with_touch_screen_164.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.