CNC YCQ6s Automatic Transfer Switch Catalogue, technical data p.2

CNC Electric

CNC Electric YCQ6s series PC-class ATS: 16-630 A, 400 V, 3P/4P, 120 kA conditional short-circuit rating, 0.45 s (100-250 A frames) and 0.6 s (400-630 A) transfer time.

On this page

Overview

CNC Electric's YCQ6s catalogue presents a PC-class automatic transfer switch (ATS) for two-source neutral-earthed systems at AC 50/60 Hz up to 400 V. Rated operating current runs from 16 A to 630 A. When an abnormality is detected in one source it transfers the supply automatically to the other; uses include primary-to-standby transfer, changeover between two load circuits and safe isolation. The standard is IEC 60947-6-1.

The type code combines company code, frame current (100, 160, 250, 400, 630), poles (3P/4P), function type (A basic, B enhanced) and rated current. Current steps are listed as 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160, 180, 200, 225, 315, 400, 500 and 630 A. Utilization categories are AC-31A, AC-33A and AC-33iB.

The technical table gives insulation voltage 690 V, impulse withstand 8 kV, rated operating voltage 400 V, making capacity 10 Ie, conditional short-circuit current 120 kA and control supply AC 230 V. Rated currents per frame: YCQ6s-100 20, 40, 60, 80, 100 A; -160 100, 125, 160 A; -250 200, 250 A; -400 315, 350, 400 A; -630 500, 630 A. Icw (1 s) is 7, 9 and 13 kA; transfer time is 0.45 s and 0.6 s.

The type A controller offers single-phase voltage monitoring, auto-transfer with auto-restoration, passive fire-system interlock and generator start. Type B adds three-phase monitoring, phase-loss, over- and under-voltage detection, auto-transfer without restoration, DC 24 V fire interlock, voltage and frequency monitoring, an LCD and an RS-485 port. Operating conditions are -5 to +40 C, altitude to 2000 m, pollution degree 3.

Key points

  1. Rated operating current 16-630 A; frames 100, 160, 250, 400, 630 A; 3P or 4P.
  2. Rated operating voltage 400 V; insulation 690 V; impulse 8 kV.
  3. Conditional short-circuit current 120 kA; making capacity 10 Ie.
  4. Icw (1 s): 7, 9 and 13 kA.
  5. Transfer time 0.45 s (frames 100-250 A) and 0.6 s (400-630 A).
  6. Utilization categories AC-31A, AC-33A, AC-33iB; standard IEC 60947-6-1.
  7. Controller: A basic (single-phase), B enhanced (three-phase, LCD, RS-485, DC 24 V fire interlock).
  8. Operation -5 to +40 C, to 2000 m.

Using it in design

  • Select the ATS current step against load current; no intermediate values exist in the catalogue.
  • Assess the transfer time (0.45-0.6 s) against the load and UPS supply continuity.
  • Coordinate short-circuit withstand (120 kA, Icw) with line fault current and protection selectivity.
  • Choose the type B controller if fire-system interface, generator control and monitoring are needed.
  • Verify local certification and stock separately.

Who should read it

Electrical designers and panel builders selecting ATSs for dual-supply distribution.

Document contents

  1. General
  2. Type designation
  3. Operating conditions
  4. Technical data
  5. Controller specifications
  6. Terminal description

Publication details

Authors
CNC Electric
Publisher
CNC Electric
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CNC Electric CNC YCQ6s Automatic Transfer Switch Catalogue, technical data p.2. CNC Electric. https://cncele.com/uploads/YCQ6s-Automatic-Transfer-Switch-Catalogue.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.